K-WANG



Applicable models and positioning
Covering 6 controllers, unified hardware architecture, differentiated by performance and interface:
Model Ethernet Performance/Storage Special Features
ILC 131 ETH 1 Port 192KB Program Basic Payment
ILC 151 ETH 1 port 256KB mid-range program payment
ILC 171 ETH 2TX 2-port (exchange) 512KB program dual network port MRP
ILC 191 ETH 2TX 2 Ports (Swap) 1MB Program Highest Performance
ILC 131/151 ETH/XC 1 Port Same as Basic -40 ℃~+60 ℃ Wide Temperature Range
Hardware Structure and Interface
Operation and Instruction
Mode switch: RUN/ROG, STOP, MRRESET (reset clear program)
Reset button: hidden, factory reset
LED: Running (FR), Fault (FF), Ethernet (LNK/ACT), Power Supply (UL/UM/US), Bus (RDY/FAIL)
Local I/O
8 x digital input (24V), filtering 5ms
4 x digital output (24V/0.5A/channel), total 2A
Power supply system (three independent circuits)
U_SLC: Controller power supply (19.2~30V DC), max 870mA
U_S: Segment section power supply, max 8A
U_S: Main power supply, max 8A
Requirement: The power supply has no fallback feature and is equipped with an external 2A/8A fuse
Communication ability
Ethernet
10/100M,RJ45, Automatic crossover
Dual port models with built-in switching function
Fieldbus
INTERBUS: Local bus up to 63/128 nodes, remote bus up to 4 levels
PROFINET Device: RT level, update rate * * ≥ 1ms**
Modbus/TCP:Client/Server, Maximum 32768 points
Advanced features
MRP redundancy: Supports dual network port models, switching time * * ≤ 200ms**
Serial port: RS-232 (9600bps), used for IP allocation/diagnosis
Software and Features
development environment
PC Worx / PC Worx Express ≥ V6.20
Supports 5 IEC 61131 languages with a minimum task cycle of 1ms
Storage and SD card
Built in 4MB Flash, pluggable SD card (main memory/expandable memory)
Support log storage, FTP access, program backup
web service
FTP/HTTP/HTTPS, Can set account password protection
SMTP (S) encrypted email SNMP、 Port control

Security and Certification
Explosion-proof certification
Zone 2,II 3G Ex nA IIC T4 Gc
Installed in control cabinets above IP54
Environmental level
Standard: -25 ℃~+55 ℃
XC wide temperature version: -40 ℃~+60 ℃
EMC
Meets EN 61000 series, Class A radiation
Installation and maintenance
Install
35mm DIN rail, horizontally installed
Protection level IP20, installed inside the cabinet
maintain
Firmware Upgrade: Ethernet Remote Update
Fault diagnosis: system register+LED+Diag+tool
Common faults: abnormal power supply, IP conflict, bus not connected, mode switch error
Key questions and answers
Question 1: What is the function of the dual Ethernet port and MRP function of ILC 171/191 ETH 2TX? How to configure on-site?
answer:
Dual network ports with built-in switching function can achieve linear/circular topology, saving switches; MRP is a medium redundancy protocol that switches within 200ms in the event of a ring network failure to ensure uninterrupted communication.
Configuration: In PC Worx, enter Extended Settings → MRP Client * *, set to activated, and restart to take effect.
Question 2: Do the three power supplies (U_SLC/U_S/U_S) of the ILC controller need to be separated? What are the consequences of connecting incorrectly?
answer:
Three independent functions, allowing external short circuiting of the common power supply, but must be equipped with fuses according to the current:
U_SLC: Provides power to the controller and logic, ≤ 2A fuse
U_S/U_S: Supply power to IO and bus, ≤ 8A fuse
Consequences of incorrect connection: overload burning insurance, module overheating, IO unable to output, bus unable to connect to the network.
Question 3: What are the core differences between ETH/XC wide temperature version and standard version? Which scenarios must choose XC version?
answer:
Differences:
Working temperature: Standard version * * -25~+55 ℃; XC version -40~+60 ℃**
Coating: XC version motherboard three proof coating, resistant to moisture/dust
XC version scenes must be selected:
Outdoor cabinet, no air conditioning cabinet, cold storage, vehicle mounted, coastal high humidity environment
Industrial sites with large temperature fluctuations and no temperature control

K-JIANG
Add: Jimei North Road, Jimei District, Xiamen, Fujian, China
Tell:+86-15305925923