Product model and hardware composition
UNITROL 1000-7: Basic model, maximum continuous excitation output of 7A, aimed at synchronous motor manufacturers and system integrators who pursue low cost.
UNITROL 1000-15: Core controller body, maximum continuous excitation DC output of 15 A; power unit supports AC or DC power supply; Comes with a local human-machine panel; Can run independently.
UNITROL 1000-PM40: Independent IGBT power expansion module; Communicating with the 1000-15 controller via the CAN-Bus bus, plug and play, the controller automatically configures PM40 without the need for additional debugging; The combination of the two is called UNITOL 1000-40, which increases the maximum continuous excitation current to 40 A and is suitable for retrofitting old DC excitation units for use in scenarios with excitation currents of 15-40 A.
The PM40 panel LED indicator displays critical operating status.
Typical application wiring scenarios
Parallel excitation (configurable short-circuit enhancement compound): Directly powered by the machine end, supporting external short-circuit compensation.
Redundant dual regulator configuration for PMG permanent magnet generator power supply: Two UNITROL 1000-15 units form a 100% redundant excitation system, with power provided by the permanent magnet generator PMG.
Old unit renovation: Replace traditional DC excitation machine: 1000-15+PM40 (UNITROL-40), upgrade and renovate old analog and mechanical voltage regulators.
UNITROL 1000-15 Function List
Standard Built in Functions (BASIC)
Voltage PID regulation, power factor cos φ PID regulation, reactive current PID regulation, excitation current PI manual regulation;
Output voltage testing control, internal digital setpoint; Non disruptive switching between various working modes;
Soft start function; Reactive current compensation under grid connected conditions; V/Hz limit;
Minimum excitation current limit; Three stage delay maximum excitation current limit (with temperature correlation);
Under under excitation conditions, reactive power limitation is achieved based on active power; Stator voltage limitation; Stator current limitation (temperature dependent);
Multi machine parallel reactive power balancing regulation: RS485 interface, supporting up to 32 units for parallel reactive power leveling;
Pre matching of voltage before grid connection (with the help of synchronous devices for voltage regulation);
Modbus RTU communication (RS232/RS485);
Undervoltage detection can trigger external short-circuit enhancement (compound excitation);
Built in step testing function for given values; Complete alarm and trip signal output.
Optional authorization/option functions
Automatic synchronization and Synchrocheck synchronization check function (built-in synchronization logic in the regulator);
Rotating diode fault monitoring;
IEEE 2A/2B standard power system stabilizer PSS;
Redundant system enhanced monitoring (PT voltage circuit monitoring);
CAN Bus setpoint tracking, used for dual machine redundancy;
Redundant regulator standby mode.
I/O interface
All terminals of UNITOL 1000-15 are arranged at the bottom of the equipment:
4-channel digital input;
4-channel reconfigurable digital output (can also be set as digital input);
3 analog inputs;
2-channel analog output;
RS232: Connect to the CMT 1000 laptop debugging software;
RS485: Modbus RTU communication/multi machine parallel reactive power balancing;
CAN-Bus: Docking with PM40 power module for redundant system data exchange.

Human Machine Interaction HMI
Local panel
The device comes with 4 buttons and a backlit LCD display, allowing all operations to be completed without the need for a laptop
I/O port configuration;
Select the display screen to show the measurement quantity;
Parameter setting modification;
Real time monitoring of operational status.
CMT 1000 PC Debugging Software (Windows Platform)
Debugging and maintenance tools, core capabilities:
Read, write, and configure all parameters;
Power angle/P-Q limit graphic display, visually viewing the working point of the limiter;
Oscilloscope function: can select 4 signal graphics for recording; A total of 20 channels were recorded with a sampling resolution of 50ms;
Export and save numerical data for post fault analysis.
System delivery form
ABB provides a complete pre testing system for the factory, with three options:
Single channel system: installed with a complete set of base plates, used for small and medium-sized water turbines, diesel synchronous generators, and can also be used for synchronous motor excitation.
Dual channel 100% redundant system: for situations with high requirements for reliability and availability.
Complete small cabinet set: The entire excitation system is integrated into an independent switchgear, including excitation switches, interface relays, transmitters, fuses, and all other components; Suitable for projects where the existing cabinet space is insufficient on site.
Key technical parameters
UNITROL 1000‑15
Auxiliary power supply: three-phase AC 9-250 V; single-phase AC 50-250 V; DC 18-300 V; maximum power consumption 25 W; withstand voltage 2 kV.
Power unit supply: single-phase/three-phase AC 0-250 V/DC 0-300 V, frequency 40-600 Hz; withstand voltage 2 kV.
Excitation output: continuous DC 15 A;>50 ℃ environmental current derating 1 A/K; Short term overload: maximum 30 A for 10 seconds; maximum 20 A for 4 minutes.
Built in 24 VDC auxiliary source, with a maximum output of 300 mA.
Measurement input: The maximum three-phase voltage of the generator is 250 V; the single-phase current of the generator is 1 A; the maximum single-phase voltage of the power grid is 150 V; the measurement frequency is 10-100 Hz.
Analog I/O: ± 10 V range, input impedance 100 k Ω; supports external potentiometer reference output.
Voltage regulation accuracy:<0.1%.
Environmental conditions: operating temperature 0-60 ℃; Storage -20~+75 ℃; Meet EN 61000-6-2/EN 61000-6-4 electromagnetic compatibility; Protection level IP20; The total weight of the machine is 5kg.
UNITROL 1000-PM40 power module
Power supply is the same as 1000-15;
When using three-phase AC/DC power supply: continuous excitation output of 40 A DC; 10 seconds short-term 80 A; 4 minutes short-term 50 A;
The output capability of single-phase AC power supply decreases; Protection IP20; Plug and play through CAN bus and 1000-15 controller.