K-WANG

+086-15305925923
Service expert in industrial control field!
NameDescriptionContent
Adequate Inventory, Timely Service
pursuit of excellence 
Ship control system
Equipment control system
Power monitoring system
Current position:
新闻动态
newS
   
Brand

GE IC697CHS783 Integrators Rack, 17 Slots, Front Mount

From: | Author:Wang | Time :2024-12-19 | 229 visit: | 🔊 Click to read aloud ❚❚ | Share:

GE IC697CHS783 Integrators Rack, 17 Slots, Front Mount

Genius I/O blocks with selectable I/O configuration appear in more than one list. If a
discrete combination block will have inputs only, select it from the “D IN” (F1) list. If it
will have outputs only, select it from the “D OUT” (F2) list. If it will have both inputs
and outputs, select it from the “D MIX” (F3) list. If a block is selected from the wrong list,
or if its I/O type configuration is changed at a later time, a “Genius I/O Type Mismatch” error
will be placed in the PLC Fault Table.

When a block type has been selected from the correct list, press the Enter key. A config uration screen for that block will appear.
For example, this is a configuration screen for a

115 VAC 8 Circuit Grouped I/O block.
You must enter a configuration screen for each device on the bus, although you may
wish to use the default references and configuration selections.
This does NOT configure the characteristics of the Genius I/O blocks themselves. That
separate configuration is normally done using a Hand–held Monitor, but may also be
done using Communication Request instructions in the application program. For in formation about Communication Request instructions, see chapter 5.
With the cursor positioned at the correct Device Number, configure the device type:
Select F1 for a discrete input block or combination block with inputs
only.
Select F2 for a discrete output block, or a combination block with out puts only.
Select F3 for a discrete I/O block with both inputs and outputs. This in cludes blocks configured for “outputs with feedback”.
Select F4 for an analog block that has inputs only.
Select F5 for an analog block that has outputs only.
Select F6 for an analog block with both inputs and outputs.
Select F7 to configure another Bus Controller, a High–speed Counter, a
PowerTRAC Block, a PCIM, GENI, GENA, or “generic” I/O device.

Select F8 to add a remote drop the bus.

A block’s Reference Address is the beginning reference for its inputs and outputs. As

each block is configured, the software selects the correct memory types for that block.
For example, for a discrete block with both inputs and outputs, this address is shown in
the configuration screen as:
Ref Addr : %QInnnnn
For an analog block with both inputs and outputs, this address is shown in the configuration screen as:
Ref Addr : %AQInnnnn
Memor y Type
The memory type shown on the configuration screen cannot be changed. If a discrete
combination block will NOT use the reference types shown (for example, if %QI is
shown, but the block will be configured with a Hand–held Monitor for inputs–only
operation), the block has been selected from the wrong list. The memory type displayed
on this screen must match the memory type selected with the Hand–held Monitor. If it
doesn’t, delete the current entry then re–select the block from the correct list.
Address
The Logicmaster programmer automatically assigns the next available reference address
within a memory type. If the address displayed is not appropriate, a different address
can be entered from the keyboard. Discrete references must begin on a byte boundary
(a byte boundary is a number which is one greater than a multiple of 8, for example: 9,

17, or 25). If you assign a reference address out of sequence, the software will then continue to increment
that number for additional modules. For example, if you assigned the

reference %I0401 to the first input module and it had 16 circuits, the software would
next assign %I0417 or %QI0417 to an input or combination block. You could change this
to a different address. A message appears when the highest available address has been
assigned, although you may have skipped lower addresses.

References for Blocks having both Discrete and Word Inputs: For certain types of Genius I/O blocks
(an example is the High–speed Counter block), the input data that is

