ABB REF542plus Feedline protection and measurement unit
Please read this manual carefully before using REF542plus for operation.
This manual describes how to use the interface of REF542plus (LD HMI, local detachable human-machine interface). Attention: This manual
The views and images related to HMI included in are only used as examples.
If you are not authorized or unfamiliar with REF542plus and its operating tools, do not be unfamiliar with REF542plus
Make any changes to the configuration. Changing its configuration may cause malfunctions and render it ineligible for warranty.
1.2. Symbol usage
This article includes the following icons, which are used to indicate safety related conditions or important information:
Electrical warning icons are used to indicate the presence of hazardous factors that can cause electric shock.
Warning icons are used to indicate the presence of hazardous factors that may cause personal injury.
The attention icon is used to indicate important information or warnings related to the concepts discussed in the text. It will indicate the existence of that
There is a danger that may cause software paralysis or damage to equipment or property.
Manual Title
Item identification
Application Notes
1MRS755870
CAN Manual
1VTA100189-Rev 1, en
Configuration Guide
1YZA000053-cn
iButton Programmer User Manual
1MRS755863
Manual Part 3,Installation and Commission
1VTA100004
Manual Part 4,Communication
1VTA100005
Motor Protection with ATEX Certification,Manual
1MRS755862
Operation Manual
1YZA000052-cn
Protection Function Manual
1YZA000051-cn
Technical Catalogue
1MRS755859
Technical Reference Modbus RTU
1MRS755868
Web Manual, Installation
1MRS755865
Web Manual, Operation
1MRS755864
1.5. File version
File version
product version
date
Revision history
1VTA100172-Rev1.en
2002.11.01
First release
1VTA100172-Rev2.en
2003.10.22
Upgrade to version 4D02
1VTA100172-Rev 3.en
2004.05.03
upgrade
1VTA100172-Rev 4.en
2005.04.04
upgrade
1MRS755869, Version A
2006.02.28
File upgrade
. Language
·Typesetting
1MRS755869, Version B
two point five
2006.09.30
Upgrade to software version V4E03a
1YZA000052 cn, version B
two point five
2007.01.31
This version is 1MRS755869
Chinese translation version of version B
LED strip: These three LED strips can be used to display the load status of the switch device obtained by quickly checking REF542plus
The most relevant information. They are labeled as M1, M2, and M3 respectively. Each of them consists of 12 LED lights, 10 of which are green, and 2
One is red. Under normal circumstances, 10 green LED lights are specifically used to display 0% -100% of the measured rated value of the configuration. to
Yes, each LED light corresponds to 10% of the rated value. Two red LED lights display a 20% overload status. These LED strips
The displayed measurement values can be set using operating tools.
Indicator LED: 8 freely programmable three color LED lights are available for display. These LED lights are distributed on 4 pages. Therefore, overall
32 indicator options, programmable for corresponding protection, control, monitoring, and switch input related time and status.
LED lights can be assigned to specific conditions using operating tools.
Infrared (lrDa) interface: This is an infrared serial interface that can be used to connect REF542plus to a personal computer. Use in combination
Suitable cables and operating tools can be used for the following operations:
Download the configuration to the unit.
·Upload the current configuration from the unit.
·After a malfunction occurs, upload the fault recording data. Only after pre enabling fault recording with the operating tool, can it proceed
Perform this operation.
Upload other information (measurement values, switch input status, switch output status).
Do not make any changes to the configuration of REF542plus unless you are familiar with REF542plus and its operating tools.
Changing its configuration may result in malfunctions and loss of warranty eligibility.
function. When the device is in operation, the green LED is turned on. When there is no auxiliary power supply or the equipment is not running (FUPLA is not available)
When running, the LED will turn off.
Communication malfunction. The display of this LED is only meaningful when the REF542plus is equipped with a communication module. When a communication module is detected,
The LED turns green when turned on. If there is no or no communication module detected, the LED will display in red. Installed Modbus communication
When the communication error rate increases after the signal module, the LED turns orange. When the communication error rate causes poor communication, it turns red.
When no communication error occurs or the module status register (see Modbus Technical Reference) is reset, the LED turns back green
Color. When the communication module is not present, the LED remains off.
·Alarm: When the user-defined alarm is valid, the LED turns red. Several alarm bars can be defined and configured using operation tools
Item. Alarm conditions can include tripping of protective functions, loss of SFs in circuit breakers, and so on. When the LED is turned on, it cannot be turned off
Close the circuit breaker or download a new configuration. Firstly, the alarm must be confirmed.
Interlock error: LED usually displays green. If the user attempts to perform an operation that violates the interlocking conditions, the LED will temporarily change to
red For example, operating the isolation switch when the circuit breaker is in the closed position.