K-WANG

+086-15305925923
Service expert in industrial control field!
NameDescriptionContent
Adequate Inventory, Timely Service
pursuit of excellence 
Ship control system
Equipment control system
Power monitoring system
Current position:
新闻动态
newS
   
Brand

Basler DECS-250 Digital Excitation Control System Manual

From: | Author:Wang | Time :2026-06-11 | 425 visit: | 🔊 Click to read aloud ❚❚ ▶ | Share:


Basler DECS-250 Digital Excitation Control System Manual

Product General Information

1. Product model and communication type

Two mainstream models:

LN2SA1C: equipped with ControlNet communication;

LN2SA1D: equipped with Ethernet/IP DLR (Device Ring Network) communication;

The device can be paired with Rockwell RSLogix 5000 software to complete parameter programming and control.

2. Classification of core functions

(1) Excitation regulation mode (four main modes)

AVR automatic voltage regulation: mainstream mode, stable generator terminal voltage;

FCR excitation current manual adjustment: manually control the excitation current;

PF power factor regulation: constant unit power factor;

VAR reactive power regulation: Constant reactive power output of the unit.

(2) Auxiliary control function

Soft start: The voltage ramp builds up smoothly, and the initial voltage and rise time can be set;

Excitation limit: OEL over excitation limit, UEL under excitation limit, to protect the generator from operating in a safe range;

Low frequency compensation (V/Hz): prevents overheating of the iron core under low frequency conditions;

Line voltage drop compensation: compensates for the voltage loss of long-distance transmission lines;

Automatic mode tracking: No disturbance transition during multi-mode switching;

Redundant automatic switching: seamless switching when the primary and backup devices fail.

(3) Grid connection and load distribution

Supporting parallel operation of generators, providing three compensation methods: reactive power adjustment, cross current (differential) compensation, and active load balancing; Simultaneously supporting the synchronous grid connection function of single/double circuit breakers.

(4) Complete protection function (following power standards, labeled with ANSI protection code)

Full fault protection for generator and excitation system: demagnetization (40), reverse reactive power (40Q), phase sequence error (47), overcurrent (51), overvoltage (59), undervoltage (27), excitation overvoltage (59F), voltage transformer disconnection (60FL), frequency abnormality (81O/81U), reverse power (32R), excitation diode fault, permanent magnet generator (PMG) power loss, etc.

(5) Measurement function

Real time acquisition and display: a complete set of electrical parameters including three-phase voltage/current, active/reactive/apparent power, power factor, frequency, excitation voltage/current, electrical energy (kWh/kvarh/kVAh), synchronization parameters, diode ripple, load deviation, etc.

3. Hardware input/output

input

Voltage sampling: single-phase/three-phase generator voltage, single/double bus voltage (connected to VT transformer);

Current sampling: three-phase generator current, cross current (CT transformer, compatible with 1A/5A specifications);

Analog quantity: ± 10V remote set point;

DC control power supply, PMG excitation power supply, remote excitation enable.

output

Main excitation output: PWM power output, continuous 15A DC;

Relay contacts: Fault relays, redundant relays, cross current relays (all normally open contacts);

Load sharing interface: used for active power sharing among multiple units.

communication interface

Redundant RS-232 (DB9): primary and backup device linkage tracking;

ControlNet/Ethernet/IP: interface with PLC;

USB、 Network port: Factory testing only, not available to users.


Installation specifications

1. Receipt and Storage

Check the part number and appearance upon arrival, and immediately contact the logistics if there is any damage; Temporary storage should be placed in a dry and dust-free original packaging.

2. Installation environment and mechanical requirements

Environmental level: Pollution level 2, overvoltage category II;

Requirements for hazardous locations: Equipment must be installed in cabinets with an IP54 rating or higher, and cannot be installed outdoors naked; ATEX/IECEx Zone 2、 The North American Class I Div 2 scenario must strictly follow the explosion-proof wiring rules;

Installation posture: It must be installed vertically, otherwise the heat dissipation will fail and the equipment will age prematurely;

Space gap: left and right ≥ 63.5mm, up and down ≥ 101.6mm;

Transformation adaptation: Provide adapter board (part number 9440311102), which can directly replace old CGCM/BECGCM modules.

