The first volume user manual (third edition Rev. D) of the Automation Direct DL06 micro PLC introduces the hardware specifications, installation and wiring specifications, CPU operating mechanism, memory mapping, high-speed I/O, and basic programming architecture of 9 models. It supports 20 inputs/16 outputs, dual serial communication, 229 instructions, PID closed-loop and RLLPLUS stage programming, meets Class 1 Div.2 explosion-proof and UL/CE certification, and is designed for logic control and motion control scenarios of small automation equipment.
Hardware core specifications
Project parameters
Local I/O 20 inputs (X0~X23), 16 outputs (Y0~Y17), octal addressing
229 instructions (Boolean, Math, PID, High Speed I/O)
Program memory 14.8K words (7.6K ladder diagram+7.6K V memory)
Scanning speed Boolean instruction<0.6 μ s, 1K steps approximately 1-2ms
Communication port Port1 (RS232 9600 fixed); Port2 (multi protocol, 300~38400bps)
Working temperature 0~55 ℃, humidity 5~95%, no condensation
Certified UL, CE, cUL, Class 1 Division 2
Installation and wiring specifications
Installation requirements
Method: DIN rail 35mm, horizontal installation
Spacing: Up and down ≥ 30mm, left and right ≥ 20mm
Grounding: Single point common grounding, shielded wire double ended grounding
Wiring rules
Wire gauge: 16~22AWG, single end ≤ 2 pieces
Protection: There is no built-in fuse in the output, it is recommended to add an external fast fuse
Inductive load: DC coil with parallel freewheeling diode, AC coil with MOV/TVS
I/O type
Input: DC input supports drain/source type, AC input 80~132VAC
Output: Relay (2A/point), transistor (0.5~1A/point), AC thyristor (0.5A/point)

CPU and system operation
work mode
RUN: Execute program, refresh I/O
STOP: Stop output, prohibit program changes
TERM: Allow programming/monitoring/mode switching
scanning process
Power on initialization → Read input → Peripheral service → Program execution → PID operation → Write output → Diagnosis
power-down retention
Supercapacitors: hold for several hours
Optional battery D2-BAT-1: Keep for 5 years
Default hold area: C1000~C1777, V400~V37777, CTO~CT177
Diagnostic protection
Watchdog: default 200ms, timeout shutdown
Status LED: PWR/RAN/CPU/Communication Transmission and Reception Status
Error code: stored in V7750~V7757, supports historical queries
Memory Mapping and Resources
Addressing rule: All use octal, no 8 or 9 digits
core resources
Control relay (C): 1024 points
Timer (T): 256 pieces
Counter (CT): 128 pieces
Stage (S): 1024 (RLLPLUS)
Special relays (SP): 512 pieces
V Memory: 7616 words, user available 7488 words, 128 words non-volatile
High speed I/O (HSIO) 6 modes
Mode 10: High speed counter (up to 7kHz)
Mode 20: A/B phase orthogonal counter
Mode 30: Pulse output (up to 10kHz, driving step)
Mode 40: External/Timer Interrupt
Mode 50: Pulse capture (minimum 70 μ s)
Mode60: Adjustable input filtering
Programming Architecture
Standard RLL: ladder logic, Boolean/Math/Table instructions
DRUM sequencer: 16 step sequential control, triggered by time/events
RLLPLUS Stage Programming: State Machine Process, Suitable for Sequential Actions
Communication Protocol
Port 1: K-sequence, DirectNET, MODBUS RTU (slave only)
Port 2: Supports master/slave stations, supports MRX/MWX commands for reading and writing network data
Key issues
Question 1: How are the 9 models of DL06 divided by I/O type? What are the core advantages of DC models compared to AC models?
Answer: There are 9 types based on input (AC/DC), output (relay/transistor/AC), and power supply (AC/DC). The DC input model supports high-speed I/O (counter/pulse output/interrupt), with a response time of up to 70 μ s, and can be used for simple motion control; The AC model does not have high-speed function and is only suitable for high voltage scenarios.
Question 2: How is the I/O response time of DL06 calculated? How to achieve the fastest response?
Answer: Standard response=input delay+scan time+output delay; The fastest achievable input delay+instruction execution time. Implement the fastest immediate I/O command, disable X0~X3 input filtering, use high-speed I/O mode, and avoid waiting for scan cycles.
Question 3: How to configure the power-off maintenance of DL06? Which regions are kept by default?
Answer: Maintain the range through AUX57 or software settings. Default hold: Control relays C1000~C1777, V memory V400~V37777, counters CT0~CT177; The timer and stage are not maintained by default. Long term maintenance requires the installation of D2-BAT-1 batteries.