K-WANG

+086-15305925923
Service expert in industrial control field!
NameDescriptionContent
Adequate Inventory, Timely Service
pursuit of excellence 
Ship control system
Equipment control system
Power monitoring system
Current position:
新闻动态
newS
   
Brand

ABB SPAD 346 C3 Differential Protection

From: | Author:Wang | Time :2025-06-20 | 553 visit: | 🔊 Click to read aloud ❚❚ ▶ | Share:

ABB SPAD 346 C3 Differential Protection

Scope and Introduction

Document purpose: To introduce the differential protection setting calculation of SPAD 346 C3 protection relay module SPCD 3D53, which is applicable to two winding power transformers and involves differential protection of three winding power transformers, motors, generators, etc., including setting suggestions and discussion of intermediate current transformer (CT) requirements.

Protection principle: By comparing the phase currents on both sides of the protected object, when the differential current of a certain phase current exceeds the starting value of the stable action characteristic or the instantaneous protection stage value, the relay sends an action signal, which has the characteristics of fast action speed, high stability of faults outside the area, and high sensitivity to faults inside the area. CT selection and relay setting should be cautious.


Two winding power transformer protection

(1) Vector Group Matching (SGF1)

By using SGF1/1... 8 switches, the vector groups of power transformers are numerically matched on the high voltage (HV) and low voltage (LV) sides. Based on the phase shift and delta connection inside the relay, there is no need for intermediate CT, and the zero sequence component in the phase current can be automatically eliminated. Different vector groups correspond to different switch positions and check sums.

(2) CT ratio correction (I ₁/In, I ₂/In)

When the CT secondary current is different from the rated current under the rated load of the power transformer, the CT ratio on both sides of the transformer needs to be corrected. Calculate the rated load of the power transformer firstI nT=S n/(3 × U n), then calculate the transformation ratio correction settings I 1/In=I nT/I p (HV side) and I 2/In=I T/I p (LV side), where I p Rated primary current for CT, and the rated input current (1A or 5A) on the HV and LV sides of the relay can be different, using 1A secondary current can improve CT performance.

(3) Startup ratio (S)

Due to the inaccuracy of CT and changes in the position of the tap changer, an increase in load current will cause differential current to increase by the same percentage. The setting of the start-up ratio (S) affects the slope of the relay action characteristics between the first (fixed 0.5 × In) and second turning point (set I 2tp), which is calculated as the sum of CT accuracy on both sides, tap changer adjustment range, relay action accuracy (4%), and required margin (usually 5%).

(4) Basic Startup Settings (P/In)

The basic setting (P) defines the minimum sensitivity of protection, taking into account the no-load current of power transformers, which is generally calculated asP=0.5 × S+P, where P 'represents the no-load loss of the transformer at maximum voltage, usually used when the actual value is unknown

P ′=10%。

(5) Second turning point (I ₂ tp/In)

The second turning point defines the point at which the influence of the activation ratio S in the action characteristics ends and the slope begins at 100%. Its setting needs to balance stability and sensitivity. In power transformer protection applications, the range of 1.5-2 is usually selected, with 1.5 being more stable for out of zone faults and 2.0 being more sensitive for in zone faults.

(6) Second harmonic blocking (Id2f/Id1f>)

The excitation inrush current of power transformers during excitation contains a large amount of second harmonic. Differential protection is locked by detecting the content of second harmonic (low setting stage). The recommended setting for second harmonic locking in power transformer protection is 15%, which can be enabled by setting the switch SGF2/1=1, and the setting can be reduced to 10% during the first excitation.

(7) Instantaneous differential current stage (Id/In>>)

It is recommended to use it together with the low setting stage to provide faster protection in case of severe faults, and is not subject to harmonic blocking. Its setting needs to be high enough to prevent the differential relay module from tripping when the transformer is excited, usually 6-10.

(8) Fifth harmonic blocking and unlocking (Id5f/Id1f>, Id5f/Id1f>>)

Used to lock the relay action when there is a sudden voltage rise (or frequency drop), based on the fifth harmonic component of the transformer excitation current to monitor overexcitation. Due to the need to know the magnetization characteristics of the transformer, it is usually not enabled, that is, SGF2/3 and SGF2/4 are set to 0.

(9) Interference recorder

The internal interference recording function of the relay module is a powerful tool for analyzing the causes of transformer inrush current and tripping. The factory default settings are used during normal operation, and the serial communication parameters V241 and V245 need to be changed during inrush current research.


