K-WANG
ABB HESG324013R0101 216AB61 BINARY OUTPUT * NCS1704
Module Overview
Model and positioning:
Model: HESG324013R0101, belonging to 216AB61 binary output module, used for REG216/REG216 Classic protection system.
Function: Provides 32 binary outputs for controlling relays or signal indications, supports short circuit protection and status indicator light display.
Technical Parameter
Number of output channels: 32, supporting independent control.
Output type: transistor output, supporting short circuit protection and overload protection.
Load capacity
Maximum continuous current: 5 A (DC/AC).
Maximum impulse current (0.5 seconds): 10 A.
Voltage range
DC:24-250 V
-AC:24-240 V
Isolation characteristics: Electrical isolation, isolation voltage ≥ 1 kV AC, to prevent interference and fault crosstalk.
Status indication: The front-end LED indicator displays the output status (lit when activated).
Response time: Typical response time ≤ 30 ms, ensuring fast action.
Short circuit protection: automatic current limiting and shutdown, and can automatically recover after the fault is cleared.
Application scenarios
Protection system interface:
Connect to the parallel bus (B448C) of REG216/REG216 Classic for outputting trip signals, alarm signals, or controlling external devices such as circuit breakers and contactors.
Industrial automation:
Drive trip relays in generator and transformer protection, or serve as signal extension modules in distributed control systems.
Redundant system:
Supports redundant configuration, enhances system reliability, and is suitable for power systems with high availability requirements.
Hardware and Installation
Physical characteristics:
Size: Meets the 19 inch rack installation standard and occupies 1 rack unit (1U).
Terminal type: Removable screw terminal, supporting 4 mm ² wire connection.
Installation method:
Insert the REG216 system rack and communicate with the processor unit (such as 216VC62a) through a parallel bus, supporting hot plugging (power off operation required).
compatibility:
Used in conjunction with input modules (such as 216GW62), processor modules (216VC624), and power modules (216NG6x) of the REG216 series.
Can be configured with
Logical control:
Support configuring output logic through software (such as AND/OR/NOT gates), which can be linked with protection functions (such as overcurrent protection triggering trip output).
Diagnosis and Monitoring:
Built in self-monitoring function to detect output short circuits, overloads, and power failures.
Real time monitoring of output status through HMI or communication interface, supporting event recording and fault code reporting.
Communication protocol:
Compatible with SPA and IEC 60870-5-103 protocols, it can remotely control the output status through Modbus or LON bus.
Ordering and Accessories
Ordering information:
Model: HESG324013R0101 (216AB61 module).
Supporting system: REG216/REG216 Classic protection system, requiring a rack (such as 216MB66) and power module (216NG6x).
Accessories:
System cable (IK61): used for connecting modules, with a length of 2.5 meters or 4 meters to choose from.
Redundant power module: supports dual power input to enhance system power supply reliability.