ABB DSRF180A 57310255-AV equipment frame
This section applies to drives that
are delivered in several transport
units and are equipped with a
heating cable.
1. Connect the power supply of the heating cable.
2. Connect the heating cables of two adjoining
transport units with each other (6-4).
3. Fasten the connectors with cable ties.
For further information, see the applica ble wiring diagrams.
The drive is prepared for top or bottom cable entry with one or a
combination of the following cable entries:
• 6-hole cable entry
• Cable entry with EMC plates
• Undrilled Aluminium Plate
6.8.1 6-hole cable entry
Usage
Power cables, ground cables, bonding conductors
Included in delivery
Galvanized plate (1), sealing compound (2)
Cores per cable
6.8.2 Cable entry with EMC plates
Usage
Power cables, ground cables, bonding conductors
Auxiliary power cables, control cables
Included in delivery
Galvanized plate with net-like EMC sleeves (1) and
sealing grommets (2)
EMC cushions (1) on the underside of the EMC
plate if cable entry is used for control cables.
For further information eg, location and
dimensions, see the applicable mechani cal drawings.

The method to prepare the cables for connection to their
corresponding busbars is described below.
6.9.1 Further information 6.9.2 Preparing the cable entry and the cables
Determining the cable length
1. Determine the required length of a cable
between the point of entry and the connection
point inside the cabinet.
2. Cut the cable to the required length before con nection.
Preparing cables for 6-hole entry plates
Prepare the cable termination as illustrated in
6-5: B.
See mechanical drawings for information
on:
• Project-specific cable entry
• Distance between the point of cable
entry and the termination bars
• Busbar and fastening hole dimensions
• Busbar designations
See wiring diagrams for information on:
• Conventions for cross-references and
device identification
6-5
1. Outer cable sheath
2. Grommet
3. Entry plate
4. EMC sleeve
5. Conductor insulation removed to
expose cable shield
6. Cable tie
7. Conductor screen extension to be
connected to PE ground busbar
8. Heat-shrinkable termination
6-5 Preparing power
cables for EMC plates NOTICE
Risk of damage or malfunction!
Waste inside the cabinet can cause damage or mal -
function.
If possible, do not cut cables inside the terminal
compartment. Retrieve any waste which acciden tally dropped into the cabinet.