K-WANG

+086-15305925923
Service expert in industrial control field!
NameDescriptionContent
Adequate Inventory, Timely Service
pursuit of excellence 
Ship control system
Equipment control system
Power monitoring system
Current position:
新闻动态
newS
   
Brand

Basler DECS-250 Digital Excitation Control System Manual

From: | Author:Wang | Time :2026-06-11 | 9 visit: | 🔊 Click to read aloud ❚❚ | Share:


Basler DECS-250 Digital Excitation Control System Manual

Product General Information

1. Product model and communication type

Two mainstream models:

LN2SA1C: equipped with ControlNet communication;

LN2SA1D: equipped with Ethernet/IP DLR (Device Ring Network) communication;

The device can be paired with Rockwell RSLogix 5000 software to complete parameter programming and control.

2. Classification of core functions

(1) Excitation regulation mode (four main modes)

AVR automatic voltage regulation: mainstream mode, stable generator terminal voltage;

FCR excitation current manual adjustment: manually control the excitation current;

PF power factor regulation: constant unit power factor;

VAR reactive power regulation: Constant reactive power output of the unit.

(2) Auxiliary control function

Soft start: The voltage ramp builds up smoothly, and the initial voltage and rise time can be set;

Excitation limit: OEL over excitation limit, UEL under excitation limit, to protect the generator from operating in a safe range;

Low frequency compensation (V/Hz): prevents overheating of the iron core under low frequency conditions;

Line voltage drop compensation: compensates for the voltage loss of long-distance transmission lines;

Automatic mode tracking: No disturbance transition during multi-mode switching;

Redundant automatic switching: seamless switching when the primary and backup devices fail.

(3) Grid connection and load distribution

Supporting parallel operation of generators, providing three compensation methods: reactive power adjustment, cross current (differential) compensation, and active load balancing; Simultaneously supporting the synchronous grid connection function of single/double circuit breakers.

(4) Complete protection function (following power standards, labeled with ANSI protection code)

Full fault protection for generator and excitation system: demagnetization (40), reverse reactive power (40Q), phase sequence error (47), overcurrent (51), overvoltage (59), undervoltage (27), excitation overvoltage (59F), voltage transformer disconnection (60FL), frequency abnormality (81O/81U), reverse power (32R), excitation diode fault, permanent magnet generator (PMG) power loss, etc.

(5) Measurement function

Real time acquisition and display: a complete set of electrical parameters including three-phase voltage/current, active/reactive/apparent power, power factor, frequency, excitation voltage/current, electrical energy (kWh/kvarh/kVAh), synchronization parameters, diode ripple, load deviation, etc.

3. Hardware input/output

input

Voltage sampling: single-phase/three-phase generator voltage, single/double bus voltage (connected to VT transformer);

Current sampling: three-phase generator current, cross current (CT transformer, compatible with 1A/5A specifications);

Analog quantity: ± 10V remote set point;

DC control power supply, PMG excitation power supply, remote excitation enable.

output

Main excitation output: PWM power output, continuous 15A DC;

Relay contacts: Fault relays, redundant relays, cross current relays (all normally open contacts);

Load sharing interface: used for active power sharing among multiple units.

communication interface

Redundant RS-232 (DB9): primary and backup device linkage tracking;

ControlNet/Ethernet/IP: interface with PLC;

USB、 Network port: Factory testing only, not available to users.


Installation specifications

1. Receipt and Storage

Check the part number and appearance upon arrival, and immediately contact the logistics if there is any damage; Temporary storage should be placed in a dry and dust-free original packaging.

2. Installation environment and mechanical requirements

Environmental level: Pollution level 2, overvoltage category II;

Requirements for hazardous locations: Equipment must be installed in cabinets with an IP54 rating or higher, and cannot be installed outdoors naked; ATEX/IECEx Zone 2、 The North American Class I Div 2 scenario must strictly follow the explosion-proof wiring rules;

Installation posture: It must be installed vertically, otherwise the heat dissipation will fail and the equipment will age prematurely;

Space gap: left and right ≥ 63.5mm, up and down ≥ 101.6mm;

Transformation adaptation: Provide adapter board (part number 9440311102), which can directly replace old CGCM/BECGCM modules.