Three winding power transformer protection

The SPAD 346 C relay can be used for three winding transformers or two winding transformers with two output feeders. On the dual feeder side of the transformer, the two CT currents of each phase must be summed through parallel connections, usually requiring an intermediate CT to handle vector group and/or ratio mismatches, and at least 75% of the short-circuit power should be fed from the transformer side with only one connection to the relay, otherwise it may cause unstable protection.


Motor and generator protection

The calculation process for setting up differential protection applications for motors or generators is very similar to that of power transformers, but the vector group should be set to Yy0. The starting ratio (S) is calculated as the sum of the CT accuracy on both sides, the relay action accuracy (4%), and the required margin (usually 2.5-5%). The second turning point (I ₂ tp/In) may cause CT saturation due to current during motor start-up, with a typical setting value of 1.0. The generator is usually between 1.0-1.5, and the motor and generator usually do not require second or fifth harmonic blocking.


Combination protection of motor and autotransformer

The differential relay measures the phase current on both sides of the protected object, and the protection area includes the autotransformer and motor. The current between all autotransformer/motor combinations and the network must be measured, and its setting is the same as that of ordinary motor protection applications. The autotransformer will have a typical starting sequence during the motor starting process, from power supply to acting as a parallel reactor and then to bypass.


Variable frequency motor and its power transformer protection

SPAD 346 C can only be used to protect power transformers that supply power to frequency converters, and is not suitable for protecting power transformers or motors powered by frequency converters, as the fundamental frequency component in the relay is numerically filtered through a Fourier filter and is not suitable for measuring the output of frequency converters.


Short overhead or cable protection

SPAD 346 C can be used for differential protection of overhead or cable lines. When the distance between measurement points is long, an intermediate CT may be required to reduce CT load. Using 1A secondary current can reduce CT load, and the actual accuracy limit factor (Fa) of CT can be calculated to ensure compliance with requirements.


Summary

This guide describes how to select and calculate differential protection settings for SPAD 346 C protection relays, introduces the working principle and setting effect of relays, and presents the calculation process through examples. It also describes protection application examples for three winding power transformers, motors, and generators, discusses the applicability of SPAD 346 C relays in frequency converter applications, and finally describes differential protection for short overhead or cable lines through examples of calculating the actual accuracy limit factor of intermediate CT.


