ABB 3BSE008538R1 High Voltage Inverter Spare Parts
For compliance with the protection objectives of theGerman EMC Act (EMVG) in systems and machines, the
following EMC standards must be
satisfied:
For emitted interference, the following apply:
EN 61000-6-3 Specialised basic standard for emissions in light industry can
be satisfied with special features (mains filters, screened
power cables) in the lower rating range *(EN 50081-1).
EN 61000-6-4 Specialised basic standard for emissions in industry *
For interference immuni
(EN 50081-2).
ty, the following apply:
EN 61000-6-1 Specialised basic standard for interference immunity in
residential areas *(EN 50082-1).
EN 61000-6-2 Specialised basic standard for interference immunity in
industry. If this standard is satisfied, then the EN 61000-6-1
standard is automatically satisfied as well *(EN 50082-2).
* The old generic standards are given in brackets
Product Standard EN 61800-3
EMC standard for drive systems (PowerDriveSystem),
interference immunity and emissions in residential
areas, enterprise zones with light industry and in
industrial facilities.
This standard must be complied with in the EU for
satisfying the EMC requirements for systems and
machines!
Standards
Second environment (industry) with PDS categories C3, C4 EN 61800-3
Not applicable EN 61000-6-3
Satisfied On customer's request Satisfied EN 61000-6-4
Satisfied EN 61000-6-2
EN 61000-6-1
PDS category C3 PDS category C4 Classification
The following overview utilises
the terminology and indicates
the action required in
accordance with Product
Standard
EN 61800-3
For the DCS880 series, the
limit values for emitted
interference are complied with,
provided the measure
indicated is carried out. PDS of
category C2 (formerly
restricted distribution in first
environment) is intended to be
installed and commissioned
only by a professional (person
or organization with necessary
skills in installing and/or
commissioning PDS including
their EMC aspects).
For power converters without
additional components, the
following warning applies:
This is a product of category
C2 under IEC 61800-3:2004.
In a domestic/residential
environment this product may
cause radio interference in
which case supplementary
mitigation measures my be
required.
The field supply is not depicted
in this overview diagram. For
the field current cables, the
same rules apply as for the
armature-circuit cables.
M M M M M M
Supply transformer for a
residential area (rating
normally ≤ 1.2 MVA)
Earthed 400 V network
with neutral conductor ;
3~ ≤ 400 A
Operation at low-voltage network together with
other loads of all kinds, apart from some kinds
of sensitive communication equipment.
Line reactor +
Y-capacitor Line reactor
Converter Converter
Mains filter
Earthed
neutral
Medium-voltage network
Industrial zone
Line reactor
Converter
M M M M
Converter
transformer
Converter
transformer
with earthed
iron core
(and earthed
screen where
appropriate)
I > 400 A
and / or
U > 500 V
Operation with separate power converter transformer. If there
are other loads at the same secondary winding, these must be
able to cope with the commutation gaps caused by the power
converter. In some cases, commutating reactors will be
required.

Converters size H5 configuration using FEX-425-Int field exciter
Wiring the drive according to this diagram offers the highest degree of monitoring functions done by the drive.
Field converters FEX-425-Int are equipped with their own synchronization and must be supplied from
independent mains supply voltage max. 500 V (single-phase or 3-phase).