3. General requirements for wiring

Wire: Unified use of copper core wire, temperature resistance ≥ 105 ℃, voltage resistance ≥ 600V;

Grounding: The grounding terminal (56) of the chassis must use * * ≥ 3.3mm ² (12AWG) * * copper wire for single point grounding, and multiple devices must have independent grounding bars;

Shielded wire: Shielded twisted pair cables are preferred for voltage, current, communication, and excitation circuits, and the shielding layer is grounded according to terminal specifications;

CT safety rules: Open circuit is strictly prohibited on the secondary side of current transformers, and short-circuit terminals must be installed.

4. Terminal definition and wiring

(1) Left terminal block (core functional terminal)

Divide load sharing, excitation enable, shield grounding, generator/bus voltage sampling, current sampling, cross current circuit, control power supply, PMG power supply, excitation power output, chassis grounding, etc., and clarify the range of wire diameters suitable for each terminal.

(2) Right side interface

RS-232 (DB9): Redundant communication, using crossover lines, defining pins such as transmit/receive and ground;

ControlNet: Dual BNC interface (redundant networking);

Ethernet/IP DLR: dual RJ45 ring network interface;

USB/Ethernet port: factory specific, factory disabled.

5. Various circuit wiring schemes

Control power supply: DC 18~32V (nominal 24V), connected to BAT+/- terminal;

PMG working power supply: supports single-phase/three-phase, can be output from permanent magnet machine or generator (requires voltage transformer VT);

Excitation output: EXC+/- is the PWM power output, and redundant systems require parallel freewheeling diodes in the excitation winding;

Voltage sampling: supports multiple VT connections including single-phase, delta, three wire/four wire star, and dual bus;

Current sampling: three-phase CT connection, PSS function must be configured with three-phase current;

Cross current compensation: Multiple units are connected in parallel with a dedicated CT circuit for reactive power sharing, which can adjust the impedance of the circuit through an external resistor;

Remote analog input: ± 10V signal is used for remote constant value adjustment;

Remote excitation enable: 24V DC switch quantity control excitation switching.

6. Electrical parameters in hazardous areas

Clearly define the maximum voltage, current, power, and cable capacitance/inductance limits for the intrinsic safety circuit. The default parameters for the cable are 60pF/ft and 0.2 μ H/ft, which need to be matched with the parameters of the associated equipment.

Operating principle and operation

1. Hardware architecture

Integrated microprocessor ADC/DAC、 Various acquisition circuits, excitation power units, relays, and multiple communication modules use flash memory to store parameters.

2. Detailed explanation of the four major excitation regulation modes

Each mode is equipped with PID regulation algorithm, which can independently configure proportional, integral, derivative, and total gain; Simultaneously supporting internal set point tracking and mode switching rate adjustment.

3. Parallel operation compensation function

Reactive power regulation: When the load increases, the voltage drops proportionally, suitable for grid connected units;

Cross current compensation: Multiple units are connected in parallel to achieve equal distribution of reactive power, and the circuit gain is adjusted to adapt to different working conditions;

Line voltage drop compensation: compensates for the voltage loss of long-distance lines.

4. Limiting function (core protection)

(1) V/Hz low frequency limit

Double turning point, double slope adjustable curve, automatic voltage drop when frequency decreases, to prevent overheating of the generator core.

(2) OEL overexcitation limit

There are two modes: offline (single machine) and online (grid connected), each with high/medium/low current thresholds and delays, and a counter to prevent repeated overexcitation and burning of the excitation winding.

(3) UEL under excitation limit

Segmented line characteristics prevent generator phase loss and overheating of the end iron core. The curve can be customized according to multiple points of active power.

5. Comprehensive protection logic

All faults are divided into two categories: alarm and trip: excitation overvoltage, reverse reactive power, and PLC fault will directly cut off excitation; All fault states are uploaded to the PLC through communication tags, and fault relays can customize triggering conditions. Additional feature protection: Excitation diode monitoring, determining diode open/short circuit by detecting current ripple frequency.

6. Synchronous grid connection function

Supports three modes: automatic synchronization, allowed synchronization, and synchronization verification; Adapt to single/double busbars, different phase sequences/wiring groups, and can set voltage, frequency, phase locking windows and closing delays, while supporting empty busbar closing logic.

