K-WANG
ABB DI810 digital input module
Basic information
Product Model: DI810 (Digital Input Module)
System: ABB Ability ™ System 800xA ®
Article Number: 3BSE008508R1
Mechanical specifications: S800 series
Core functions and features
Channel configuration: 16 channels, supporting 24V DC input, using current sinking signal type.
Isolation design: 16 channels are divided into 2 groups (8 channels per group), and each group is isolated from the ground.
Protection and monitoring:
Each group is equipped with one process voltage monitoring input, and if the voltage disappears, an error signal can be fed back through the Modulus feedback channel.
The input circuit includes current limiting components and EMC protection components, and the sensor power supply can achieve current limiting through MTU.
Status indicator: The front is equipped with F (fault), R (operation), W (warning) indicator lights, and 16 channel "0"/"1" status indicator lights.
Specification parameters
Electrical performance: Input voltage range: "0" state -30~+5 V, "1" state 15~30 V; Input impedance 3.5 k Ω; Filtering time can be selected from 2, 4, 8, 16 ms
Insulation and power consumption: rated insulation voltage of 50 V, dielectric test voltage of 500 V AC; Typical power consumption of 1.8 W;+5 V Modular Bus current consumption of 50 mA,+24 V bus and external no current consumption
Physical specifications: Width 45 mm, Depth 102 mm (including connector 111 mm), Height 119 mm; Weight 0.15 kg; Maximum on-site cable length 600 meters
Compatibility: Compatible with MTU models: TU810, TU812, TU814, TU818, TU830, TU833, TU838, TU850; Key control code AA
Environment and Certification
Working environment: Operating temperature 0~+55 ° C (certification range+5~+55 ° C), storage temperature -40~+70 ° C; relative humidity 5%~95% (no condensation); Pollution level 2, anti-corrosion level ISA-S71.04: G3; Protection level IP20.
Certification compliance: Possessing CE mark and complying with EN 61010 series and UL 61010 series electrical safety standards; Certified for hazardous locations such as C1 Div 2 cULus and ATEX Zone 2; Obtained certification from classification societies such as ABS and BV; Compliant with RoHS and WEEE directives.
Precautions
Installation environment
It needs to be installed in a temperature environment of 0 to+55 ° C (certification range is+5 to+55 ° C), with a storage temperature of -40 to+70 ° C.
The relative humidity of the installation environment should be maintained between 5% and 95% and in a non condensing state, with a pollution level of 2 (in accordance with IEC 60664-1), while also meeting the G3 anti-corrosion level specified in ISA-S71.04.
When installed vertically in a compact MTU, the maximum ambient temperature is 40 ° C (104 ° F).
Mechanical Installation
This module belongs to the S800 series mechanical specifications and needs to be installed in compatible MTU models such as TU810, TU812, TU814, etc.
When installing, pay attention to the size of the module, which has a width of 45mm, a depth of 102mm (including 111mm connectors), and a height of 119mm. Adequate space should be reserved.
Wiring specifications
The maximum on-site cable length is 600 meters (656 yards), and the cable length needs to be controlled within this range during wiring.
The input voltage range is -30.+5V for the "0" state and 15.30V for the "1" state. When wiring, ensure that the input voltage meets this specification.
The input impedance of the module is 3.5k Ω, and impedance matching should be considered when wiring.
Isolation requirements
The 16 input channels of the module are divided into 2 groups, each with 8 channels. Each group is isolated from the ground, and care should be taken not to damage this isolation characteristic when wiring.
The rated insulation voltage of the module is 50V, and the dielectric test voltage is 500V AC. During the wiring process, it is necessary to avoid exceeding this insulation and test voltage.
Other precautions
The sensor power supply can be current limited through MTU, and the wiring should be set correctly according to the actual situation.
The key control code for the module is AA, and compatibility with related equipment must be ensured during wiring and installation