2 Function Profile
2.1 Measurements of Power Parameters
Measurements of power parameters include 3-phase Voltage Measurements, 3-phase
Current Measurements, power factor Measurements, then calculate other extended
power parameters such as power, Kilowatt-hour, etc..
Current,Zero-sequence Current
la,lb, lc, In
Line_line Voltage /Phase Voltage
Uab, Ubc,Uca / Ua, Ub, Uc
3-phase Power Factor*
Pfa,PFb,PFc,LD(lead),LG(lag)
System Frequency and Power FactorF,PF
System Power
P. Q
3-phase Frequency
Fa,Fb, Fc
3-phase Active Power*
Pa, Pb, Pc
3-phase Reactive Power*
Qa, Qb, Qc
3-phase Apparent Power*
Sa, Sb, Sc
3-phase Active Kilowatt-hour*
KWH,KWHa, KWHb,KWHc
3-phase Reactive Kilowatt-hour*
KWARH,KWARHa,KWARHb,KWARHc
*Voltage & Current Measurements
Measured voltage signals are obtained through collecting and processing, and the true
RMS of 3 line_line voltage or phase voltage is displayed on the screen of PMC16.we
adopt direct input if the measured voltage is 0.4KV, and use voltage transformer as
input if the measured voltage is 0.69KV-35KV.
PMC16 allows for a voltage measurement of up to 999999V.
Measured current signals are obtained through collecting and processing, and the true
RMS of 3-phase current is displayed on the screen of PMC16.we adopt direct input if
the measured current is no more than 5A,and use current transformer as input if the
measured current is above 5A.
PMC16 allows for a current measurement of up to 32000A.
The secondary circuit current of the zero-sequence current transformer used in zero-
sequence current measurements is0.02-1A. Measured current signals are obtained
through collecting and processing, and the trueRMS of zero-sequence current is
displayed on the screen of PMC16.