  • Siemens 6SL3244-0SA01-1AA0 - SINAMICS G120 Control Unit
  • DANFOSS 175Z2688 - COATEDE CONTROLUNIT VLT5000
  • SIEMENS 6FM1721-3AA20 - Positioning Module
  • REXORTH VTS0605 PVAR S21 - Drive Module
  • BECKHOFF 2915-0000 - Control Module
  • COOPER EATON CGLine 400 40071347901 - CEAG CG Controller
  • SIEMENS 3UF5031-3AN00-1 - SIMOCODE DP Basic Unit
  • SIGMATEK DNC305 05-011-305 - Drive Controller
  • Multivac MV1 10249768 - Control Module
  • SCHNEIDER ELECTRIC MES114 59646 & 59645 - Circuit Breaker Accessory
  • CAMILLE BAUER CAPAX 44-580-0012 - Transmitter
  • HENGSTLER VT360P LS1/TOK - Encoder
  • BURKERT 8792 - 24V DC IP65 / IP67 Positioner
  • SENSOPART V10-OB-A1-W6 - Vision Sensor
  • ALLEN-BRADLEY 1762-L40BXB SER.C REV.J - MicroLogix 1200 Controller
  • HITACHI CPU22-02HC 33025801-2 - CPU Module
  • HITACHI AGH-0 33034810-2 - Control Board
  • PHILIPS AIH110 VER 1.0 - Control Module
  • BAUMULLER DO8000 - Drive Controller
  • B&R PS477 3PS477.9 Rev.C0 - Power Supply
  • ABB ALFA LAVAL 200-CISB - Communication Interface 2 x SatBus
  • Moeller MI4-570-TA1 - HMI Operator Panel
  • ABB ACH550-01-06A9-4+B055 - Variable Frequency Drive
  • ABB TPU2 3HNE00313-1 REV 12 - Teach Pendant Unit
  • Schneider Electric BRS368H130ABA - Stepper Motor
  • Foxboro FCM100E P0972ZA - I/A Series Communication Module
  • Siemens 6ES7 450-1AP00-0AE0 6ES7450-1AP00-0AE0 - Simatic S7 Version:04 Counter Module
  • Schneider Electric ATV320U07N4W - Altivar Machine Drive
  • Priva TouchPoint Flush V06:02 5060002 - Control Panel
  • Lenze ESMD402L4TXA - 4kW SMD Inverter Drive
  • Lenze ESMD402L4TXA - 4kW SMD Inverter Drive
  • Schneider Electric PM210 PM210MG - Powerlogic Power Meter
  • ASCOM U982-DB/1C U982 - Power Supply / Communication Module
  • DYADIC SYSTEMS SCN5-010-050-S03-NA - Servo Cylinder
  • Reliance Electric GMI-S04 - AC/AC CONVERTER 380/400V 50/60Hz 3.9/5.2A
  • Pro-Face GLC150-BG41-XY32KF-24V 3080060 PFXGLC150BDBP - Touch Screen HMI
  • ROFIN RSL TERMINAL V2 0185.01/03 - TERMINAL
  • HONEYWELL R7241E1077 - Burner Control / Amplifier
  • SEW MM22C-503-00 8241201 - 2.2kW Movimot Drive
  • Brand Digital III 50mL - Burette
  • Danfoss 195N0039 VLT2811PS2B20STR1DBF00A00C0 - 2.4kVA VLT Drive
  • SONY LG10-2 EK1 - Digital Gauge Indicator
  • EMERSON SKD3400750 - 7.5kW AC Drive
  • SIEMENS 6AV6 542-0AG10-0AX0 - MULTIPANEL HMI
  • TELEMECANIQUE ATV21HU55N4 - ALTIVAR21 5.5KW Variable Speed Drive
  • MITSUBISHI A985GOT-TBA-EU - GOT900 Touch Screen HMI
  • SCHNEIDER LXM32AD30N4 - Lexium 32 Servo Drive
  • SICK PSR01-1501 M20Z-02550A122 - Safety Laser Scanner
  • GECMA CHALLENGER 15-2-FMO - LITE TOUCH Monitor
  • Uniop EK02 6ZA982 - HMI Operator Panel
  • TELEMECANIQUE ATV18U54M2 - SQUARE D ALTIVAR 18 3kW Drive
  • Schneider Electric ATV312HU75S6 - 7.5kW Altivar 312 Drive
  • Siemens 6GK7243-5DX30-0XE0 6GK7 243-5DX30-0XE0 - Communications Processor
  • Schneider Electric LV432455 VIGI630 - 3POLE Earth Leakage Module
  • Rexroth PSI 6100.750 L1 R911170694-107 - frequency inverter / inverter
  • SWEDISH MICROWAVE AB Ku-Band BDC 138010-45-D0 - Block Downconverter
  • METTLER TOLEDO IND429 IND429-BB30 - Weighing Terminal
  • Siemens 6SL3210-5HE10-4UF0 - Sinamics V90 Servo Drive
  • B&R X20CP0482 Rev.D0 - X20 CPU Module
  • Mitsubishi FR-E720S-110SC-EC FRE720S110SCEC - 31A~11A Drive With Filter
  • ABB ACH580-01-026A-4 - Variable Frequency Drive
  • Siemens 6SL3210-1KE13-2AP1 - SINAMIC G120CDP 1.1kw Drive
  • Schneider Electric TM250D 4P3D LV431440 - Compact NSX250 Circuit Breaker
  • RELIANCE ELECTRIC GD.722.81.00-A 802288-74C - MAXITRON Servo Control Card
  • Uniop EK02 6ZA982 - HMI Operator Panel
  • Siemens 6SE9113-7JA13 - MICRO MASTER Junior 1.5kW Inverter
  • Mitsubishi FR-E720S-110SC-EC FRE720S110SCEC - 31A~11A Drive with Filter
  • Johnson Controls FEC2621 MS-FEC2621-0 - Field Equipment Controller
