Processor and Storage
CPU:PowerPC 8245, Main frequency of 400MHz, capable of running AIM and DP ship applications
Memory: 32 MB SDRAM; Flash Memory: 16 MB Flash
Various communication interfaces
Interface type specification parameters
Universal serial port 12 channel RS-232/RS-422/RS-485; 4-channel isolated RS-232/RS-422/RS-485
CAN bus dual channel CAN bus, speed 1 Mbps
Profibus dual channel Profibus, speed 12 Mbps
SPBus (connected to RIO400 remote IO) 1 channel; RS-485 multipoint bus; Manchester code; Maximum 2 MHz; Optocoupler isolation 500V; 9-pin DSUB male connector; Power supply 10-28.8VDC
Ethernet dual independent 100 Mb LAN port
Digital I/O 4-channel universal digital input DI; 4-channel universal digital output DO
System monitoring function
BIST has built-in self-test and reports fault information to the operator station;
Hardware watchdog Watchdog, with system status output;
Built in temperature sensor and cooling fan fault alarm;
Panel status LED, including Run/Error operation fault indicator light, with a total of 8 status LEDs.
Redundancy feature
Support RCU500 redundant configuration;
Hot replacement is supported in redundant systems, allowing for non-stop replacement of controllers.
Mechanical and Installation
DIN standard rail installation, plug-in connectors for easy installation and replacement.
Dimensions: height 355 mm x width 158 mm x depth 87 mm; weight 1.35 kg.

Electrical parameters
Power supply: 24 VDC ± 20%; Maximum power consumption of 20W;
Wiring terminal: screw terminal, compatible with wire cross-sectional area of 1.5 mm ²;
Maximum heat dissipation of 20W; protection level of IP20.
Environmental conditions
Project parameters
Working temperature: 0 ℃~70 ℃
Storage temperature -25 ℃~70 ℃
Relative humidity for work/storage up to 98% RH
EMC Electromagnetic Compatibility EN 61000-6-2, EN 61000-6-4, IEC 60945
Adhere to standards and class certification
Following standards: IEC 61131-2, IEC 60945, IACS E10, IEC 61508 (functional safety); Possessing CE marking.
Classification certification (expected to be completed in Q2 2004): DNV, ABS, T Ü V Rheinland (IEC61508 functional safety).