K-WANG



Basic Information
Product: MC200 Controller (Dual Processor Architecture)
Version: Rev.132025-09-03, compatible with firmware V2.06
Usage: Main controller for generator sets, parallel connection of multiple machines, automatic switching between mains and generators, power management, cloud monitoring
Applicable to various power plant architectures such as single/multiple units, MPM/MSB/MPTM, etc
Configuration tool: BoardPrg4 (PC parameter configuration, curve editing, PLC programming)
Core technical specifications
1. Power Supply and Physics
Power supply: 12/24VDC, range 8-32VDC, reverse protection
Display: 4.3 "TFT color screen, 480 × 272
Size: 247 × 187 × 70mm, protective front panel IP55
Working temperature: -25 ℃~+60 ℃
Sampling: 10kHz, 12 bit accuracy
2. Electrical measurement
Voltage: three-phase/single-phase, 400V/100V range, true RMS TRMS
Current: External CT 1A/5A, accuracy<0.2%
Frequency: 50/60Hz, resolution 0.1Hz
Measurement: voltage, current, power, power factor, kWh, temperature, battery voltage
3. Protection accuracy
Covering ANSI/IEEE standard protection:
Overcurrent/undercurrent (50/51), overvoltage/undervoltage (27/59)
Overfrequency/underfrequency (81U/81O), reverse power, imbalance, synchronization failure
Action accuracy: ± 0.5% voltage, ± 50mHz frequency, action time ± 35ms
Overview of Hardware Interfaces (Core Terminals)
1. Digital quantity IO
Input: 18 channels of optical isolation DI, supporting co positive/co negative, expandable to 50 channels
Output: 18 channels of DO (relay+static)
Relay: 15/16( 3A@30VDC )17/18( 10A@250VAC )
Static: positive/negative output, short circuit/overcurrent protection
Support AND/OR logic, virtual DI/DO, PLC control
2. Analog IO
Input: 7-way AI (0-10V/current/resistance), supports custom curves
Output: 2-channel AO (± 10V, isolated), used for speed/voltage regulation
Scalable: Temperature and analog module
3. Battery measurement terminal
JG: mains voltage | JF: generator voltage
JE: Three phase current | JI: Fourth current (neutral/differential)
Supports star, delta, single-phase, and Aron connections
4. Communication interface
RS232、RS485(Modbus RTU)
USB (configuration/upgrade)
Ethernet 10/100M (Modbus TCP, NTP, cloud)
Dual CAN
CAN0: Expansion Module (EXBUS)
CAN1: PMCBus multi machine parallel bus

Core functions
1. Operation mode
OFF/RESET、MAN、AUTO、TEST、REMOTE START
Panel buttons: START/STOP, MAN/AUTO, MCB/MGCB close/open
2. Automatic switching of mains power (AMF)
Detect abnormal mains voltage/frequency → Start the unit → Synchronize → Close MGCB → Load
Restore mains power → Switch back to mains power → Shutdown for cooling
3. Synchronization and Parallel Connection
Automatic/manual synchronization (synchronous table, phase/voltage/frequency difference judgment)
Multi machine load sharing (active/reactive)
Support: MPM, MSB, MPTM, MSB+MSTP and other types of power stations
4. Power and load management
Base Load, Import/Export Power Settings
Peak Shaving: Peak shaving and valley filling
Load Shedding: Overload shedding (4 groups)
Start and stop units according to priority, and automatically rotate between primary and backup machines
5. Protecting Logic
Electrical: overvoltage, undervoltage, overcurrent, phase loss, reverse power, synchronization failure
System: Battery high and low voltage, board temperature too high, emergency stop, communication failure
Support the protection of override blocking (critical protection cannot be blocked)
6. PLC function
Built in soft PLC, supporting logic blocks, virtual variables, and custom logic
Can independently control IO, linkage protection, and customize processes
7. Smart Cloud platform
TLS 1.2 encrypted upload
Remote monitoring, alarm, parameters, curves
No need for a public IP address, supports internal network penetration
Operation and display interface
1. Display mode
P. XX: Parameter programming (graded password: Super User/Maker/Installer/User)
S. XX: Status (Mode, Alarm, Communication, IO)
M. XX: Electrical measurement (voltage, current, power, kWh)
B. XX: PCMBus Multi Machine Data
H. XX: Historical records (events, trends, extreme values)
L. XX: PLC Information
2. Operation permissions
4-level password protection, key parameters can only be modified with OFF/RESET
Support factory parameter recovery and password reset
Installation and wiring specifications
Installation: Panel opening 218 × 159mm, fixed with screws
Grounding: Functional grounding JB must be connected to ensure EMC
Voltage circuit: 2A slow melting fuse needs to be connected in series
Current circuit: CT strictly prohibits open circuit
Communication: CAN/RS485 twisted pair shielded wire, terminal 120 Ω resistor
Emergency stop: Connect to JJ public terminal, power outage triggers alarm
Alarm and Malfunctions (Anomalies)
1. Level 3 alarm
W (Warning): Warning, do not trip
U (Unload): Unload, skip MGCB/GCB
A (Alarm): Alarm, shutdown
2. Typical fault codes
005: GCB not disconnected
013/014: MCB/MGCB not closed
016: Overcurrent
022: Startup timeout
048: Emergency stop
051: Board temperature too high
272/273: Synchronization failed/parameter inconsistency
3xx: Analog fault
7xx: Digital quantity fault
9xx: PLC malfunction
3. Fault handling
Mute, confirm, reset, lock records
Historical records can be checked for time, events, and measurement values
Expansion module (optional)
DITEL 16IN: Extended DI
DITEL 8OUT: Extended DO
DIVIT: Expanding AI (Voltage/Current)
DANOUT: Extend AO
DITHERM/DIGRIN: Temperature measurement (thermocouple/Pt100)
Typical application scenarios
Single Unit AMF: Automatic Switching from Mains to Generator
Multi unit parallel connection: load sharing, priority start stop
Parallel connection of mains power: peak shaving, backup, uninterrupted power supply
Pump station/machine room/data center: high reliability backup power supply
Remote unmanned operation: cloud monitoring+SMS/remote control