K-WANG
ABB RTU560E Remote Terminal Unit
Product positioning and application scenarios
RTU560E is a component of RTU560 remote terminal unit, suitable for application scenarios of small and medium-sized data point scale, including:
Centralized or distributed system architectures such as local network sites and small distribution substations.
In the field of oil and gas networks: pipeline leak detection and block valve control, pipeline flow measurement, oil well monitoring and control.
OEM applications that require multifunctionality, precise computation, data storage, or custom protocols.
Core Features
Design features: Adopting a compact design, high cost-effectiveness, supporting customer specific configurations, modular structure for easy expansion.
Architecture flexibility: It can adapt to centralized or distributed system architectures and can be configured with up to 27 I/O cards through an expansion bus.
Technical parameters
Hardware composition and specifications
Shell (560HOS80): The dimensions are 366 × 258 × 310 mm (height × width × depth), and the protection level meets EN 60950 and 50178 standards, reaching IP 30.
Central processing unit (560CMU80): equipped with ELAN 400 processor (66 MHz) and 4 MB DRAM (optional 16 MB); Includes 2 RS232 interfaces (baud rate 50-38400), 1 RS485 interface (up to 19200 baud rate), and 2 optional modem slots; Equipped with MMK interface (serial connection with internal web server), optional 10BaseT Ethernet interface.
Multi I/O card (560MIO80): supports 24-60V and 110-220V DC process voltage; Contains 16 binary inputs (input current 1-3 mA), 2 counter inputs (up to 8 kHz), 8 binary outputs, and 4 analog inputs.
Fiber coupler (560FOC80): Input voltage 5-24V, emission wavelength 850 nm, input optical power range -24.0 to -10.0 dBm, maximum transmission rate 1 MBit.
Power supply: 560PSU80 (DC/DC) supports 24-60 V DC or 110-220 V DC input; 560PSU81 (AC/DC) supports 110-230 V AC input.
Environmental adaptation: The working temperature range is -20 to+70 º C.
Communication and Function
Communication capability: Provides up to 3 communication ports, supporting protocols such as IEC 60870-5-101/102/103/104, Modbus, SPA, DNP3.0, RP570/71, etc; Optional Ethernet interface, supports modems (analog dial-up, V.23, GSM, etc.).
Core function: Supports PLC 61131 standard and has data archiving function; Flow calculation for turbine flow measurement (including AGA 8 density calculation, can support other standards upon request); Support optional slave/master protocols (such as IEC870-5-101).