K-WANG
The module can be directly connected to the Profibus DP bus, which provides switch inputs for connecting PNP3 line sensors.
Each input has a short-circuit protection function, with a yellow and a red LED indicating ON or overload status.
GE FANUC IC676PBO082 output module
IC676PBO082
8 inputs, DC
Supply voltage
Module power supply 18-30 VDC
Internal current consumption
Auxiliary power supply
<100 mA (from bus power supply)
18-30 VDC
Output circuit (8) DC actuator
Output voltage 18-30 VDC
Output current 2.0A per circuit, short circuit protection
Switching frequency<500 Hz
Connector
Auxiliary power supply 4-pin M12 connector
Bus M12 connector, anti loosening
Input M12 connector
set up
Address 0-99 (decimal) is controlled by two rotary switches
LED indicator
Bus green/red: normal operation/no communication
Power green/red: normal operation/bus power failure
Output status yellow: Output ON
Shell 60 x 178 x 49.3 (W x H x D)
Protection level NEMA4, IP 67
Working temperature -25 ° C to+60 ° C
Working humidity 95%
Hybrid switch module (IP67)
The module can be directly connected to the Profibus DP bus for connecting switch inputs and driving switch actuators.
Both input and output have short-circuit protection function. Each input channel indicates ON or short-circuit status through a yellow and a red LED, and each output is connected
There is a green/red dual color LED indicating ON or short circuit status.
The module is encapsulated with epoxy resin and uses metal connectors, making it very sturdy.
The module is connected to the Profibus DP bus through an M12 connector. One green and one red indicator light indicate the online/offline status of the module, and the module supports up to
The communication rate of the module automatically matches the communication rate of the main station at 12Mbps. The module address can be set through two rotary switches, which can be set
From 0 to 99.
The power supply is connected through a 4-pin M12 connector. The green power LED indicates that the module is powered normally.
In order to configure the module software, a GSD file is attached to the module.
Recommended cable connectors:
Profibus:IC676ACC004、IC676ACC005
Characteristics of switch mixed module
The input of the switch quantity is used to connect the PNP3 line sensor
24VDC, maximum load 2.0A switch output
• Input and output short-circuit protection function
Automatic detection of communication speed
M12 connectors are used for bus and input/output connections
M12 connector is used for connecting bus power supply and auxiliary power supply
Compliant with NEMA4, VDE0106 standards and IEC protection level IP67
• Maximum communication speed of 12 Mbps
Characteristics of switch mixed module
IC676PBM442
DC 4 inputs/4 outputs
Supply voltage
Bus power supply 18-30 VDC
Internal current consumption
Auxiliary power supply
<100 mA (from bus power supply)
18- 30 VDC
Input circuit (4) PNP 3-wire sensor
Input voltage 18-30 VDC (from bus power supply)
Input current of 5 mA per channel, short circuit protection
Input delay ON: 3.1 ms
OFF:4.1 ms
Output circuit (4) DC actuator
Output voltage 18-30 VDC
Output current 2.0A per circuit, short circuit protection
Switching frequency<500 Hz
Connector
Bus and auxiliary power supply
Bus
input
4-pin M12 connector
M12 connector, anti loosening
M12 connector
set up
Address 0-99 (decimal) can be accessed through two rotary switches located under the protective cap
LED indicator
Bus green/red: normal operation/no communication
Power Supply
Input status
Green/Red: Normal operation/Bus power failure
Yellow/Red: Input ON/Short Circuit
Output status yellow/red: Output ON/short circuit
Shell 60 x 178 x 49.3 (W x H x D)
Protection level NEMA 4 and IEC IP 67
Working temperature: 0 ° C to+55 ° C (32 ° C to+131 ° F)