K-WANG

+086-15305925923
Service expert in industrial control field!
NameDescriptionContent
Adequate Inventory, Timely Service
pursuit of excellence 
Ship control system
Equipment control system
Power monitoring system
Current position:
新闻动态
newS
   
Brand

ABB SPAD 346 C3 Differential Protection

From: | Author:Wang | Time :2025-06-20 | 376 visit: | 🔊 Click to read aloud ❚❚ | Share:

ABB SPAD 346 C3 Differential Protection

Scope and Introduction

Document purpose: To introduce the differential protection setting calculation of SPAD 346 C3 protection relay module SPCD 3D53, which is applicable to two winding power transformers and involves differential protection of three winding power transformers, motors, generators, etc., including setting suggestions and discussion of intermediate current transformer (CT) requirements.

Protection principle: By comparing the phase currents on both sides of the protected object, when the differential current of a certain phase current exceeds the starting value of the stable action characteristic or the instantaneous protection stage value, the relay sends an action signal, which has the characteristics of fast action speed, high stability of faults outside the area, and high sensitivity to faults inside the area. CT selection and relay setting should be cautious.


Two winding power transformer protection

(1) Vector Group Matching (SGF1)

By using SGF1/1... 8 switches, the vector groups of power transformers are numerically matched on the high voltage (HV) and low voltage (LV) sides. Based on the phase shift and delta connection inside the relay, there is no need for intermediate CT, and the zero sequence component in the phase current can be automatically eliminated. Different vector groups correspond to different switch positions and check sums.

(2) CT ratio correction (I ₁/In, I ₂/In)

When the CT secondary current is different from the rated current under the rated load of the power transformer, the CT ratio on both sides of the transformer needs to be corrected. Calculate the rated load of the power transformer firstI nT=S n/(3 × U n), then calculate the transformation ratio correction settings I 1/In=I nT/I p (HV side) and I 2/In=I T/I p (LV side), where I p Rated primary current for CT, and the rated input current (1A or 5A) on the HV and LV sides of the relay can be different, using 1A secondary current can improve CT performance.

(3) Startup ratio (S)

Due to the inaccuracy of CT and changes in the position of the tap changer, an increase in load current will cause differential current to increase by the same percentage. The setting of the start-up ratio (S) affects the slope of the relay action characteristics between the first (fixed 0.5 × In) and second turning point (set I 2tp), which is calculated as the sum of CT accuracy on both sides, tap changer adjustment range, relay action accuracy (4%), and required margin (usually 5%).

(4) Basic Startup Settings (P/In)

The basic setting (P) defines the minimum sensitivity of protection, taking into account the no-load current of power transformers, which is generally calculated asP=0.5 × S+P, where P 'represents the no-load loss of the transformer at maximum voltage, usually used when the actual value is unknown

P ′=10%。

(5) Second turning point (I ₂ tp/In)

The second turning point defines the point at which the influence of the activation ratio S in the action characteristics ends and the slope begins at 100%. Its setting needs to balance stability and sensitivity. In power transformer protection applications, the range of 1.5-2 is usually selected, with 1.5 being more stable for out of zone faults and 2.0 being more sensitive for in zone faults.

(6) Second harmonic blocking (Id2f/Id1f>)

The excitation inrush current of power transformers during excitation contains a large amount of second harmonic. Differential protection is locked by detecting the content of second harmonic (low setting stage). The recommended setting for second harmonic locking in power transformer protection is 15%, which can be enabled by setting the switch SGF2/1=1, and the setting can be reduced to 10% during the first excitation.

(7) Instantaneous differential current stage (Id/In>>)

It is recommended to use it together with the low setting stage to provide faster protection in case of severe faults, and is not subject to harmonic blocking. Its setting needs to be high enough to prevent the differential relay module from tripping when the transformer is excited, usually 6-10.

(8) Fifth harmonic blocking and unlocking (Id5f/Id1f>, Id5f/Id1f>>)

Used to lock the relay action when there is a sudden voltage rise (or frequency drop), based on the fifth harmonic component of the transformer excitation current to monitor overexcitation. Due to the need to know the magnetization characteristics of the transformer, it is usually not enabled, that is, SGF2/3 and SGF2/4 are set to 0.

(9) Interference recorder

The internal interference recording function of the relay module is a powerful tool for analyzing the causes of transformer inrush current and tripping. The factory default settings are used during normal operation, and the serial communication parameters V241 and V245 need to be changed during inrush current research.