7. Load sharing

Active power sharing: Through the interaction of 0-5V analog signals, multiple units can evenly share the active load, and the adjustment rate and deviation limit can be set;

Reactive power sharing: Utilizing cross current circuits to achieve reactive power distribution in parallel units.

8. Redundant system

The main and backup DECS-250 devices track parameters in real-time through RS-232. In the event of a main device failure/disconnection, the backup device will take over without disturbance; Equipped with redundant relays to switch excitation output.

9. Measurement function

High precision collection of various electrical quantities and cumulative values of electrical energy, with overflow rules for electrical energy data and support for zeroing operations.


Parameter configuration

1. Configuration prerequisites

RSLogix 5000+RSNetWorx software is required to collect basic data such as generator nameplate, VT/CT ratio, excitation parameters, and motor characteristic curves in advance.

2. Module creation and key setting

Add 1407-CGCM module to the ControlLogix controller, supporting three electronic key modes: fully matched/compatible/disabled, to prevent module mismatches.

3. Configuration page (multi tab pagination)

All parameters are paginated by function, and each type of parameter has a range limit. After modification, some parameters need to be restarted/disabled for excitation to take effect:

Generator parameters: rated voltage, current, power, excitation parameters;

Transformer parameters: VT/CT wiring method, transformation ratio;

Excitation settings: soft start, excitation overvoltage, loss of current threshold;

V/Hz, OEL, UEL curve parameters;

PID gain: proportional/integral/derivative parameters of each regulating circuit;

Tracking and switching rate: mode tracking, redundant tracking, set point change rate;

Synchronization parameters: voltage/frequency/phase locking, bus offset compensation;

Protection settings: thresholds and delays for overcurrent, overvoltage, undervoltage, frequency, reverse power, etc;

Fault relays: Customize which faults trigger relay outputs.

4. Data classification

Configuration table: Basic parameters of the equipment, which can only be written when the excitation is turned off;

Non periodic table writing: parameters such as gain and compensation can also be modified during excitation operation.


Startup and Debugging

1. Safety preparation

Power off and hang up before homework, and take anti-static measures; The CT secondary side must be short circuited.

2. Essential tools

Programming computer, communication network card, dual channel recorder, voltage/current simulation source.

3. Step by step debugging process

Appearance and wiring inspection;

Power on, verify the control power supply and network communication status;

Static testing: Simulate voltage/current signals, verify sampling and protection functions;

Redundancy function test: manually switch between primary and backup machines to verify the switching logic;

Real machine debugging: Start the unit, test FCR and AVR modes in sequence, and set PID parameters;

Synchronous grid connection test: Verify the closing logic in the test position and normal position;

Full functional verification of parallel load, various limiters, and diode protection;

Finally archive all configuration parameters.


Software interface

1. Five communication data tables (based on ControlNet CIP protocol)

Periodic reading (input table): real-time status, all fault indicators, synchronization information, measurement values (time critical data);

Periodic writing (output table): mode selection, constant value, excitation enable, fault reset, synchronization command;

Non periodic reading: full measurement data, auxiliary parameters (non real time);

Non periodic writing: gain, voltage compensation, energy reset;

Configuration table: Fixed parameters at the bottom layer of the device.

2. Communication rules

Due to different firmware versions, there may be differences in the length of the data table, and it is necessary to match the message length;

The configuration table can only be written when the excitation is turned off, and non periodic writing is not limited by the excitation state;

Define a large number of tags corresponding to each state, parameter, and fault, which can be directly called in the PLC program.

3. Data format and range

Clearly define the data types, units, and value ranges of all analog and switch quantities, as well as the calculation and overflow rules for accumulated electrical energy.


Troubleshooting

Classify fault phenomena, causes, diagnostic methods, and solutions according to functional modules, covering the entire scenario:

Abnormal regulation of FCR/AVR/PF/VAR;

Adjustment, cross current, and line compensation faults;

Abnormal operation of OEL/UEL limiter;

Active load sharing failure;

Synchronization and grid connection failure;

Inaccurate measurement data;

ControlNet network malfunction (interpretation of indicator light status);

Redundant switching failure;

Various types of protection misoperation/refusal.

Network indicator lights: distinguish the on/off/flashing/red/green status of A/B channels and module status lights, corresponding to fault types (address duplication, link failure, module fatal error, etc.).