  • BENDER IR475LYT-429 - A-ISOMETER Insulation Monitor
  • Berger lahr D550 RS15 22.550-00-30b - Stepper Drive
  • Rexroth PSI 6100.750 L1 R911170694-107 - Frequency Inverter / INVERTER
  • KOYO 205 D2-06B-1 D2-240 H2-ECOM D2-08ND3 F2-08TRS - DIRECT LOGIC PLC WITH MODULE
  • TELEMECANIQUE ATV18U54M2 ATV18U54M - SQUARE D ALTIVAR 18 3kW Drive
  • Lenze 471-E1.D - Board / Controller Speed
  • Mitsubishi FR-A740-00038-EC - Frequency Inverter
  • Johnson Controls IOM3723 MS-IOM3723-0 - Input/Output Module
  • CURTIS 1238-5602 - AC Motor Controller
  • FOXBORO P0912XX REV.A - 220VAC Power Supply
  • Siemens 6SE9113-7JA13 - MICRO MASTER Junior 1.5kW Inverter
  • Mitsubishi FR-A740-00038-EC - Frequency Inverter
  • KOYO 205 D2-06B-1 D2-240 H2-ECOM D2-08ND3 F2-08TRS - DIRECT LOGIC PLC WITH MODULE
  • AUTZ M406D-00101 - Servo Motor
  • Lauer PCS095 PG095.508.BB - Operator Panel
  • ABB SCOP45SB/DX232 - SattCon OP45 SB Operator Panel
  • SEW Eurodrive MCH42A0030-5A3-4-00 MDX60A0030-5A3-4-00 - 4.8kVA Movidrive Inverter
  • BENDER IR475LYT-429 - A-ISOMETER Insulation Monitor
  • Johnson Controls FEC2621 MS-FEC2621-0 - Field Equipment Controller
  • Johnson Controls IOM3723 MS-IOM3723-0 - Input/Output Module
  • Berger lahr D550 RS15 22550-00-30b - Stepper Drive
  • SIEMENS 6FX1120-4BD03 6FX11204BD03 5702049304.00 E-Stand: A - Sinumerik Module
  • Allen-Bradley 1771-NIV B - HIGH RESOLUTION ISOLATED ANALOG SERIES Module
  • HONEYWELL XFC2D06001 - Flow Computer / Controller
  • Contraves Varidyn Compact ADB 380.90M - DC Drive 380v - 400v 90A 50kVA
  • Red Lion Control GEM52000 - Control Module
  • Siemens 6ES5 955-3NC13 - modular power supply TYPE:DIN41752
  • Danfoss ICV50 G20Mn50T / 027H5200 - Valve zaw
  • Eberle PLS508 P-814 / 2X EA-88 / A-812 / MT-81 / S-11 - PLC with Modules
  • Siemens 6ES7 314-6CF01-0AB0 6ES7314-6CF01-0AB0 - SIMATIC CPU314C-2 DP
  • EBERLE EM-525-87 EM52487 - ICE DETECTOR BASE UNIT
  • Telemecanique / Schneider TSXRKZ02 - TSX Micro automation plus 7module
  • B&R 5DLSDL.1001-00 - Display Link Receiver
  • Siemens 6FX1120-4BD03 6FX11204BD03 5702049304.00 E-Stand: A - Sinumerik Module
  • ALLEN-BRADLEY 1771-NIV A - HIGH RESOLUTION ISOLATED ANALOG SERIES Module
  • ALLEN-BRADLEY 1771-NIV B - HIGH RESOLUTION ISOLATED ANALOG SERIES Module
  • Contraves Varidyn Compact ADB 380.90M - DC Drive 380V - 400V 90A 50kVA
  • Contraves Varidyn Compact ADB 380.90M - DC Drive 380V - 400V 90A 50kVA
  • Ropex RES-202 - Resistron Temperature Controller
  • HONEYWELL XFC2D06001 - Flow Computer / Controller
  • Telemechanics ATV452U40 - DIMMER ALTIVAR5 SERIES 452 4kW 5HP Frequency Inverter
  • VEGA VEGAPLUS61 PS61.XXAGPHAMAX - Radar Level Sensor
  • BRANSON ULTRASONIC TRANSDUCER - Ultrasonic Transducer
  • Danfoss ICV50 G20Mn50T / 027H5200 - Valve Valvola Zaw
  • Schneider Electric 2001549/1 GALAXY PW 5102851200 NT07 - panler card
  • REXROTH VT3006-36 A - Proportional Valve Amplifier
  • Allen-Bradley 1746-OBP16 SERIES:C - SLC 500 OUTPUT MODULE
  • SCHNEIDER LXM32MD12N4 - Lexium 32 Servo Drive
  • Schneider Electric ATV630U22N4 - 2.2KW Altivar Process Drive
  • Allen-Bradley 1746-OBP16 SERIES:C - SLC 500 OUTPUT MODULE
  • Vanderlande 0E2550-00002... - Bagtrax Integrated Power Module 400V 32A
  • B&R X20CP0410 Rev.D0 - X20 CPU Module
  • VANDERLANDE 0E2550-00002 02EDD2B0100 - BAGTRAX Integrated Power Module 400V 32A
  • Rexroth R061205010 - Linear Bushing / Bearing
  • INDRAMAT TVM1.2-50-220/300-W0-220/380 - Power Supply Module
  • Vanderlande 0E2550-00002... - Bagtrax Integrated Power Module 400V 32A
  • HOMAG KEB 07F5S1A-YA00 09E5T60-1001 - Combivert Inverter WITH KEYPAID AND FILTER
  • Siemens 3RW3047-1BB14 - Soft Starter
  • Sumitomo AF-500 AF502-A40 - 0.4kW Transistor Inverter
  • Sumitomo AF-500 AF502-A40 - 0.4kW Transistor Inverter