Three winding power transformer protection

The SPAD 346 C relay can be used for three winding transformers or two winding transformers with two output feeders. On the dual feeder side of the transformer, the two CT currents of each phase must be summed through parallel connections, usually requiring an intermediate CT to handle vector group and/or ratio mismatches, and at least 75% of the short-circuit power should be fed from the transformer side with only one connection to the relay, otherwise it may cause unstable protection.


Motor and generator protection

The calculation process for setting up differential protection applications for motors or generators is very similar to that of power transformers, but the vector group should be set to Yy0. The starting ratio (S) is calculated as the sum of the CT accuracy on both sides, the relay action accuracy (4%), and the required margin (usually 2.5-5%). The second turning point (I ₂ tp/In) may cause CT saturation due to current during motor start-up, with a typical setting value of 1.0. The generator is usually between 1.0-1.5, and the motor and generator usually do not require second or fifth harmonic blocking.


Combination protection of motor and autotransformer

The differential relay measures the phase current on both sides of the protected object, and the protection area includes the autotransformer and motor. The current between all autotransformer/motor combinations and the network must be measured, and its setting is the same as that of ordinary motor protection applications. The autotransformer will have a typical starting sequence during the motor starting process, from power supply to acting as a parallel reactor and then to bypass.


Variable frequency motor and its power transformer protection

SPAD 346 C can only be used to protect power transformers that supply power to frequency converters, and is not suitable for protecting power transformers or motors powered by frequency converters, as the fundamental frequency component in the relay is numerically filtered through a Fourier filter and is not suitable for measuring the output of frequency converters.


Short overhead or cable protection

SPAD 346 C can be used for differential protection of overhead or cable lines. When the distance between measurement points is long, an intermediate CT may be required to reduce CT load. Using 1A secondary current can reduce CT load, and the actual accuracy limit factor (Fa) of CT can be calculated to ensure compliance with requirements.


Summary

This guide describes how to select and calculate differential protection settings for SPAD 346 C protection relays, introduces the working principle and setting effect of relays, and presents the calculation process through examples. It also describes protection application examples for three winding power transformers, motors, and generators, discusses the applicability of SPAD 346 C relays in frequency converter applications, and finally describes differential protection for short overhead or cable lines through examples of calculating the actual accuracy limit factor of intermediate CT.