routinely broadcast by the block consists of BOTH discrete and word–type data.
For such a block, the configured Reference Address represents three memory locations
(in %I, %Q, and %AI memories) instead of the two (%I and %Q) assigned to other types
of blocks.
For example, a High–speed Counter block has 16 bits of input data, 16 bits of output
data, and 15 words of calculated data. If a High–speed Counter block were configured
to use Reference Address 0049, the following memory locations would be used by the
block:
  • Woodward 8272-796 - Real Power Sensor Module 115/230v-ac
  • Woodward 5463-873 - NetCon Output Module
  • Woodward 8271-567 - Load Sensor Module 120/208v-ac
  • Woodward Type UG-8 P/N 8522-300 EG - Governor R.P.M 1075-1650 With Motor Groschopp
  • WOODWARD 9905-971 REV J - LINKNET 16 CHANNEL DISCRETE INPUT MODULE
  • WOODWARD 8280-3014 - 723 PLUS DIGITAL CONTROL REV NEW
  • Woodward 505DE - Digital Control System
  • Woodward 5453-750 - Ethernet Interface FTM
  • Woodward 9907-018 Rev H - 2301A Load Sharing & Speed Control
  • WOODWARD 5420-1080 V4.3 - BOARD-PPA WITHBOX
  • Woodward b 8271-347SP - 2301 speed control
  • Woodward 9905-795 Rev B - Digital Synchronizer and Load Control
  • Woodward 9905-377 Rev. A - 2301A Load Sharing and Speed Control
  • WOODWARD 8272-582 - Generator speed control module
  • WOODWARD 9907-247 REV K - 828 DIGITAL CONTROL UNIT
  • WOODWARD 5466-353 REV C - NETCON MAIN CHASSIS TRANSCEIVER
  • Woodward Type UG-8 P/N 8524-708 - Governor 760-1560 Governor R.P.M
  • WOODWARD 9907-247 REV K - 828 DIGITAL CONTROL UNIT
  • WOODWARD 8440-1831 REV. H - EASYGEN3000 3200-5 - WITHOUT ACCESSORIES
  • WOODWARD 8444-1002 REV G - UMT1 MEASURING TRANSDUCERS
  • Woodward 5410-312C - Digital Marine Control Printed Circuit Board
  • Woodward 9905-799 REV F - Digital Synchronizer & Load Control , V#456
  • Woodward 9907-014 - 2301A for controller
  • Woodward Type UG-8 P/N B522-446 - Governor R.P.M 500-1200
  • WOODWARD 8272-221 REV.B - DIGITAL REFERENCE UNIT
  • Woodward 8901-037 - Booster Servomotor Single
  • WOODWARD 8444-1019 REV G - UMT 1 MEASURING TRANSDUCER
  • WOODWARD 1767-367 Z21 WK 0920702 - GOVERNOR MOTOR 2700 RPM KM 58-20 K 230V
  • WOODWARD 9905-972 Rev:G - LINKNET 6 CHANNEL 4-20mA OutPut
  • Woodward E8250-501 - Actuator Governor
  • WOODWARD 5466-258 REV M - SIMPLEX DISCRETE I/O MODULE
  • WOODWARD 5501-470 REV E - NETCON CPU MODULE
  • Woodward 8406-120 rev H - egcp-2 digital control
  • Woodward 8440-1799 - Easygen-350 Rev B
  • Woodward 8440-1878 - DSLC-2 Digital Synchronizer Load Control
  • Woodward 5464-843 - Cpu Processor Module
  • WOODWARD 8440-1409 Rev. J - MFR2 MDE Synchronization & Protection MSP
  • Woodward 9907-014 - controller
  • WOODWARD 9907-173 - LOAD SHARING MODULE 120V
  • WOODWARD 8440-1831 REV. K - EASYGEN 3200-5 - WITHOUT ACCESSORIES
  • Woodward 9905-969 - LinkNet Module LinkNet 6C 4-20ma in w/24v
  • Woodward 8520-498 - Governor Type UG-8 Governor R.P.M 850-1650
  • WOODWARD 5466-257 REV.-C - NETCON 5000 MODEL REMOTE TRANSCEIVER I/O MODULE
  • WOODWARD 8800 - 1001 REV-C - DSS-2, 2 CHANNEL DIGITAL SPEED SWITCH
  • WOODWARD 5501-467 REV. C - MICRONET SIMPLEX POWER SUPPLY
  • Woodward 8273-584 - Atlas-ii Digital Control
  • Woodward 8440-1019 b - spm-d10 synchronizing system
  • Woodward CSC3SUWA REV K - CSC3SUWA Controller
  • Woodward 5441-693 Rev B - Digital I/O Module
  • WOODWARD DPG-2201-002 REV.D - Governor Onan DIGITAL SPEED CONTROLLER
  • Woodward 9905-377 Rev. A - 2301A Load Sharing and Speed Control
  • WOODWARD 8440-1884K - GENERATOR CONTROLLER EASYGEN-2500-5 REV,K
  • WOODWARD 8404-1006 - Industrial Component
  • WOODWARD 5437-1118 - PROTECHTPS MODULE Relay Bulkhead Panel
  • Woodward 8440 1801 Rev C - Easygen-350-50B/X Genset Control Engine Generator 24VDC
  • WOODWARD 5466-348 - MODULE
  • Woodward 9905-799 REV F - Digital Synchronizer & Load Control , V#456
