K-WANG

+086-15305925923
Service expert in industrial control field!
NameDescriptionContent
Adequate Inventory, Timely Service
pursuit of excellence 
Ship control system
Equipment control system
Power monitoring system
Current position:
新闻动态
newS
   
Brand

Basler DECS-250 Digital Excitation Control System Manual

From: | Author:Wang | Time :2026-06-11 | 288 visit: | 🔊 Click to read aloud ❚❚ ▶ | Share:


Basler DECS-250 Digital Excitation Control System Manual

Product General Information

1. Product model and communication type

Two mainstream models:

LN2SA1C: equipped with ControlNet communication;

LN2SA1D: equipped with Ethernet/IP DLR (Device Ring Network) communication;

The device can be paired with Rockwell RSLogix 5000 software to complete parameter programming and control.

2. Classification of core functions

(1) Excitation regulation mode (four main modes)

AVR automatic voltage regulation: mainstream mode, stable generator terminal voltage;

FCR excitation current manual adjustment: manually control the excitation current;

PF power factor regulation: constant unit power factor;

VAR reactive power regulation: Constant reactive power output of the unit.

(2) Auxiliary control function

Soft start: The voltage ramp builds up smoothly, and the initial voltage and rise time can be set;

Excitation limit: OEL over excitation limit, UEL under excitation limit, to protect the generator from operating in a safe range;

Low frequency compensation (V/Hz): prevents overheating of the iron core under low frequency conditions;

Line voltage drop compensation: compensates for the voltage loss of long-distance transmission lines;

Automatic mode tracking: No disturbance transition during multi-mode switching;

Redundant automatic switching: seamless switching when the primary and backup devices fail.

(3) Grid connection and load distribution

Supporting parallel operation of generators, providing three compensation methods: reactive power adjustment, cross current (differential) compensation, and active load balancing; Simultaneously supporting the synchronous grid connection function of single/double circuit breakers.

(4) Complete protection function (following power standards, labeled with ANSI protection code)

Full fault protection for generator and excitation system: demagnetization (40), reverse reactive power (40Q), phase sequence error (47), overcurrent (51), overvoltage (59), undervoltage (27), excitation overvoltage (59F), voltage transformer disconnection (60FL), frequency abnormality (81O/81U), reverse power (32R), excitation diode fault, permanent magnet generator (PMG) power loss, etc.

(5) Measurement function

Real time acquisition and display: a complete set of electrical parameters including three-phase voltage/current, active/reactive/apparent power, power factor, frequency, excitation voltage/current, electrical energy (kWh/kvarh/kVAh), synchronization parameters, diode ripple, load deviation, etc.

3. Hardware input/output

input

Voltage sampling: single-phase/three-phase generator voltage, single/double bus voltage (connected to VT transformer);

Current sampling: three-phase generator current, cross current (CT transformer, compatible with 1A/5A specifications);

Analog quantity: ± 10V remote set point;

DC control power supply, PMG excitation power supply, remote excitation enable.

output

Main excitation output: PWM power output, continuous 15A DC;

Relay contacts: Fault relays, redundant relays, cross current relays (all normally open contacts);

Load sharing interface: used for active power sharing among multiple units.

communication interface

Redundant RS-232 (DB9): primary and backup device linkage tracking;

ControlNet/Ethernet/IP: interface with PLC;

USB、 Network port: Factory testing only, not available to users.


Installation specifications

1. Receipt and Storage

Check the part number and appearance upon arrival, and immediately contact the logistics if there is any damage; Temporary storage should be placed in a dry and dust-free original packaging.

2. Installation environment and mechanical requirements

Environmental level: Pollution level 2, overvoltage category II;

Requirements for hazardous locations: Equipment must be installed in cabinets with an IP54 rating or higher, and cannot be installed outdoors naked; ATEX/IECEx Zone 2、 The North American Class I Div 2 scenario must strictly follow the explosion-proof wiring rules;

Installation posture: It must be installed vertically, otherwise the heat dissipation will fail and the equipment will age prematurely;

Space gap: left and right ≥ 63.5mm, up and down ≥ 101.6mm;

Transformation adaptation: Provide adapter board (part number 9440311102), which can directly replace old CGCM/BECGCM modules.