  • LTI Drives CDF30.002.C0.7 Compact Servo Controller 08685963 DC 24V Industrial Module
  • LUST LTI Drives CDB32.008.W2.4.BR.PC1 Servo Drive Industrial Motion System
  • LUST LTI Drives CDB34.003.C2.4.PC1.H15 Servo Motor Driver Industrial Control Unit
  • LUST LTI Drives CDA32.004.C1.4.H08.B0 Servo Drive Mat. 3084456 Industrial Control
  • LUST LTI Drives CDE34.005.W2.2 Industrial Servo Drive Motion Control Unit
  • LUST LTI Drives CDA34.006.W3.0 Servo Drive Software V3.70-04 Industrial Controller
  • LTI Drives CDB32.004.C2.4.SH Servo Drive Compact Motion Controller
  • Woodward 9905-373 - Digital Synchronizer And Load Controller
  • WOODWARD MAGNETIC PICKUPS - Sensor
  • WOODWARD GCP-30 - Steuertafel for Industrial Regulator Genset Control Package
  • WOODWARD GOVERNOR 9907-1183 REV A - 505 ENHANCED TURBINE CONTROL
  • WOODWARD 9907-173 REV B - Module Load Sharing 120 Volt
  • WOODWARD 9907-014 - 2301A controller
  • Woodward 9905-029 - SPM-A Synchronizer Module Rev C
  • WOODWARD 8440-1799 EASYGEN-350 REV B - Genset Controller
  • WOODWARD 5466-258 REV M - SIMPLEX DISCRETE I/O MODULE
  • Woodward 8440-1884 C - Controller Easygen 2500-5
  • Woodward 8441-1153 - Monitoring Unit 250VAC
  • WOODWARD 8406-120 REV G - EGCP-2 DIGITAL CONTROL
  • Woodward 8273-584 - Atlas-ii Digital Control
  • Woodward 8272-582 - APM Motor Control 8272582
  • Woodward 9905-377 Rev. A - 2301A Load Sharing and Speed Control
  • WOODWARD 8272-517 - Pm Motor Control
  • WOODWARD 9905-797 REV.B - DIGITAL SYNCHRONIZER AND LOAD CONTROL DSLC-D
  • WOODWARD 8272-582 - APM MOTOR CONTROL
  • Woodward Seg FP2-8-24 - Emergency Power Telecommunications Module NP2
  • WOODWARD 2001-12E2U1B1S1A - Fuel Shut Off Valve Stop Solenoid Valve 2000-4505
  • Woodward 8440-1884 K - Genset Controller Easygen-2500-5
  • Woodward 9905-760 - Linknet Termination Module
  • Woodward 8404-009 - Proact Digital Plus Front Panel Rev. H
  • Woodward 8271-651 - Digital Speed Reference
  • Woodward 3077-474C - 8605895 5501-031 D Circuit Module
  • WOODWARD 5466-257 REV.-C - NETCON 5000 MODEL REMOTE TRANSCEIVER I/O MODULE
  • Woodward 8273-101 Rev: A - 2301D Digital Load Sharing and Speed Control
  • WOODWARD 8272-799 - 2301A SPEED CONTROL WITH REMOTE REFERENCE REV:C
  • Woodward 8272-517 - PM Motor Control
  • Woodward 8290-048 8290048 Rev. F - Generator Load Sensor
  • woodward 8273-1012 rev c - 2301e Load Sharing and Speed Control
  • WOODWARD 9905-797 - DIGITAL SYNCHRONIZER AND LOAD CONTROL FOR 3 PHASE GENERATORS
  • WOODWARD 8280-3014 - 723 PLUS DIGITAL CONTROL REV NEW
  • WOODWARD 8440-1884 REV G - GENSET CONTROLLER EASYGEN-2500-5/P1
  • Woodward 8272-683 K - Digital Reference
  • WOODWARD 9907-014 - SPEED CONTROL 2301A REV H
  • Woodward Type UG-8 P/N 037260 - Governor R.P.M 1075-1650 Motor KM58-20
  • WOODWARD 9905-970 - LINKNET 6 CHANNEL 100 OHM RTD Rev:J
  • Woodward 9907-1183 Rev C - Steam Turbine Digital SCREEN 505E Turbine Control
  • Woodward 8440-1614 - GCP-30 Genset Control Package, Rev: F, Type 1, E231544
  • Woodward DC11006-304-024 - ACTUOTOR DYNA ACTUATOR - BARBER-COLMAN
  • Woodward 9905-971 - LINKNET 6 CHANNEL 100 OHM RTD Rev:K
  • Woodward DYNK-10249 - Actuator Controller Kit - DYNA 2000
  • Woodward LR21035 - MFR1 MULTI FUNCTION RELAY REV F
  • Woodward 8440-1831 - EASYGEN 3200-5 P/N: REV. G Gererator Controller
  • Woodward 8272-516 - PM MOTOR CONTROL REV J
  • Woodward 8440-2080 - EASYGEN 2000 genset controller EASYGEN-2300-5/P1
  • Woodward 505DE - Digital Control System
  • Woodward 701 - Digital Speed Control 18-40 VDC 4-20 MA
  • Woodward 8440-1799 - EASYGEN-350 REV B
  • Woodward 8272-582 - Apm Motor Control 100-220v AC/DC
  • Woodward 5501-031 D - 3077-474C 8605895 Circuit Module
  • Woodward XD1-T - XD1T55SAT TRANSFORMER DIFFERENTIAL PROTECTION RELAY
  • Woodward 8272-517 - PM Motor Control 220vac
