Product Overview
The Eaton LZM series is a low-voltage molded case circuit breaker and isolating switch, covering 15~1000A, designed for high-density residential, commercial, and industrial power distribution. It is standardized in four compact frameworks to reduce inventory and design costs.
Core parameters
Framework and rated current
Maximum rated current of frame model
LZM1 160A
LZM2 300A
LZM3 630A
LZM4 1000A
Breaking capacity (400/415V)
Basic type: 25kA
Comfort type: 36kA
Standard type: 50kA
Extremes and Standards
Number of poles: 3 poles, 4 poles
Neutral wire protection: * * 100%/60% * * phase current
Execution standard: IEC/EN 60947-2
Release unit
Thermomagnetic release A
Overload: 0.8~1 × In
Short circuit: 6-10 × In
Applicable: Conventional cable and system protection
Electronic release AE
Overload: 0.5~1 × In, with LED indicator
Short circuit: 2~12 × In
Application: High precision, selectivity, and generator protection

Product type
Circuit breaker LZM: overload+short circuit protection, can be equipped with various types of trip and accessories
Isolation switch LN: only has isolation function, can be remotely disconnected, without protective tripping
Attachment system
Auxiliary contacts: standard HIN, fault indication HIA, front snap fit installation
Release attachment
Under voltage trip XU: voltage drop * * 35%~70% * * trip
Split excitation trip XA: remote pulse circuit breaker
Operating attachments
Door link rotating handle: IP66 protection, padlockable
Remote operation XR: two-wire/three wire control, closing delay of 60-100ms
Installation accessories: 35/75mm guide rail buckle, insulation enclosure, spacer block, wiring terminal
Installation and Environment
Installation: front unified position, buckle type, reducing costs
Temperature: -25~+70 ℃, * * 50 ℃ * * Capacity reduction required according to the coefficient
Spacing: The minimum distance between LZM4 and other frames is 15mm
Wiring: Box/Tunnel Terminal, Supports Cu/Al Cable, Maximum 300mm ²
Engineering characteristics
Selectivity: The upper and lower circuit breakers cooperate, and the fault section trips independently without affecting other circuits
Backup protection: LZMN current limiting current is used as the upper protection for high short-circuit current fields
Minimum cross-section of cable
LZM1:≥10mm²
LZM2:≥10mm²
LZM3:≥16mm²
LZM4:≥95mm²
lifespan
Mechanical: LZM1/2: 10000 times; LZM4: 5000 times
Electrical: LZM1/2:200 times under AC-23B; LZM4: 100 times
Key questions and answers
Question 1: How many frame specifications are there for the LZM series? What are the corresponding maximum current and breaking capacity?
Answer: There are a total of four frameworks. LZM1(160A)、LZM2(300A)、LZM3(630A)、LZM4(1000A); The maximum breaking capacity of the entire series can reach 50kA (415V).
Question 2: What are the core differences between thermal magnetic release A and electronic release AE in terms of protection range and applicable scenarios?
Answer: Thermomagnetic A: Overload 0.8~1 × In, short circuit 6~10 × In, low cost, used for conventional cable/system protection; Electronic AE: Overload 0.5~1 × In, short circuit 2~12 × In, equipped with LED and microprocessor, higher accuracy, suitable for selective protection, generators, and high-precision distribution scenarios.
Question 3: How to use LZM circuit breaker in high temperature environment? How to reduce capacity at 50 ℃?
Answer: The device allows operation at * * -25~+70 ℃, with 40 ℃ as the baseline; At 50 ℃, the thermomagnetic type needs to be multiplied by a capacitance reduction factor of 0.93-0.98, while the electronic type LZM4 does not require a capacitance reduction factor; Actual load current=rated current x corresponding temperature coefficient.