3. General requirements for wiring

Wire: Unified use of copper core wire, temperature resistance ≥ 105 ℃, voltage resistance ≥ 600V;

Grounding: The grounding terminal (56) of the chassis must use * * ≥ 3.3mm ² (12AWG) * * copper wire for single point grounding, and multiple devices must have independent grounding bars;

Shielded wire: Shielded twisted pair cables are preferred for voltage, current, communication, and excitation circuits, and the shielding layer is grounded according to terminal specifications;

CT safety rules: Open circuit is strictly prohibited on the secondary side of current transformers, and short-circuit terminals must be installed.

4. Terminal definition and wiring

(1) Left terminal block (core functional terminal)

Divide load sharing, excitation enable, shield grounding, generator/bus voltage sampling, current sampling, cross current circuit, control power supply, PMG power supply, excitation power output, chassis grounding, etc., and clarify the range of wire diameters suitable for each terminal.

(2) Right side interface

RS-232 (DB9): Redundant communication, using crossover lines, defining pins such as transmit/receive and ground;

ControlNet: Dual BNC interface (redundant networking);

Ethernet/IP DLR: dual RJ45 ring network interface;

USB/Ethernet port: factory specific, factory disabled.

5. Various circuit wiring schemes

Control power supply: DC 18~32V (nominal 24V), connected to BAT+/- terminal;

PMG working power supply: supports single-phase/three-phase, can be output from permanent magnet machine or generator (requires voltage transformer VT);

Excitation output: EXC+/- is the PWM power output, and redundant systems require parallel freewheeling diodes in the excitation winding;

Voltage sampling: supports multiple VT connections including single-phase, delta, three wire/four wire star, and dual bus;

Current sampling: three-phase CT connection, PSS function must be configured with three-phase current;

Cross current compensation: Multiple units are connected in parallel with a dedicated CT circuit for reactive power sharing, which can adjust the impedance of the circuit through an external resistor;

Remote analog input: ± 10V signal is used for remote constant value adjustment;

Remote excitation enable: 24V DC switch quantity control excitation switching.

6. Electrical parameters in hazardous areas

Clearly define the maximum voltage, current, power, and cable capacitance/inductance limits for the intrinsic safety circuit. The default parameters for the cable are 60pF/ft and 0.2 μ H/ft, which need to be matched with the parameters of the associated equipment.

Operating principle and operation

1. Hardware architecture

Integrated microprocessor ADC/DAC、 Various acquisition circuits, excitation power units, relays, and multiple communication modules use flash memory to store parameters.

2. Detailed explanation of the four major excitation regulation modes

Each mode is equipped with PID regulation algorithm, which can independently configure proportional, integral, derivative, and total gain; Simultaneously supporting internal set point tracking and mode switching rate adjustment.

3. Parallel operation compensation function

Reactive power regulation: When the load increases, the voltage drops proportionally, suitable for grid connected units;

Cross current compensation: Multiple units are connected in parallel to achieve equal distribution of reactive power, and the circuit gain is adjusted to adapt to different working conditions;

Line voltage drop compensation: compensates for the voltage loss of long-distance lines.

4. Limiting function (core protection)

(1) V/Hz low frequency limit

Double turning point, double slope adjustable curve, automatic voltage drop when frequency decreases, to prevent overheating of the generator core.

(2) OEL overexcitation limit

There are two modes: offline (single machine) and online (grid connected), each with high/medium/low current thresholds and delays, and a counter to prevent repeated overexcitation and burning of the excitation winding.

(3) UEL under excitation limit

Segmented line characteristics prevent generator phase loss and overheating of the end iron core. The curve can be customized according to multiple points of active power.

5. Comprehensive protection logic

All faults are divided into two categories: alarm and trip: excitation overvoltage, reverse reactive power, and PLC fault will directly cut off excitation; All fault states are uploaded to the PLC through communication tags, and fault relays can customize triggering conditions. Additional feature protection: Excitation diode monitoring, determining diode open/short circuit by detecting current ripple frequency.

6. Synchronous grid connection function

Supports three modes: automatic synchronization, allowed synchronization, and synchronization verification; Adapt to single/double busbars, different phase sequences/wiring groups, and can set voltage, frequency, phase locking windows and closing delays, while supporting empty busbar closing logic.