  • Woodward 8934-658 - Repair Kit UG8D Governor
  • Woodward 5437 18 - module netcon derivative analog rev.A
  • Woodward 8272-171 A - Pm Motor Control
  • Woodward MRN3-1/2 - SEG mains uncoupling relay MRN314D mains decoupling relay
  • Woodward 9905-373 - Digital Synchronizer and Load Control 18-40 VDC Rev P
  • Woodward 5431-640 C - Dual Dynamics 1000 Series Speed Control Module
  • Woodward 5501-031 D - 3077-474C 8605895 Circuit Module
  • Woodward 9907-247 - 828 DIGITAL CONTROL
  • Woodward 8440-1855-G - EASYGEN-2200-5 /P1 12/24VDC GENSET CONTROLLER
  • Woodward NC3-2-8 (NO) - GENERATOR CONTROLLER
  • Woodward 8271-467 K - 2301 LOAD SHARING AND SPEED CONTROL PART NO:
  • Woodward 8440-2177 A - SPM-D2-10 Digital Synchronising Controller
  • Woodward LXMG1614E-14-11 - CCFL and UV Lamps Inverter Module
  • Woodward 8270-990 - signal converter
  • Woodward 9905-068 - LOW VOLTAGE 2301A LOAD SHARING & SPEED CONTOL P/N:
  • Woodward 8901-051 - BOOSTER SERVOMOTOR, SINGLE CYLINDER, 2:1
  • Woodward 8444-1024 D - MWS4-55M CONTROL MODULE UNIT
  • Woodward 5448-914 - GCP-20 Genset Control GCP-20 REV D P/n:
  • Danfoss BHA-1 018-1942 - Hydraulic Actuator
  • Woodward 9905-001 L - SPM-A SYNCHRONIZER
  • Woodward 5464-850 - Module
  • Woodward 5501-371 - Micronet Simplex Mpu Aio Rev C
  • Woodward 8272-132 B - POWER SENSOR
  • Woodward 9907-028 - SPM-A Synchronizer
  • Woodward SA-3678-AM-2 - Overspeed Electric Governor, Model ESSE2-AM
  • Woodward E8250-502 - GOVERNOR ACTUATOR
  • Woodward 8440-1884 J - Controller EASYGEN-2500-5
  • Woodward 5441-693 - DIGITAL I/O MODULE -MISSING PART
  • Woodward SA-4450 - Speed Controller APECS 3100 For Magnetic Pickup
  • Woodward 9903-466 - 701 DIGITAL SPEED CONTROL REV G
  • Woodward 1765-843 - Governor Speed Adjusting Motor P/N Type: SMM40 220V AC 50/60Hz
  • Woodward 9905-760 - Linknet Termination Module
  • Woodward 9907-247 - 828 DIGITAL CONTROL UNIT REV K
  • Woodward 5484-721 - motor
  • Woodward 8440-1734 - MFR-2 Rev.A Multi Function Relay MFR-2
  • Woodward CSC3SUWA - Controller
  • Woodward 8440-1667 - REV B SPM-D1010B/XN
  • Woodward 8406-120 - egcp-2 digital control
  • Woodward DPG-2201-002 - DIGITAL CONTROLLER REV D
  • Woodward 8272-516 - Pm Engine Control Rev J
  • Woodward 8440-1831 - EASYGEN 3200-5 P/N: REV. K - WITHOUT ACCESSORIES
  • Woodward 8273-101 - LOAD SHARING & SPEED CONTROL
  • Woodward 8440-1855-G - EASYGEN-2200-5 /P1 12/24VDC GENSET CONTROLLER
  • Woodward 9907-247 - 828 DIGITAL CONTROL UNIT REV K
  • Woodward LR21035 - MFR1 MULTI FUNCTION RELAY REV J
  • Woodward 8404-009 - PROACT DIGITAL PLUS FRONT PANEL REV J
  • Woodward 9905-204 - Rev N SPM-A synchronizer
  • Woodward 8521-367 - UG-8 P/N r R.P.M 750-1280 Governor / UG8
  • Woodward 9907-175 - Load Sharing Module Rev. B
  • Woodward 5464-645 - DRIVER MODULE REV A 2C ACT DRIVE
  • Woodward 8404-009 - PROACT DIGITAL PLUS FRONT PANEL REV J
  • Woodward 9907-175 - Load Sharing Module Rev. B
  • Woodward 8406-102 - Rev A EGCP-2 Digital Control Engine Generator 8406102
  • Woodward EASYGEN-2500-5 - Controller Genset
  • Woodward 8440-2082 - Controller
  • Woodward 8272-516 - PM MOTOR CONTROL REV J
  • Woodward 9905-373 - Digital Synchronizer and Load Control 18-40 VDC Rev P
  • Woodward 5501-429 - Actuator Controller 25mA 2 Channel , (UPP)
  • Woodward 8440-1869 - SPM-D10 Synchronizing System Control-SPM-D10B/PSY4-F-D
  • Woodward 9907-175 - Load Sharing Module Rev. A
  • Woodward 8200-224 - Servo Position Controller
  • Woodward 9906-619 - 723 PLUS DIGITAL CONTROL ( 8280-604 )
  • Woodward 8440-1519 - EASYGEN PART NO: REV: 4
  • Woodward 5501-371 - REV C MODULE- MICRONET SIMPLEX MPU & AIO FTM
  • Woodward EASYGEN-3200-5/P1 - Generator Controller Module Rev F
  • Woodward 8440-1884K - GENERATOR CONTROLLER EASYGEN-2500-5 REV,K
  • Woodward 5466-353 - REV C NETCON MAIN CHASSIS TRANSCEIVER