3. General requirements for wiring

Wire: Unified use of copper core wire, temperature resistance ≥ 105 ℃, voltage resistance ≥ 600V;

Grounding: The grounding terminal (56) of the chassis must use * * ≥ 3.3mm ² (12AWG) * * copper wire for single point grounding, and multiple devices must have independent grounding bars;

Shielded wire: Shielded twisted pair cables are preferred for voltage, current, communication, and excitation circuits, and the shielding layer is grounded according to terminal specifications;

CT safety rules: Open circuit is strictly prohibited on the secondary side of current transformers, and short-circuit terminals must be installed.

4. Terminal definition and wiring

(1) Left terminal block (core functional terminal)

Divide load sharing, excitation enable, shield grounding, generator/bus voltage sampling, current sampling, cross current circuit, control power supply, PMG power supply, excitation power output, chassis grounding, etc., and clarify the range of wire diameters suitable for each terminal.

(2) Right side interface

RS-232 (DB9): Redundant communication, using crossover lines, defining pins such as transmit/receive and ground;

ControlNet: Dual BNC interface (redundant networking);

Ethernet/IP DLR: dual RJ45 ring network interface;

USB/Ethernet port: factory specific, factory disabled.

5. Various circuit wiring schemes

Control power supply: DC 18~32V (nominal 24V), connected to BAT+/- terminal;

PMG working power supply: supports single-phase/three-phase, can be output from permanent magnet machine or generator (requires voltage transformer VT);

Excitation output: EXC+/- is the PWM power output, and redundant systems require parallel freewheeling diodes in the excitation winding;

Voltage sampling: supports multiple VT connections including single-phase, delta, three wire/four wire star, and dual bus;

Current sampling: three-phase CT connection, PSS function must be configured with three-phase current;

Cross current compensation: Multiple units are connected in parallel with a dedicated CT circuit for reactive power sharing, which can adjust the impedance of the circuit through an external resistor;

Remote analog input: ± 10V signal is used for remote constant value adjustment;

Remote excitation enable: 24V DC switch quantity control excitation switching.

6. Electrical parameters in hazardous areas

Clearly define the maximum voltage, current, power, and cable capacitance/inductance limits for the intrinsic safety circuit. The default parameters for the cable are 60pF/ft and 0.2 μ H/ft, which need to be matched with the parameters of the associated equipment.

Operating principle and operation

1. Hardware architecture

Integrated microprocessor ADC/DAC、 Various acquisition circuits, excitation power units, relays, and multiple communication modules use flash memory to store parameters.

2. Detailed explanation of the four major excitation regulation modes

Each mode is equipped with PID regulation algorithm, which can independently configure proportional, integral, derivative, and total gain; Simultaneously supporting internal set point tracking and mode switching rate adjustment.

3. Parallel operation compensation function

Reactive power regulation: When the load increases, the voltage drops proportionally, suitable for grid connected units;

Cross current compensation: Multiple units are connected in parallel to achieve equal distribution of reactive power, and the circuit gain is adjusted to adapt to different working conditions;

Line voltage drop compensation: compensates for the voltage loss of long-distance lines.

4. Limiting function (core protection)

(1) V/Hz low frequency limit

Double turning point, double slope adjustable curve, automatic voltage drop when frequency decreases, to prevent overheating of the generator core.

(2) OEL overexcitation limit

There are two modes: offline (single machine) and online (grid connected), each with high/medium/low current thresholds and delays, and a counter to prevent repeated overexcitation and burning of the excitation winding.

(3) UEL under excitation limit

Segmented line characteristics prevent generator phase loss and overheating of the end iron core. The curve can be customized according to multiple points of active power.

5. Comprehensive protection logic

All faults are divided into two categories: alarm and trip: excitation overvoltage, reverse reactive power, and PLC fault will directly cut off excitation; All fault states are uploaded to the PLC through communication tags, and fault relays can customize triggering conditions. Additional feature protection: Excitation diode monitoring, determining diode open/short circuit by detecting current ripple frequency.

6. Synchronous grid connection function

Supports three modes: automatic synchronization, allowed synchronization, and synchronization verification; Adapt to single/double busbars, different phase sequences/wiring groups, and can set voltage, frequency, phase locking windows and closing delays, while supporting empty busbar closing logic.

7. Load sharing

Active power sharing: Through the interaction of 0-5V analog signals, multiple units can evenly share the active load, and the adjustment rate and deviation limit can be set;

Reactive power sharing: Utilizing cross current circuits to achieve reactive power distribution in parallel units.