7. Load sharing

Active power sharing: Through the interaction of 0-5V analog signals, multiple units can evenly share the active load, and the adjustment rate and deviation limit can be set;

Reactive power sharing: Utilizing cross current circuits to achieve reactive power distribution in parallel units.

8. Redundant system

The main and backup DECS-250 devices track parameters in real-time through RS-232. In the event of a main device failure/disconnection, the backup device will take over without disturbance; Equipped with redundant relays to switch excitation output.

9. Measurement function

High precision collection of various electrical quantities and cumulative values of electrical energy, with overflow rules for electrical energy data and support for zeroing operations.


Parameter configuration

1. Configuration prerequisites

RSLogix 5000+RSNetWorx software is required to collect basic data such as generator nameplate, VT/CT ratio, excitation parameters, and motor characteristic curves in advance.

2. Module creation and key setting

Add 1407-CGCM module to the ControlLogix controller, supporting three electronic key modes: fully matched/compatible/disabled, to prevent module mismatches.

3. Configuration page (multi tab pagination)

All parameters are paginated by function, and each type of parameter has a range limit. After modification, some parameters need to be restarted/disabled for excitation to take effect:

Generator parameters: rated voltage, current, power, excitation parameters;

Transformer parameters: VT/CT wiring method, transformation ratio;

Excitation settings: soft start, excitation overvoltage, loss of current threshold;

V/Hz, OEL, UEL curve parameters;

PID gain: proportional/integral/derivative parameters of each regulating circuit;

Tracking and switching rate: mode tracking, redundant tracking, set point change rate;

Synchronization parameters: voltage/frequency/phase locking, bus offset compensation;

Protection settings: thresholds and delays for overcurrent, overvoltage, undervoltage, frequency, reverse power, etc;

Fault relays: Customize which faults trigger relay outputs.

4. Data classification

Configuration table: Basic parameters of the equipment, which can only be written when the excitation is turned off;

Non periodic table writing: parameters such as gain and compensation can also be modified during excitation operation.


Startup and Debugging

1. Safety preparation

Power off and hang up before homework, and take anti-static measures; The CT secondary side must be short circuited.

2. Essential tools

Programming computer, communication network card, dual channel recorder, voltage/current simulation source.

3. Step by step debugging process

Appearance and wiring inspection;

Power on, verify the control power supply and network communication status;

Static testing: Simulate voltage/current signals, verify sampling and protection functions;

Redundancy function test: manually switch between primary and backup machines to verify the switching logic;

Real machine debugging: Start the unit, test FCR and AVR modes in sequence, and set PID parameters;

Synchronous grid connection test: Verify the closing logic in the test position and normal position;

Full functional verification of parallel load, various limiters, and diode protection;

Finally archive all configuration parameters.


Software interface

1. Five communication data tables (based on ControlNet CIP protocol)

Periodic reading (input table): real-time status, all fault indicators, synchronization information, measurement values (time critical data);

Periodic writing (output table): mode selection, constant value, excitation enable, fault reset, synchronization command;

Non periodic reading: full measurement data, auxiliary parameters (non real time);

Non periodic writing: gain, voltage compensation, energy reset;

Configuration table: Fixed parameters at the bottom layer of the device.

2. Communication rules

Due to different firmware versions, there may be differences in the length of the data table, and it is necessary to match the message length;

The configuration table can only be written when the excitation is turned off, and non periodic writing is not limited by the excitation state;

Define a large number of tags corresponding to each state, parameter, and fault, which can be directly called in the PLC program.

3. Data format and range

Clearly define the data types, units, and value ranges of all analog and switch quantities, as well as the calculation and overflow rules for accumulated electrical energy.


Troubleshooting

Classify fault phenomena, causes, diagnostic methods, and solutions according to functional modules, covering the entire scenario:

Abnormal regulation of FCR/AVR/PF/VAR;

Adjustment, cross current, and line compensation faults;

Abnormal operation of OEL/UEL limiter;

Active load sharing failure;

Synchronization and grid connection failure;

Inaccurate measurement data;

ControlNet network malfunction (interpretation of indicator light status);

Redundant switching failure;

Various types of protection misoperation/refusal.