Technical specifications

1. Power parameters

Control power supply: DC 18~32V (nominal 24V);

Working power supply (PMG/parallel input): distinguish the AC input range corresponding to the three excitation outputs of 32V/63V/125V;

2. Sampling circuit

Voltage sampling: 100~600Vac, each phase load < 1VA;

Current sampling: 1A/5A CT compatible, maximum 30A, load<1VA.

3. Excitation output

Continuous output of 15ADC; 10 second strong excitation 30Adc; Distinguish the minimum excitation resistance corresponding to different output voltages.

4. Accuracy indicators

AVR: steady-state accuracy ± 0.1%, full load ± 0.25%;

FCR、 Accuracy of reactive power and power factor circuits;

Dynamic indicators such as temperature drift and response time.

5. Protection and functional parameters

Organize all action thresholds, delays, and adjustment ranges for protection; Soft start V/Hz、 The parameter range for various compensations.

6. Environment and Machinery

Test standards for working temperature, humidity, vibration resistance, impact, salt spray, dielectric strength, etc.

7. Certification and Compliance

Explosion proof certification: UL, CSA, IECEx, ATEX (Class I Div 2/Zone 2);

Environmental protection: EU RoHS, China RoHS, with a total environmental protection service life of 40 years, in compliance with the WEEE directive;

Safety regulations: CE, cULus, etc.


Overcurrent characteristic curve

Built in 17 national/American standard inverse time and timed overcurrent curves, benchmarking the characteristics of traditional electromechanical relays such as ABB and GE;

Provide formulas for trip and reset calculations, as well as a table of curve constants;

Provide a conversion table between the electromechanical relay and the time scale of this equipment;

Supports voltage lockout overcurrent function, and can adjust the action setting according to the voltage ratio.