8. Redundant system

The main and backup DECS-250 devices track parameters in real-time through RS-232. In the event of a main device failure/disconnection, the backup device will take over without disturbance; Equipped with redundant relays to switch excitation output.

9. Measurement function

High precision collection of various electrical quantities and cumulative values of electrical energy, with overflow rules for electrical energy data and support for zeroing operations.


Parameter configuration

1. Configuration prerequisites

RSLogix 5000+RSNetWorx software is required to collect basic data such as generator nameplate, VT/CT ratio, excitation parameters, and motor characteristic curves in advance.

2. Module creation and key setting

Add 1407-CGCM module to the ControlLogix controller, supporting three electronic key modes: fully matched/compatible/disabled, to prevent module mismatches.

3. Configuration page (multi tab pagination)

All parameters are paginated by function, and each type of parameter has a range limit. After modification, some parameters need to be restarted/disabled for excitation to take effect:

Generator parameters: rated voltage, current, power, excitation parameters;

Transformer parameters: VT/CT wiring method, transformation ratio;

Excitation settings: soft start, excitation overvoltage, loss of current threshold;

V/Hz, OEL, UEL curve parameters;

PID gain: proportional/integral/derivative parameters of each regulating circuit;

Tracking and switching rate: mode tracking, redundant tracking, set point change rate;

Synchronization parameters: voltage/frequency/phase locking, bus offset compensation;

Protection settings: thresholds and delays for overcurrent, overvoltage, undervoltage, frequency, reverse power, etc;

Fault relays: Customize which faults trigger relay outputs.

4. Data classification

Configuration table: Basic parameters of the equipment, which can only be written when the excitation is turned off;

Non periodic table writing: parameters such as gain and compensation can also be modified during excitation operation.


Startup and Debugging

1. Safety preparation

Power off and hang up before homework, and take anti-static measures; The CT secondary side must be short circuited.

2. Essential tools

Programming computer, communication network card, dual channel recorder, voltage/current simulation source.

3. Step by step debugging process

Appearance and wiring inspection;

Power on, verify the control power supply and network communication status;

Static testing: Simulate voltage/current signals, verify sampling and protection functions;

Redundancy function test: manually switch between primary and backup machines to verify the switching logic;

Real machine debugging: Start the unit, test FCR and AVR modes in sequence, and set PID parameters;

Synchronous grid connection test: Verify the closing logic in the test position and normal position;

Full functional verification of parallel load, various limiters, and diode protection;

Finally archive all configuration parameters.


Software interface

1. Five communication data tables (based on ControlNet CIP protocol)

Periodic reading (input table): real-time status, all fault indicators, synchronization information, measurement values (time critical data);

Periodic writing (output table): mode selection, constant value, excitation enable, fault reset, synchronization command;

Non periodic reading: full measurement data, auxiliary parameters (non real time);

Non periodic writing: gain, voltage compensation, energy reset;

Configuration table: Fixed parameters at the bottom layer of the device.

2. Communication rules

Due to different firmware versions, there may be differences in the length of the data table, and it is necessary to match the message length;

The configuration table can only be written when the excitation is turned off, and non periodic writing is not limited by the excitation state;

Define a large number of tags corresponding to each state, parameter, and fault, which can be directly called in the PLC program.

3. Data format and range

Clearly define the data types, units, and value ranges of all analog and switch quantities, as well as the calculation and overflow rules for accumulated electrical energy.


Troubleshooting

Classify fault phenomena, causes, diagnostic methods, and solutions according to functional modules, covering the entire scenario:

Abnormal regulation of FCR/AVR/PF/VAR;

Adjustment, cross current, and line compensation faults;

Abnormal operation of OEL/UEL limiter;

Active load sharing failure;

Synchronization and grid connection failure;

Inaccurate measurement data;

ControlNet network malfunction (interpretation of indicator light status);

Redundant switching failure;

Various types of protection misoperation/refusal.

Network indicator lights: distinguish the on/off/flashing/red/green status of A/B channels and module status lights, corresponding to fault types (address duplication, link failure, module fatal error, etc.).


Technical specifications

1. Power parameters

Control power supply: DC 18~32V (nominal 24V);

Working power supply (PMG/parallel input): distinguish the AC input range corresponding to the three excitation outputs of 32V/63V/125V;

2. Sampling circuit

Voltage sampling: 100~600Vac, each phase load < 1VA;

Current sampling: 1A/5A CT compatible, maximum 30A, load<1VA.