Network indicator lights: distinguish the on/off/flashing/red/green status of A/B channels and module status lights, corresponding to fault types (address duplication, link failure, module fatal error, etc.).


Technical specifications

1. Power parameters

Control power supply: DC 18~32V (nominal 24V);

Working power supply (PMG/parallel input): distinguish the AC input range corresponding to the three excitation outputs of 32V/63V/125V;

2. Sampling circuit

Voltage sampling: 100~600Vac, each phase load < 1VA;

Current sampling: 1A/5A CT compatible, maximum 30A, load<1VA.

3. Excitation output

Continuous output of 15ADC; 10 second strong excitation 30Adc; Distinguish the minimum excitation resistance corresponding to different output voltages.

4. Accuracy indicators

AVR: steady-state accuracy ± 0.1%, full load ± 0.25%;

FCR、 Accuracy of reactive power and power factor circuits;

Dynamic indicators such as temperature drift and response time.

5. Protection and functional parameters

Organize all action thresholds, delays, and adjustment ranges for protection; Soft start V/Hz、 The parameter range for various compensations.

6. Environment and Machinery

Test standards for working temperature, humidity, vibration resistance, impact, salt spray, dielectric strength, etc.

7. Certification and Compliance

Explosion proof certification: UL, CSA, IECEx, ATEX (Class I Div 2/Zone 2);

Environmental protection: EU RoHS, China RoHS, with a total environmental protection service life of 40 years, in compliance with the WEEE directive;

Safety regulations: CE, cULus, etc.


Overcurrent characteristic curve

Built in 17 national/American standard inverse time and timed overcurrent curves, benchmarking the characteristics of traditional electromechanical relays such as ABB and GE;

Provide formulas for trip and reset calculations, as well as a table of curve constants;

Provide a conversion table between the electromechanical relay and the time scale of this equipment;

Supports voltage lockout overcurrent function, and can adjust the action setting according to the voltage ratio.

