GE IS421UCSBS1A processor
Effective with RX3i Firmware Release 8.603
, the CPE330 supports Ethernet Global Data (EGD)
Class 1. This feature is available on all firmware releases of CPE4004
.
▪ The rack-based IC695ETM001 Ethernet Interface has dual RJ45 ports connected through an
auto-sensing switch. This eliminates the need for rack-to-rack switches or hubs. The ETM001
supports upload, download and online monitoring, and provides 32 SRTP channels with a
maximum of 48 simultaneous SRTP server connections. It also supports Modbus TCP. For details
on Ethernet Interface capabilities, refer to PACSystems RX7i & RX3i TCP/IP Ethernet
Communications User Manual, GFK-2224.
▪ PROFIBUS communications via the PROFIBUS Master module, IC695PBM300. For details, refer to
the PACSystems RX3i PROFIBUS Modules User’s Manual, GFK-2301.
▪ PROFINET communications via any supported PROFINET Controller and any supported PROFINET
Scanner.
o Supported PROFINET Controllers include the embedded PROFINET Controller function
offered by IC695CPE400 and IC695CPE330, and the rack-mounted PROFINET Controller
module IC695PNC001.
o Supported PROFINET Scanners include the RX3i PROFINET Scanner module
IC695PNS0015
, the RX3i IC695CEP001, and the VersaMax PROFINET Scanner modules
IC200PNS001 & IC200PNS002.
For details, refer to the PACSystems RX3i PROFINET IO-Controller Manual, GFK-2571F or later and
PACSystems RX3i PROFINET Scanner Manual, GFK-2737F or later.
▪ Effective with the release of IC695CEP001 and IC694CEE001, the RX3i may be configured to
control a remote drop consisting of one or two I/O modules. The RX3i interface to the remote
drop is managed by the PROFINET Controller, IC695PNC001. Refer to PACSystems RX3i CEP
PROFINET Scanner User Manual, GFK-2883.
▪ HART Pass Through allows an RX3i CPU to communicate HART asset management data between
HART-capable I/O modules and PC-based asset management tools. This entails usage of PCbased applications, RX3i Analog modules with HART functionality and (optionally) supporting
PROFINET products. HART Pass Through operation is described in the PACSystems HART Pass
Through User Manual, GFK-2929.
The following RX3i CPUs support HART Pass Through: IC695CPE305, IC695CPE310, IC695CPU315,
IC695CPU320, IC695CRU320, IC695CPE330
6,7
(Firmware Release 8.50 or later).
The following RX3i analog modules support HART:
IC695ALG626
IC695ALG628
IC695ALG728
If used for HART Pass Through, the supporting RX3i PROFINET Controller and PROFINET Scanner
must also contain HART-compatible firmware:
3 Proficy Machine Edition Release 8.60 SIM 5 is required for EGD Class 1 on both LAN1 and LAN2 of CPE330. This PME version
also supports Advanced Configuration Parameters for EGD on CPE330. Alternately, PME Release 8.60 (not SIM 5) supports
EGD on CPE330 LAN1 only, and does not support Advanced Configuration Parameters for EGD.
4 Proficy Machine Edition Release 9.00 SIM 8 or later is required for native configuration support of the CPE400.
5
IC695PNS001 firmware release 2.40 added support for a number of I/O modules not previously supported, as documented
in PACSystems RX3i PROFINET Scanner Important Product Information, GFK-2738L.
6 When used to support HART Pass Through, CPE330 must do so via a PNC001 and cannot employ its embedded PROFINET
feature for this purpose.
7
IC695CPE330 firmware release 8.95 added support for the Remote Get HART Device Information COMMREQ

IC695PNC001-AK Firmware Release 2.20
IC695PNS001-ABAH Firmware Release 2.308
IC695CEP001-AAAD Firmware Release 2.30.
▪ Effective with the release of IC695GCG001, the RX3i may be equipped to control a Genius Bus.
The RX3i interface to the Genius Gateway is managed by the PROFINET Controller, IC695PNC001.
Refer to PACSystems RX3i Genius Communications Gateway User Manual, GFK-2892.
▪ Effective with the release of IC695EDS001, the RX3i may be configured as a DNP3 Outstation.
Refer to PACSystems RX3i DNP3 Outstation Module IC695EDS001User’s Manual, GFK-2911.
▪ Effective with the release of IC695EIS001, the RX3i may be configured to act as an IEC 104 Server.
Refer to PACSystems RX3i IEC 104 Server Module IC695EIS001 User’s Manual, GFK-2949.
▪ IC695CMM002 and IC695CMM004 expand the serial communications capability of the RX3i
system. Refer to PACSystems RX3i Serial Communications Modules User’s Manual, GFK-2460.
▪ CPE310, CPU310, CPU315, CPU/CRU320 and NIU001 provide two serial ports, one RS-232 and
one RS-485.
▪ CPE305 provides one RS-232 serial port.
▪ CPE330 provides no serial ports.
▪ The serial port on CPE400 is disabled.
▪ Effective with CPE305/CPE310/CPE4009 Firmware Release 9.20, or CPE330 Firmware Release
9.21, the CPE embedded Ethernet interface supports Simple Network Time Protocol (SNTP) Client,
Coordinated Universal Time (UTC), and Daylight Savings Time (DST). Refer to PACSystems RX7i,
RX3i and RSTi-EP TCP/IP Ethernet Communications User Manual, GFK-2224 version Q or higher.