  • ABB BRC410 SPBRC410 Harmony Bridge Controller
  • ABB PFCL201CE-50kN 3BSE006699D0005 Pressductor PillowBlock Load Cell
  • ABB 5SHY3545L0009 3BHB013085R0001 IGCT Module
  • Wika IPT10 - Process Pressure Transmitter
  • Omron SK20-C1DT-D - Programmable Controller PLC Unit
  • Foxboro Eckardt (Schneider) AE214 - Field Indicator Digital Display Meter
  • Omron CJ1W-OD232 - Transistor Output Unit PLC Module
  • Jetter JX2-IO16 - Digital Input Output Module PLC
  • SEFI ACS 48.6A-NS - Power Supply Unit
  • Schneider (Telemecanique) XBTF011110 - Magelis Membrane Keyboard Overlay
  • Siemens 6ES5246-4UA41 - Simatic S5 Positioning Module
  • Siemens 6SL3120-2TE13-0AA3 - Sinamics S120 Dual Motor Module Inverter
  • SEW Eurodrive MAS51A005-503-50 - Movidyn Servo Drive Controller
  • Record ATE 20 - Automatic Door Brake Motor
  • Record ATE STA 21 - Automatic Door Brake Motor
  • Sanyo Denki R2AA06040FXP02 - AC Servo Motor
  • Omron NX-ID4442 - DC Digital Input Unit PLC Module
  • Schneider (Telemecanique) XBTGT2330 - Magelis Advanced Touch Panel HMI
  • ABB DX561-A1 - AC500 Digital Input Output PLC Module
  • SEW Eurodrive MC07B0004-2A3-4-00 - Movitrac B AC Frequency Inverter Drive
  • Schneider (Telemecanique) FT20CBCL030 - Connection Communication Cable
  • Visions AXFR 600601 - Gap Control Side Board PCBA
  • Allen Bradley 1797-CEC-A-C01 - Flex Ex Communication Interface Adapter
  • Siemens 6ES5095-8MC03 - Simatic S5 Programmable Controller CPU
  • Tectrol / Pitney Bowes TC53S-1392 - Power Supply Unit
  • Bronkhorst P-702C-FAC-88-Z - Digital Mass Flow Controller
  • Allen Bradley 1757-SRM - ControlLogix Redundancy Module
  • Neste 0635-107 - Control Board for SLX Automatic Sliding Door
  • RSF Elektronik MS 2x.x4 MO - Linear Encoder Sensor
  • Pro-face GP37W2-BG41-24V - Graphic Terminal Operator Panel HMI
  • Allen Bradley 2711P-RP1 - PanelView Plus Logic Module HMI
  • ABB (Asea Brown Boveri) GNT0144700R0004 - Power Supply Electronic Board Module
  • SEW Eurodrive MC-LTE-B-0008-2B1-1-40 - Movitrac LTE AC Frequency Inverter Drive
  • Siemens 3RK1301-0AB10-0AA4 - Direct Starter Modular Motor Starter
  • Yaskawa SGDB-15VD - Servopack Servo Drive Amplifier
  • National Instruments NI 9421 - 8-Channel C Series Digital Input Module
  • Yaskawa SGDB-10VD - Servopack Servo Drive Amplifier
  • National Instruments NI 9476 - 32-Channel C Series Source Digital Output Module
  • Pitney Bowes R782000 - Turbojet Controller Board PCBA
  • Lika IT65-Y-1000BND2 - Incremental Encoder Sensor
  • Came 002ZT6 - Control Panel Board for Gear Motors
  • Desin HS-300/7500 - Multivariable Process Controller Unit
  • Pilz PNOZ mc1p - Modular Safety Relay Controller
  • Innovative Robotics PTNR2-2-NES - Controller Interface Board Module
  • Schneider Electric (Telemecanique) TSXCB4020 - Printer Communication Link Cable
  • Wika IPT10 - Process Pressure Transmitter
  • Schneider Electric (Modicon) TSXDMF342A - Extension Digital Analog Module for TSX17 PLC
  • Omron F150-KP - Vision System Cursor Key Pack Console
  • National Instruments BNC-2110 - Shielded Connector Block Accessory
  • Bosch Rexroth (Indramat) CSH01.2C-SE-EN2-EN2-CCD-NN-S-FW - Servo Drive Control Panel Interface Module
  • GHM / Gefran / Baumer GHM510573A/1000 - Incremental Encoder Sensor
  • National Instruments NI 9425 - 32-Channel C Series Digital Input Module
  • Schneider (Telemecanique) STBDDO3705 - Digital Output Module STB
  • Siemens 6EP1436-1SH01 - Regulated Power Supply Unit
  • Schneider Electric (Modicon) TSXFPP20 - Fipway PCMCIA Communication Board
  • April QMB 3202 - PLC Output Card Module with Parameter Surveillance
  • Siemens 6ES5240-1AA12 - Simatic S5 Communication Processor Module
  • Midi Engineering MI907A - Stepper Motor Midi Amplifier Driver
  • Schneider Electric (Telemecanique) TSXAEZ414 - TSX Series Analog Input Module
  • Schneider (Telemecanique) TSX17-20 - TSX17 Compact PLC Controller Unit
  • Siemens 6ES5955-3LC14 - Simatic S5 Modular Power Supply Unit
  • Schneider (Telemecanique) ATV66U72N4 - Altivar 66 AC Frequency Inverter Drive
  • Omron NX-OD4256 - Transistor Output Unit PLC Module