  • Woodward 8272-796 - Real Power Sensor Module 115/230v-ac
  • Woodward 5463-873 - NetCon Output Module
  • Woodward 8271-567 - Load Sensor Module 120/208v-ac
  • Woodward Type UG-8 P/N 8522-300 EG - Governor R.P.M 1075-1650 With Motor Groschopp
  • WOODWARD 9905-971 REV J - LINKNET 16 CHANNEL DISCRETE INPUT MODULE
  • WOODWARD 8280-3014 - 723 PLUS DIGITAL CONTROL REV NEW
  • Woodward 505DE - Digital Control System
  • Woodward 5453-750 - Ethernet Interface FTM
  • Woodward 9907-018 Rev H - 2301A Load Sharing & Speed Control
  • WOODWARD 5420-1080 V4.3 - BOARD-PPA WITHBOX
  • Woodward b 8271-347SP - 2301 speed control
  • Woodward 9905-795 Rev B - Digital Synchronizer and Load Control
  • Woodward 9905-377 Rev. A - 2301A Load Sharing and Speed Control
  • WOODWARD 8272-582 - Generator speed control module
  • WOODWARD 9907-247 REV K - 828 DIGITAL CONTROL UNIT
  • WOODWARD 5466-353 REV C - NETCON MAIN CHASSIS TRANSCEIVER
  • Woodward Type UG-8 P/N 8524-708 - Governor 760-1560 Governor R.P.M
  • WOODWARD 9907-247 REV K - 828 DIGITAL CONTROL UNIT
  • WOODWARD 8440-1831 REV. H - EASYGEN3000 3200-5 - WITHOUT ACCESSORIES
  • WOODWARD 8444-1002 REV G - UMT1 MEASURING TRANSDUCERS
  • Woodward 5410-312C - Digital Marine Control Printed Circuit Board
  • Woodward 9905-799 REV F - Digital Synchronizer & Load Control , V#456
  • Woodward 9907-014 - 2301A for controller
  • Woodward Type UG-8 P/N B522-446 - Governor R.P.M 500-1200
  • WOODWARD 8272-221 REV.B - DIGITAL REFERENCE UNIT
  • Woodward 8901-037 - Booster Servomotor Single
  • WOODWARD 8444-1019 REV G - UMT 1 MEASURING TRANSDUCER
  • WOODWARD 1767-367 Z21 WK 0920702 - GOVERNOR MOTOR 2700 RPM KM 58-20 K 230V
  • WOODWARD 9905-972 Rev:G - LINKNET 6 CHANNEL 4-20mA OutPut
  • Woodward E8250-501 - Actuator Governor
  • WOODWARD 5466-258 REV M - SIMPLEX DISCRETE I/O MODULE
  • WOODWARD 5501-470 REV E - NETCON CPU MODULE
  • Woodward 8406-120 rev H - egcp-2 digital control
  • Woodward 8440-1799 - Easygen-350 Rev B
  • Woodward 8440-1878 - DSLC-2 Digital Synchronizer Load Control
  • Woodward 5464-843 - Cpu Processor Module
  • WOODWARD 8440-1409 Rev. J - MFR2 MDE Synchronization & Protection MSP
  • Woodward 9907-014 - controller
  • WOODWARD 9907-173 - LOAD SHARING MODULE 120V
  • WOODWARD 8440-1831 REV. K - EASYGEN 3200-5 - WITHOUT ACCESSORIES
  • Woodward 9905-969 - LinkNet Module LinkNet 6C 4-20ma in w/24v
  • Woodward 8520-498 - Governor Type UG-8 Governor R.P.M 850-1650
  • WOODWARD 5466-257 REV.-C - NETCON 5000 MODEL REMOTE TRANSCEIVER I/O MODULE
  • WOODWARD 8800 - 1001 REV-C - DSS-2, 2 CHANNEL DIGITAL SPEED SWITCH
  • WOODWARD 5501-467 REV. C - MICRONET SIMPLEX POWER SUPPLY
  • Woodward 8273-584 - Atlas-ii Digital Control
  • Woodward 8440-1019 b - spm-d10 synchronizing system
  • Woodward CSC3SUWA REV K - CSC3SUWA Controller
  • Woodward 5441-693 Rev B - Digital I/O Module
  • WOODWARD DPG-2201-002 REV.D - Governor Onan DIGITAL SPEED CONTROLLER
  • Woodward 9905-377 Rev. A - 2301A Load Sharing and Speed Control
  • WOODWARD 8440-1884K - GENERATOR CONTROLLER EASYGEN-2500-5 REV,K
  • WOODWARD 8404-1006 - Industrial Component
  • WOODWARD 5437-1118 - PROTECHTPS MODULE Relay Bulkhead Panel
  • Woodward 8440 1801 Rev C - Easygen-350-50B/X Genset Control Engine Generator 24VDC
  • WOODWARD 5466-348 - MODULE
  • Woodward 9905-799 REV F - Digital Synchronizer & Load Control , V#456
  • Woodward 9907-018 - 2301A Load Sharing & Speed Control Rev H
  • Woodward GM9412H918-R2 1766-039 REV E - Cruise Control Motor
  • 5466-258 WoodWard - 48 Input 24 Output Discrete I/O, (UPP)
  • WOODWARD 5484-877 - PM MOTOR 24VDC 15RPM