3. Excitation output

Continuous output of 15ADC; 10 second strong excitation 30Adc; Distinguish the minimum excitation resistance corresponding to different output voltages.

4. Accuracy indicators

AVR: steady-state accuracy ± 0.1%, full load ± 0.25%;

FCR、 Accuracy of reactive power and power factor circuits;

Dynamic indicators such as temperature drift and response time.

5. Protection and functional parameters

Organize all action thresholds, delays, and adjustment ranges for protection; Soft start V/Hz、 The parameter range for various compensations.

6. Environment and Machinery

Test standards for working temperature, humidity, vibration resistance, impact, salt spray, dielectric strength, etc.

7. Certification and Compliance

Explosion proof certification: UL, CSA, IECEx, ATEX (Class I Div 2/Zone 2);

Environmental protection: EU RoHS, China RoHS, with a total environmental protection service life of 40 years, in compliance with the WEEE directive;

Safety regulations: CE, cULus, etc.


Overcurrent characteristic curve

Built in 17 national/American standard inverse time and timed overcurrent curves, benchmarking the characteristics of traditional electromechanical relays such as ABB and GE;

Provide formulas for trip and reset calculations, as well as a table of curve constants;

Provide a conversion table between the electromechanical relay and the time scale of this equipment;

Supports voltage lockout overcurrent function, and can adjust the action setting according to the voltage ratio.

