Core functions and hardware features
Built in measuring transformer: through-hole diameter of Φ 18mm; L1/L2/L3/N passes through the transformer, and PE protection wire is strictly prohibited from passing through the transformer window.
Two level alarm threshold
Main alarm (I2 { Delta n1} ): 30~500 mA, measurement bandwidth 0-700 Hz;
Pre alert: Choose one of two options by dialing the code, which is 50%/100% of the main alarm value.
Adjustable delay
Main alarm delay: potentiometer adjustment 0-10 seconds;
Warning delay: Select 0 seconds/1 second for dialing.
Two independent alarm relays, each with one set of switching contacts; Set NO normally open/NC normally closed for contact logic dialing;
Fault memory latch: Alarm status latch is saved and needs to be reset and cleared;
TEST/RESET composite button
Short press<1 s: RESET reset alarm;
Long press>2 seconds: TEST device self-test;
Supports external T/R terminals and external test reset buttons.
status indicator
ON green power light: always on when powered on; Over range flicker;
ALARM yellow warning light: reaching the main alarm constant light; Flashing when reaching the 50% warning threshold;
LED bar chart: displays the percentage (0-100%) of the measured residual current relative to the set value (I2 { Delta n1} ).
Analog output M+/M ---: outputs a 0-100% proportional signal (0-400 μ A), which can be connected to an external pointer measuring instrument;
Equipped with lead sealable transparent protective cover plate; Independent auxiliary power supply; Compliant with IEC 60755 Type-B standard.
Application scenarios
Used for TN and TT grounding distribution systems, 2/3/4 line AC-DC hybrid circuits:
Variable frequency speed regulation drive equipment;
UPS uninterruptible power supply, six pulse rectification, unidirectional rectification with filtering, battery charger;
Perform AC/DC mixed residual current monitoring on normal uncharged conductors (N neutral wire, PE wire).
Working principle: Built in core transformer collects circuit vector and residual current; The leakage exceeds the set threshold, and after a set delay, the relay will activate; Alarm latch, manual reset required; Real time observation of leakage percentage using a light column. This device only serves as a monitoring output dry contact and does not have a tripping power output. It requires an external contactor and PLC to achieve circuit disconnection.
Panel coding and potentiometer configuration
potentiometer
T/s: main alarm response delay, adjustable range 0-10 seconds;
I Δ n × 1/× 10: Set the main alarm current level and use range dialing to achieve 30-500 mA.
DIP dip switch
Warning trigger threshold: A=50% (I2 { Delta n1} ); B=100 % (I_{Delta n1});
Warning delay: A=1 s; B=0 s;
Relay contact mode: A=NO normally open; B=NC normally closed;
Measurement range gear: 30 mA/50 mA gear selection.
Terminal Definition
A1/A2: Auxiliary power supply Us, it is recommended to equip the circuit with 6A fuses;
M+/M ---: Analog output of external measuring instruments;
T/R: External test reset button;
11-12-14: Main alarm relay conversion contact;
21-22-24: Pre alarm relay conversion contact.

Type-B current detection capability (IEC 60755-2)
Current type Action current range
50Hz AC 0.5~1 × (I2 { Delta n} )
Pulsating DC (positive and negative half waves, phase controlled half waves) 0.5 ~1.4 × (I2 { Delta n} )
Overlay 6mA smooth DC half wave current of 0.5~1.4 × (I2 { Delta n} )
Pure smooth DC residual current 0.5 ~2 × (I2 { Delta n} )
Key technical parameters
Relay output: 2 sets of conversion contacts; NO/NC configurable, fault memory enabled;
Contact rated voltage: AC250V/DC300V;
Connection capability AC/DC 5A;
Breaking capacity: AC230V cos φ=0.4 is 2A; DC220V L/R=0.04s is 0.2A;
The electrical lifespan is 12000 cycles.
Environment and Machinery
Working temperature -25 ℃~+70 ℃; Storage -40 ℃~+75 ℃; Climate level 3K5;
The impact and vibration meet the requirements of IEC 60068 series; EMC complies with EN 61543 and EN 61000-6-4;
Installation: DIN rail IEC 60715, can also be fixed with M4 screws; Polycarbonate shell UL94-V0;
Protection level: internal IP30; Wiring terminal IP20;
Dimensions (mm): Width 99 x Height 73 x Depth 65; Weight ≤ 350 g;
Wire cross-sectional area: Hard wire 0.2-4 mm ²; Soft wire 0.2-2.5 mm ².
Ordering model (different auxiliary power supply versions)
Model Power Supply Us Material Number Remarks
RCMA475LY AC 230 V B 9404 2002 Industrial+Civil General
RCMA475LY-13 AC 90-132 V B 9404 2004 Industrial+Civil General
RCMA475LY-21 DC 9.6-84 V B 9404 2014 for industrial applications only
RCMA475LY-23 DC 77-286 V B 9404 2015 for industrial applications only
Optional accessories for matching
9604-4241: 96 × 96mm external display meter, reading 0-100% residual current;
RK170 signal converter: Input 0-400 μ A, output 0-10 V/0/4-20 mA isolated analog signal, connected to PLC system.
Important usage points
The PE protection ground wire must not pass through the built-in transformer window, otherwise the measurement will fail; Only pass L1/L2/L3/N through the through-hole window.
Fault alarm status is locked and needs to be reset to clear; Power outage will not clear the latch alarm.
The TEST button is for local self check testing and is not equivalent to circuit leakage protection testing.
Belonging to a monitoring device, there is no power trip output, and an external contactor/PLC must be connected to cut off the circuit.
M+/M - output without electrical isolation; When connecting to the automation system, it is essential to use the RK170 isolation converter.
Execution standards
IEC 62020, IEC 60755 Amendment 2 (Type-B).