  • Woodward 9907-018 - 2301A Load Sharing & Speed Control Rev H
  • Woodward GM9412H918-R2 1766-039 REV E - Cruise Control Motor
  • 5466-258 WoodWard - 48 Input 24 Output Discrete I/O, (UPP)
  • WOODWARD 5484-877 - PM MOTOR 24VDC 15RPM
  • Woodward 8272-221 B - Digital Reference Unit
  • Woodward 9905-796 - Digital Synchronizer And Load Control (Rev. H)
  • WOODWARD 5441-645 REV.G - 10AMP RELAY INTERFACE 11459968
  • Woodward 9907-207 - 721 Digital Control 88-132VAC
  • WOODWARD 8272-582 - APM MOTOR CONTROL AC/DC 100~220V
  • Woodward 5464-843 - Cpu Processor Module
  • Woodward 9905-001 L - SPM-A Synchronizer 115/230V 50/60Hz 10W
  • Seg Power Protection PCK4 P/N 8445 1006 A / PCKR-MW - Protection Relay 24VDC
  • Woodward 8405-062 - Actuator
  • Woodward 5464-738 - Industrial Control System
  • Woodward CSC3HUWB - controller
  • Woodward 8272-517 - PM Motor Control 220vac
  • Woodward 8272-582 - APM Motor Control
  • Woodward LR20025 MFR1375M MFR 1 - Controlling
  • Woodward 9905-392 - Proact Driver Model III
  • WOODWARD 8250-774 - ACTUATOR/GOVERNOR
  • Woodward 505DE - Digital Control System
  • Woodward 8280-303 D - 721 Digital Control Rev.G 2.0 AMP 28 VDC
  • WOODWARD DPG-2201-002 REV NEW - DIGITAL CONTROLLER
  • WOODWARD 8272-286 - 2301A LOAD SHARING & SPEED CONTROL MODULE
  • WOODWARD 8440-1884 REV M - GENSET CONTROLLER EASYGEN-2500-5/P1
  • Woodward 9905-797 Rev. M - Digital Sync And Charge Control
  • W0ODWARD ART-01681 - IDS Communicator Control Box
  • Woodward 8273-584 - Digital Control Unit ATLAS-II REV: A 18-32VDC, 60W
  • WOODWARD 5501-470 REV E - NETCON CPU MODULE
  • Woodward 1752 1752-227 - Revision D FireFly Current Load input Engine Control
  • Woodward 8440-1877 - MSLC-2-5 Control
  • Woodward 8271468 - Generator Loading Control (Rev. D)
  • Woodward 9905-387 - Pro Act Driver Model lll (Rev. F)
  • Woodward 9905-363 - Sincronizzatore Digitale E Controllo Carico
  • WOODWARD 8272-583 - APM MOTOR CONTROL
  • WOODWARD EGCP-2 - Digital Generator Control Panel 4-20MA 5V 500HZ
  • Woodward 9905-392 - Proact Driver Model III
  • Woodward 9905-392 - Proact Driver Model III
  • Woodward 8270-007 - Load Signal Control
  • Woodward 8271-651 - Digital Speed Reference
  • WOODWARD 8440-2219 - EASYGEN-2500-5-P1-K49 GENSET CONTROLLER
  • Woodward D8271-394 - 2301 Load Sharing And Speed Control Module 20-40v-dc
  • Woodward 8200-1504 Rev:E - Peak200 Steam Turbine Control Front Panel Mount HVAC
  • WOODWARD 8444-1022 REV F - UMT 1 MEASURING TRANSDUCER
  • WOODWARD 8440-1923 A - EASYGEN-3200-5 CONTROLLER
  • WOODWARD 9907-014 - 2301A controller
  • Woodward 8272-583 - Amp Motor Control DC24V
  • Woodward 9907-147 REV N - ProTech 203 Overspeed Protection System
  • Woodward 8270-417 - 2301 speed sensor
  • Woodward 8272-583 - Amp Motor Control DC24V
  • Woodward 8934-658 - Repair Kit UG8D Governor
  • Woodward 5437-281 - analog module
  • Woodward 8440-2177 A - SPM-D2-10 Digital Synchronising Controller
  • SA-4478 EPS1000 - Speed Switch
  • Woodward 9907-014 Rev: J - 2301A Speed Control
  • Woodward 9907-026 Rev C - Load Sharing Module
  • Woodward B8271-464 H B8271464 - 2301 Speed Control
  • WOODWARD 8440-1667 REV C - SPM-D10 SYNCRONIZING UNIT
  • Woodward 8440-2082 - EASYGEN-3200XT-P1 Engine Generator Control
  • Woodward 8406-120 rev H - egcp-2 digital control
  • WOODWARD SPM-D - SYNCHRONIZING SYSTEM
  • Woodward 8271-651 - Digital Speed Reference
  • WOODWARD 8444-1074 A - MODULE
  • WOODWARD 8440-2050 Rev B - EASYGEN-3200-5 CONTROLLER
  • Woodward 8440-1613 REV E - GCP30 Genset Control Package
  • Woodward 9907-018 - Load Sharing & Speed Controller Rev H 90-240VAC
  • Woodward 5466-315 - module
  • Woodward 9905-204 Rev N - SPM-A synchronizer
  • Woodward XG2 - Protection relay
  • WOODWARD 9907-175 LOAD SHARING MODULE REV A - Load Sharing Module
  • Woodward 9907-166 REV: N - 505E Turbine Control 110V AC/DC