  • Woodward 8272-221 B - Digital Reference Unit
  • Woodward 9905-796 - Digital Synchronizer And Load Control (Rev. H)
  • WOODWARD 5441-645 REV.G - 10AMP RELAY INTERFACE 11459968
  • Woodward 9907-207 - 721 Digital Control 88-132VAC
  • WOODWARD 8272-582 - APM MOTOR CONTROL AC/DC 100~220V
  • Woodward 5464-843 - Cpu Processor Module
  • Woodward 9905-001 L - SPM-A Synchronizer 115/230V 50/60Hz 10W
  • Seg Power Protection PCK4 P/N 8445 1006 A / PCKR-MW - Protection Relay 24VDC
  • Woodward 8405-062 - Actuator
  • Woodward 5464-738 - Industrial Control System
  • Woodward CSC3HUWB - controller
  • Woodward 8272-517 - PM Motor Control 220vac
  • Woodward 8272-582 - APM Motor Control
  • Woodward LR20025 MFR1375M MFR 1 - Controlling
  • Woodward 9905-392 - Proact Driver Model III
  • WOODWARD 8250-774 - ACTUATOR/GOVERNOR
  • Woodward 505DE - Digital Control System
  • Woodward 8280-303 D - 721 Digital Control Rev.G 2.0 AMP 28 VDC
  • WOODWARD DPG-2201-002 REV NEW - DIGITAL CONTROLLER
  • WOODWARD 8272-286 - 2301A LOAD SHARING & SPEED CONTROL MODULE
  • WOODWARD 8440-1884 REV M - GENSET CONTROLLER EASYGEN-2500-5/P1
  • Woodward 9905-797 Rev. M - Digital Sync And Charge Control
  • W0ODWARD ART-01681 - IDS Communicator Control Box
  • Woodward 8273-584 - Digital Control Unit ATLAS-II REV: A 18-32VDC, 60W
  • WOODWARD 5501-470 REV E - NETCON CPU MODULE
  • Woodward 1752 1752-227 - Revision D FireFly Current Load input Engine Control
  • Woodward 8440-1877 - MSLC-2-5 Control
  • Woodward 8271468 - Generator Loading Control (Rev. D)
  • Woodward 9905-387 - Pro Act Driver Model lll (Rev. F)
  • Woodward 9905-363 - Sincronizzatore Digitale E Controllo Carico
  • WOODWARD 8272-583 - APM MOTOR CONTROL
  • WOODWARD EGCP-2 - Digital Generator Control Panel 4-20MA 5V 500HZ
  • Woodward 9905-392 - Proact Driver Model III
  • Woodward 9905-392 - Proact Driver Model III
  • Woodward 8270-007 - Load Signal Control
  • Woodward 8271-651 - Digital Speed Reference
  • WOODWARD 8440-2219 - EASYGEN-2500-5-P1-K49 GENSET CONTROLLER
  • Woodward D8271-394 - 2301 Load Sharing And Speed Control Module 20-40v-dc
  • Woodward 8200-1504 Rev:E - Peak200 Steam Turbine Control Front Panel Mount HVAC
  • WOODWARD 8444-1022 REV F - UMT 1 MEASURING TRANSDUCER
  • WOODWARD 8440-1923 A - EASYGEN-3200-5 CONTROLLER
  • WOODWARD 9907-014 - 2301A controller
  • Woodward 8272-583 - Amp Motor Control DC24V
  • Woodward 9907-147 REV N - ProTech 203 Overspeed Protection System
  • Woodward 8270-417 - 2301 speed sensor
  • Woodward 8272-583 - Amp Motor Control DC24V
  • Woodward 8934-658 - Repair Kit UG8D Governor
  • Woodward 5437-281 - analog module
  • Woodward 8440-2177 A - SPM-D2-10 Digital Synchronising Controller
  • SA-4478 EPS1000 - Speed Switch
  • Woodward 9907-014 Rev: J - 2301A Speed Control
  • Woodward 9907-026 Rev C - Load Sharing Module
  • Woodward B8271-464 H B8271464 - 2301 Speed Control
  • WOODWARD 8440-1667 REV C - SPM-D10 SYNCRONIZING UNIT
  • Woodward 8440-2082 - EASYGEN-3200XT-P1 Engine Generator Control
  • Woodward 8406-120 rev H - egcp-2 digital control
  • WOODWARD SPM-D - SYNCHRONIZING SYSTEM
  • Woodward 8271-651 - Digital Speed Reference
  • WOODWARD 8444-1074 A - MODULE
  • WOODWARD 8440-2050 Rev B - EASYGEN-3200-5 CONTROLLER
  • Woodward 8440-1613 REV E - GCP30 Genset Control Package
  • Woodward 9907-018 - Load Sharing & Speed Controller Rev H 90-240VAC
  • Woodward 5466-315 - module
  • Woodward 9905-204 Rev N - SPM-A synchronizer
  • Woodward XG2 - Protection relay
  • WOODWARD 9907-175 LOAD SHARING MODULE REV A - Load Sharing Module
  • Woodward 9907-166 REV: N - 505E Turbine Control 110V AC/DC