  • Yaskawa / Omron SGDH-04AE-OY - Sigma II Servo Drive 400W
  • RSF Elektronik MS 20.04-2M - Linear Encoder Scale Sensor
  • ITT GMW (Metrosx) DAA288-240 A - LED Message Display Board
  • Allen Bradley 1757-SRM - ControlLogix Redundancy Module
  • Sensorex Alpha-LSE - Display Inclinometer Indicator
  • Omron NX-DA3603 - Analog Output Unit PLC Module
  • Grundig Electronic NRP 02 - Power Supply Control Unit Module
  • ProSoft Technology RLX-FHES-F - RadioLinx Industrial Wireless Hotspot Router
  • Omron NX-EIC202 - EtherCAT Coupler Unit PLC Module
  • Omron NX-TS3201 - Temperature Sensor Input Unit PLC Module
  • Omron CQM1-CPU41-V1 - Sysmac CQM1 PLC CPU System
  • April CPU5001 - PLC CPU Processing Unit
  • Yaskawa JZDP-D008-020-E - Linear Servo Motor Actuator
  • Bronkhorst P-702C-FAC-88-Z - Digital Mass Flow Controller
  • Allen Bradley 2711-K3A17L - PanelView 300 Operator Terminal HMI
  • Schneider (Telemecanique) TSXAEM411 - TSX Series Analog Input Module
  • Schneider Electric (Telemecanique) XBTGT5330 - Magelis Advanced Touch Panel HMI
  • Siemens 6ES5928-3UA12 - Simatic S5 Central Processing Unit PLC
  • Schneider (Telemecanique) TSXSUP65 - Power Supply Module
  • Schneider (Telemecanique) TSXLES61 + TSXLES60 - TSX Series Fine Line Box Local Module
  • Siemens 6SE6440-2AD23-0BA1 - Micromaster 440 AC Frequency Inverter Drive
  • National Instruments NI 9205 - 32-Channel C Series Analog Input Module
  • Yaskawa CIMR-PCC42P2 - Varispeed AC Frequency Inverter Drive
  • ABB PM554-T-A1 - AC500 PLC CPU Module
  • National Instruments cDAQ-9178 - 8-Slot CompactDAQ USB Chassis Backplane
  • Allen Bradley 1786-RPA - ControlNet Repeater Adapter Module
  • Allen Bradley 1770-KFD - DH-485 Communication Interface Module
  • Grundig Electronic NSP 02 - Power Supply Control Unit Module
  • Teq Q07.K3S.002A - Control Panel Logic Board
  • Allen Bradley 1300-ITSSC - Signal Converter Interface Module
  • Omron CQM1H-CPU51 - CQM1H Modular PLC System
  • ProSoft Technology 4207-DFNT-MCM - ProLinx Industrial Gateway Module
  • Schneider Electric TSXSCP114 - RS485 PCMCIA Communication Board
  • Grundig NGE 01 - Power Supply Unit
  • Grundig NZP 03 - Power Supply Unit
  • Siemens 6ES5246-4UA41 - Simatic S5 Positioning Module
  • Danaher / Atlas Copco / Socapel SAM-PA-400-30-E - Servo Power Supply Controller Unit
  • Klöckner Moeller EM4-101-DD1 - Easy Control Relay Module
  • Bosch Rexroth DKC-10.3-012-3-MGP-01VRS - Indramat Digital Servo Controller Drive
  • Schneider (Telemecanique) XBTGT2110 - Magelis Touch Panel HMI with Cutter
  • Berger Lahr (Sig Positec) WD3-004.1802 - Stepper Motor Controller Driver
  • ProSoft Technology MVI56-WA-EIP - ControlLogix Wireless EtherNet/IP Communication Module
  • Allen Bradley 1794-ACNR15 - Flex I/O ControlNet Adapter Module
  • Fanuc A06B-6096-H201 - Servo Amplifier Module
  • Panasonic MSDA083A1 - AC Servo Driver Amplifier
  • Teq Q07.K3P.003B - Control Panel Logic Board
  • Schneider (Telemecanique) XBTH002010 - Magelis Operator Terminal HMI
  • Wika IPT10 - Process Pressure Transmitter
  • Teq Q07.A4P.001A - Control Panel I/O Module Board
  • Teq Q07.A3L.003A - Control Panel Module I/O Board
  • Siemens 6ES5246-4UA31 - Simatic S5 Positioning Module
  • Mitsubishi / Harmonic Drive HC-KFS43 - AC Servo Motor with Harmonic Reducer
  • Mitsubishi HC-KFS43 - AC Servo Motor
  • SES Store Electronic Systems 37120/120 - VLF Radio Transmitter Label System
  • Siemens 6SE9213-6BA40 - Micromaster AC Frequency Inverter Drive
  • Rosemount 1151DP5S22 - Differential Pressure Transmitter
  • Siemens 6FM1470-4AA20 - Simatic FM 470 Positioning Module Processor
  • Yaskawa / Omron SGDM-01ADA - Sigma II Servo Drive 100W
  • ProSoft Technology RLX-IHW-E - RadioLinx Industrial Wireless Hotspot Router
  • Vickers / Moog BRM-4S-20A - Brushless Servo Motor Drive
  • Yaskawa JZDP-D008-019-E - Linear Servo Motor Actuator
  • Siemens 7MF4032-1DA00-1AA6-Z - Pressure Transmitter
  • Parker OEM770T - Stepper Servo Drive Controller
  • Schneider (Telemecanique) XBTPM027010 - Magelis Operator Panel HMI
  • Schneider Electric (Telemecanique) TSXSCM2214 - Communication Module PCMCIA Card