  • Siemens 6SL3244-0SA01-1AA0 - SINAMICS G120 Control Unit
  • DANFOSS 175Z2688 - COATEDE CONTROLUNIT VLT5000
  • SIEMENS 6FM1721-3AA20 - Positioning Module
  • REXORTH VTS0605 PVAR S21 - Drive Module
  • BECKHOFF 2915-0000 - Control Module
  • COOPER EATON CGLine 400 40071347901 - CEAG CG Controller
  • SIEMENS 3UF5031-3AN00-1 - SIMOCODE DP Basic Unit
  • SIGMATEK DNC305 05-011-305 - Drive Controller
  • Multivac MV1 10249768 - Control Module
  • SCHNEIDER ELECTRIC MES114 59646 & 59645 - Circuit Breaker Accessory
  • CAMILLE BAUER CAPAX 44-580-0012 - Transmitter
  • HENGSTLER VT360P LS1/TOK - Encoder
  • BURKERT 8792 - 24V DC IP65 / IP67 Positioner
  • SENSOPART V10-OB-A1-W6 - Vision Sensor
  • ALLEN-BRADLEY 1762-L40BXB SER.C REV.J - MicroLogix 1200 Controller
  • HITACHI CPU22-02HC 33025801-2 - CPU Module
  • HITACHI AGH-0 33034810-2 - Control Board
  • PHILIPS AIH110 VER 1.0 - Control Module
  • BAUMULLER DO8000 - Drive Controller
  • B&R PS477 3PS477.9 Rev.C0 - Power Supply
  • ABB ALFA LAVAL 200-CISB - Communication Interface 2 x SatBus
  • Moeller MI4-570-TA1 - HMI Operator Panel
  • ABB ACH550-01-06A9-4+B055 - Variable Frequency Drive
  • ABB TPU2 3HNE00313-1 REV 12 - Teach Pendant Unit
  • Schneider Electric BRS368H130ABA - Stepper Motor
  • Foxboro FCM100E P0972ZA - I/A Series Communication Module
  • Siemens 6ES7 450-1AP00-0AE0 6ES7450-1AP00-0AE0 - Simatic S7 Version:04 Counter Module
  • Schneider Electric ATV320U07N4W - Altivar Machine Drive
  • Priva TouchPoint Flush V06:02 5060002 - Control Panel
  • Lenze ESMD402L4TXA - 4kW SMD Inverter Drive
  • Lenze ESMD402L4TXA - 4kW SMD Inverter Drive
  • Schneider Electric PM210 PM210MG - Powerlogic Power Meter
  • ASCOM U982-DB/1C U982 - Power Supply / Communication Module
  • DYADIC SYSTEMS SCN5-010-050-S03-NA - Servo Cylinder
  • Reliance Electric GMI-S04 - AC/AC CONVERTER 380/400V 50/60Hz 3.9/5.2A
  • Pro-Face GLC150-BG41-XY32KF-24V 3080060 PFXGLC150BDBP - Touch Screen HMI
  • ROFIN RSL TERMINAL V2 0185.01/03 - TERMINAL
  • HONEYWELL R7241E1077 - Burner Control / Amplifier
  • SEW MM22C-503-00 8241201 - 2.2kW Movimot Drive
  • Brand Digital III 50mL - Burette
  • Danfoss 195N0039 VLT2811PS2B20STR1DBF00A00C0 - 2.4kVA VLT Drive
  • SONY LG10-2 EK1 - Digital Gauge Indicator
  • EMERSON SKD3400750 - 7.5kW AC Drive
  • SIEMENS 6AV6 542-0AG10-0AX0 - MULTIPANEL HMI
  • TELEMECANIQUE ATV21HU55N4 - ALTIVAR21 5.5KW Variable Speed Drive
  • MITSUBISHI A985GOT-TBA-EU - GOT900 Touch Screen HMI
  • SCHNEIDER LXM32AD30N4 - Lexium 32 Servo Drive
  • SICK PSR01-1501 M20Z-02550A122 - Safety Laser Scanner
  • GECMA CHALLENGER 15-2-FMO - LITE TOUCH Monitor
  • Uniop EK02 6ZA982 - HMI Operator Panel
  • TELEMECANIQUE ATV18U54M2 - SQUARE D ALTIVAR 18 3kW Drive
  • Schneider Electric ATV312HU75S6 - 7.5kW Altivar 312 Drive
  • Siemens 6GK7243-5DX30-0XE0 6GK7 243-5DX30-0XE0 - Communications Processor
  • Schneider Electric LV432455 VIGI630 - 3POLE Earth Leakage Module
  • Rexroth PSI 6100.750 L1 R911170694-107 - frequency inverter / inverter
  • SWEDISH MICROWAVE AB Ku-Band BDC 138010-45-D0 - Block Downconverter
  • METTLER TOLEDO IND429 IND429-BB30 - Weighing Terminal
  • Siemens 6SL3210-5HE10-4UF0 - Sinamics V90 Servo Drive
  • B&R X20CP0482 Rev.D0 - X20 CPU Module
  • Mitsubishi FR-E720S-110SC-EC FRE720S110SCEC - 31A~11A Drive With Filter
  • ABB ACH580-01-026A-4 - Variable Frequency Drive
  • Siemens 6SL3210-1KE13-2AP1 - SINAMIC G120CDP 1.1kw Drive
  • Schneider Electric TM250D 4P3D LV431440 - Compact NSX250 Circuit Breaker
  • RELIANCE ELECTRIC GD.722.81.00-A 802288-74C - MAXITRON Servo Control Card
  • Uniop EK02 6ZA982 - HMI Operator Panel
  • Siemens 6SE9113-7JA13 - MICRO MASTER Junior 1.5kW Inverter
  • Mitsubishi FR-E720S-110SC-EC FRE720S110SCEC - 31A~11A Drive with Filter
  • Johnson Controls FEC2621 MS-FEC2621-0 - Field Equipment Controller
