Product positioning and safety certification
This document is the operation manual for the NE1A series secure network controller, used for mechanical functional safety distributed control systems.
Coverage model:
No EtherNet/IP: NE1A SCPU01 (- V1), NE1A SCPU02
Equipped with EtherNet/IP: NE1A SCPU01 EIP, NE1A SCPU02 EIP
Core Security Certification:
IEC 61508 SIL3
EN ISO 13849-1 PLe/Safety Category 4
EN 62061、UL 508、Class I Div 2
Hardware specifications and interfaces
1. Comparison of I/O models
Model safety input test output safety output
NE1A - SCPU01 (- V1)/- EIP 16:04:08
NE1A - SCPU02/- EIP 4:08:08
2. Electrical specifications
Power supply: 24VDC (20.4~26.4V)
Working temperature: -10~55 ℃
Protection level: IP20
Installation: 35mm DIN rail, ventilation ≥ 5mm (side), ≥ 50mm (top and bottom)
Wiring: 0.2~2.5mm ², screw torque 0.5N · m
3. Interface and indicator lights
Communication: DeviceNet, USB 1.1, EtherNet/IP (EIP)
Display: 7-segment digital tube (node/error code) MS/NS/LOCK/COMM LED
Dialing: Node address (0~63), baud rate (125k/250k/500k)
Communication function (core)
1. DeviceNet Safety
Secure main station: up to 32 connections (Ver1.0+), supporting unicast/multicast
Secure Slave: Up to 4 connections, maximum 16 byte I/O
Standard Slave: Up to 2 connections, supports Poll/COS/Cyclic
Baud rate: 125k/250k/500kbps, supports automatic detection
2. EtherNet/IP (EIP model)
IP settings: BOOTP or static IP (default 192.168.250.1)
Function: Standard I/O communication, explicit messaging, UDP packets, routing
UDP port: 64000, supports cross network access to DeviceNet devices
3. Remote I/O allocation
Mapped: General state, local I/O state, monitoring data, user tags
Security attribute differentiation: Security data can be used for security circuits; Non secure data is only used for monitoring purposes
Safe I/O Control (Core)
1. Secure input
Channel mode: unused/test pulse input/safe input/standard input
Dual channel mode:
Equivalent dual channel: Only when both channels are turned on simultaneously, is it effective
Complementary dual channel: One NO and One NC cooperation
Diagnosis: Differential time (0-65530ms), incorrect lock (default 1000ms)
2. Test output
Mode: Pulse Test, Standard Output, Shielded Lamp Output
Function: Output diagnostic pulses to detect input circuit short circuits, disconnections, and grounding faults
3. Safe output
Mode: Safe Output/Safe Pulse Test
Diagnosis: overcurrent protection, dual channel linkage, output short circuit detection
Mandatory requirement: Prohibit using test output as safe output

Programming and Function Blocks
1. Programming environment
Software: Network Configurator
Editor: A graphical logic editor that supports direct drag and drop of I/O tags
Capacity: Up to 254 functional blocks for Ver1.0 and above
2. Core functional blocks
ESTOP: Emergency stop button monitoring, supports dual channel
Light Curtain: Safety Light Curtain Monitoring
Safety Gate: Safety Gate monitoring, supporting synchronized time
Two Hand Control: Two Hand Control
Reset/Restart: Manual reset/restart, prevent automatic recovery
Logic: AND, OR, NOT, RS-FF, comparator
Operation mode and fault diagnosis
1. Operation mode
RUN: Normal operation
IDLE: Stop output, can be monitored
CONFIG: Configuration Download
SAFE MODE: System Repair
2. Fault diagnosis
7-segment code display: error code+node number
LED status:
MS green=running; Red=fatal error
NS green=communication is normal; Red=Fault
Yellow LOCK=configuration effective lock
Error History: Record fault type, time, and status
3. Common Error Handling
Error code meaning handling
P4 input power abnormality check V1/G1
P5 output power abnormal inspection V2/G2
Nd DeviceNet disabled (standalone mode) normal
D5/d6/dA Safety communication fault inspection slave station EPI、 line
Maintenance and safety regulations
1. Maintenance function
Contact action counter: Count the number of suction and closing times (0~4294967295)
Accumulated ON time monitoring: Count the duration of power on
Threshold alarm: life warning can be set
2. Mandatory safety taboos
Prohibit using standard I/O, explicit messages, UDP data as security signals
Prohibit overload connection to safety output
It is necessary to use a forced guiding contact relay and directly disconnect the emergency stop
After the power is cut off in the dangerous area, plug and unplug the wiring
Key questions and answers
Question 1: What are the two modes of dual channel safety input for NE1A? What scenarios are they used for? What is the effect of differential time?
answer:
Equivalent dual channel: Both channels are NC normally closed inputs, and simultaneous actions (such as emergency stop buttons and safety switches) must be turned on/off simultaneously to be effective.
Complementary dual channel: one NO and one NC, reverse action, used for safety doors and limit switches.
Differential time: Monitor the interval between changes in two signals, determine faults when timeout occurs, cut off outputs, and prevent switch failure or wiring errors.
Question 2: How many slave stations can NE1A carry as a Safety Master? What are the three recovery strategies after a communication failure?
answer:
Load capacity: Up to 32 secure slave connections for Ver1.0 and above; There are only 16 Pre Ver.
Fault strategy:
Automatic recovery: automatic reconnection after fault elimination
Only stop faulty connections: keep other connections running
Stop all connections: The entire line enters a safe state and needs to be manually reset
Question 3: What is the use of UDP/IP message function with EIP model? What are the communication format and port?
answer:
Purpose: Ethernet devices (PLC/PC) can directly access DeviceNet Safety slave stations through UDP, enabling cross network monitoring without the need for additional gateways.
Specifications:
Port: 64000 (FA00hex)
Command length: Maximum 492 bytes
Response length: maximum 496 bytes
Restrictions: Only Ver1.1 and above - EIP models are supported.