Any information generated in the annunciatorunit can be read by a hierarchically superior
system via the serial interface.
Data communication
The annunciator unit is provided with a serial
interface on the rear panel. By means of a bus
connection module type SPA-ZC 17/S or
SPA-ZC 21/S the unit can be connected to the
fibre-optic SPA bus. The bus connection
module type SPA-ZC 21/S is powered from
the host unit, whereas the bus connection
module SPA-ZC 17/S is provided with a
built-in power unit, which can be fed from an
external secured power source. The unit com municates with higher-level data acquisition
and control systems over the SPA bus.
Self-supervision
The annunciator incorporates a sophisticated
self-supervision system which increases the
availability of the device and the reliability of
the system. The self-supervision system con tinuously monitors the hardware and the soft ware of the unit. The system also supervises
the operation of the auxiliary supply module
and the level of the electronics' voltages gen erated by the module.
If a permanent fault is detected, the fault indi cator on the front panel is lit, the output relay
of the self-supervision system operates and
the outputs are blocked.
Auxiliary supply voltage
The auxiliary supply of the relay is obtained
from an internal plug-in type power supply
module. Two auxiliary power module types
are available: type SPGU 240A1 for the sup ply voltage range 80…265 V ac/dc and type
SPGU 48B2 for the supply voltage range
18…80 V dc. The power supply module
forms the internal voltages required by the
annunciator.

Table 1: Alarm channels
Capacity 16 channels
Type of field contact or type of incoming alarm
signal
Make contact (default)
Break contact
Rising edge
Falling edge
Pulse counter, max. 3 Hz, 0...29.999
Field contact voltage 48 V dc ±20%
Loop current of closed field contact circuit 4 mA ±20%
Channel input and reset delay time, field-selectable
values
5 ms, 20 ms (default), 100 ms, 1 s, 5 s, 20 s, 60 s
or 160 s. (Other values possible via the serial
communication.)
Table 2: External acknowledge/reset inputs
Channel acknowledge/reset Make contact
Audible device reset Make contact
The control voltages for the acknowledge/reset
circuits are obtained from the internal supply
48 V dc ±20%
Table 3: Reflash signal outputs
Reflash group alarm outputs 2 relays, NO contact (NC by soldering)
Audible device output 1 relay
Internal self-supervision output 1 relay
Additional field contact follower or group alarm
output relays by means of module SWOM 16A1
16 relays
Rated contact current/breaking voltage 3 A/250 V ac/dc
Breaking capacity for dc currents when the load
time-constant L/R ≤ 40 ms at the voltage levels
48/110/220 V dc
1 A/0.25 A/0.15 A
Table 4: Data communication
Transmission mode Fibre-optic serial bus
Coding ASCII
Data transfer, selectable 4800 or 9600 Bd
Electrical/optical bus
connection module,
powered from the host
unit
for plastic core cables SPA-ZC 21BB/S
for glass fibre cables SPA-ZC 21MM/S
Electrical/optical bus
connection module,
powered from the host
unit or from an external
power source
for plastic core cables SPA-ZC 17BB/S
for glass fibre cables SPA-ZC 17MM/S
Table 5: Auxiliary supply modules
Type of module SPGU 240A1 rated voltages Un 110/120/230/240 V ac
110/125/220 V dc
operative range 80…265 V ac/dc
SPGU 48B2 rated voltages Un 24/48/60 V ac
operative range 18…80 V dc
Power consumption under quiescent/operation
conditions
~10 W/~25 W