  • BENDER IR475LYT-429 - A-ISOMETER Insulation Monitor
  • Berger lahr D550 RS15 22.550-00-30b - Stepper Drive
  • Rexroth PSI 6100.750 L1 R911170694-107 - Frequency Inverter / INVERTER
  • KOYO 205 D2-06B-1 D2-240 H2-ECOM D2-08ND3 F2-08TRS - DIRECT LOGIC PLC WITH MODULE
  • TELEMECANIQUE ATV18U54M2 ATV18U54M - SQUARE D ALTIVAR 18 3kW Drive
  • Lenze 471-E1.D - Board / Controller Speed
  • Mitsubishi FR-A740-00038-EC - Frequency Inverter
  • Johnson Controls IOM3723 MS-IOM3723-0 - Input/Output Module
  • CURTIS 1238-5602 - AC Motor Controller
  • FOXBORO P0912XX REV.A - 220VAC Power Supply
  • Siemens 6SE9113-7JA13 - MICRO MASTER Junior 1.5kW Inverter
  • Mitsubishi FR-A740-00038-EC - Frequency Inverter
  • KOYO 205 D2-06B-1 D2-240 H2-ECOM D2-08ND3 F2-08TRS - DIRECT LOGIC PLC WITH MODULE
  • AUTZ M406D-00101 - Servo Motor
  • Lauer PCS095 PG095.508.BB - Operator Panel
  • ABB SCOP45SB/DX232 - SattCon OP45 SB Operator Panel
  • SEW Eurodrive MCH42A0030-5A3-4-00 MDX60A0030-5A3-4-00 - 4.8kVA Movidrive Inverter
  • BENDER IR475LYT-429 - A-ISOMETER Insulation Monitor
  • Johnson Controls FEC2621 MS-FEC2621-0 - Field Equipment Controller
  • Johnson Controls IOM3723 MS-IOM3723-0 - Input/Output Module
  • Berger lahr D550 RS15 22550-00-30b - Stepper Drive
  • SIEMENS 6FX1120-4BD03 6FX11204BD03 5702049304.00 E-Stand: A - Sinumerik Module
  • Allen-Bradley 1771-NIV B - HIGH RESOLUTION ISOLATED ANALOG SERIES Module
  • HONEYWELL XFC2D06001 - Flow Computer / Controller
  • Contraves Varidyn Compact ADB 380.90M - DC Drive 380v - 400v 90A 50kVA
  • Red Lion Control GEM52000 - Control Module
  • Siemens 6ES5 955-3NC13 - modular power supply TYPE:DIN41752
  • Danfoss ICV50 G20Mn50T / 027H5200 - Valve zaw
  • Eberle PLS508 P-814 / 2X EA-88 / A-812 / MT-81 / S-11 - PLC with Modules
  • Siemens 6ES7 314-6CF01-0AB0 6ES7314-6CF01-0AB0 - SIMATIC CPU314C-2 DP
  • EBERLE EM-525-87 EM52487 - ICE DETECTOR BASE UNIT
  • Telemecanique / Schneider TSXRKZ02 - TSX Micro automation plus 7module
  • B&R 5DLSDL.1001-00 - Display Link Receiver
  • Siemens 6FX1120-4BD03 6FX11204BD03 5702049304.00 E-Stand: A - Sinumerik Module
  • ALLEN-BRADLEY 1771-NIV A - HIGH RESOLUTION ISOLATED ANALOG SERIES Module
  • ALLEN-BRADLEY 1771-NIV B - HIGH RESOLUTION ISOLATED ANALOG SERIES Module
  • Contraves Varidyn Compact ADB 380.90M - DC Drive 380V - 400V 90A 50kVA
  • Contraves Varidyn Compact ADB 380.90M - DC Drive 380V - 400V 90A 50kVA
  • Ropex RES-202 - Resistron Temperature Controller
  • HONEYWELL XFC2D06001 - Flow Computer / Controller
  • Telemechanics ATV452U40 - DIMMER ALTIVAR5 SERIES 452 4kW 5HP Frequency Inverter
  • VEGA VEGAPLUS61 PS61.XXAGPHAMAX - Radar Level Sensor
  • BRANSON ULTRASONIC TRANSDUCER - Ultrasonic Transducer
  • Danfoss ICV50 G20Mn50T / 027H5200 - Valve Valvola Zaw
  • Schneider Electric 2001549/1 GALAXY PW 5102851200 NT07 - panler card
  • REXROTH VT3006-36 A - Proportional Valve Amplifier
  • Allen-Bradley 1746-OBP16 SERIES:C - SLC 500 OUTPUT MODULE
  • SCHNEIDER LXM32MD12N4 - Lexium 32 Servo Drive
  • Schneider Electric ATV630U22N4 - 2.2KW Altivar Process Drive
  • Allen-Bradley 1746-OBP16 SERIES:C - SLC 500 OUTPUT MODULE
  • Vanderlande 0E2550-00002... - Bagtrax Integrated Power Module 400V 32A
  • B&R X20CP0410 Rev.D0 - X20 CPU Module
  • VANDERLANDE 0E2550-00002 02EDD2B0100 - BAGTRAX Integrated Power Module 400V 32A
  • Rexroth R061205010 - Linear Bushing / Bearing
  • INDRAMAT TVM1.2-50-220/300-W0-220/380 - Power Supply Module
  • Vanderlande 0E2550-00002... - Bagtrax Integrated Power Module 400V 32A
  • HOMAG KEB 07F5S1A-YA00 09E5T60-1001 - Combivert Inverter WITH KEYPAID AND FILTER
  • Siemens 3RW3047-1BB14 - Soft Starter
  • Sumitomo AF-500 AF502-A40 - 0.4kW Transistor Inverter
  • Sumitomo AF-500 AF502-A40 - 0.4kW Transistor Inverter