K-WANG



Product positioning and series division
The TAIYO LX series is a brushless AC generator with a power coverage of 11.5~2250kVA, divided into three major models:
LX-G: Basic type, main stator outputs power to AVR
LX-E: Heavy duty type, with auxiliary winding providing strong excitation
LX-H: High performance type, independently powered by PMG permanent magnet generator, with the strongest ability to resist harmonics and non-linear loads
Core Features
Excellent electrical characteristics
Steady state voltage regulation accuracy: ± 1.0%
Transient pressure drop: ≤ 25%, restored to ± 3% within 2 seconds
Voltage regulation range: rated voltage * * ± 5%**
High reliability and long lifespan
Based on ISO9001/ISO14001 quality system
Brushless excitation, no carbon brush wear, easy maintenance
Compact and lightweight
Optimize electromagnetic and structural design, with small size and light weight
Rich models and high performance
Three level excitation scheme covers different load requirements
Unified 4-pole structure for full power range, compatible with diesel engine drive
Key electrical performance indicators
Project parameters
Steady state voltage regulation rate ± 1.0%
Transient voltage adjustment with sudden 100% load, voltage drop ≤ 25%, restored within 2 seconds
Overspeed tolerance of 120% rated speed, lasting for ≥ 2 minutes
Unbalanced load withstand 20% rated current negative sequence current
No load waveform distortion rate ≤ 10%
Short term short-circuit capability 50Hz: 250%/2s; 60Hz: 300%/2s (excluding LX-G)
Voltage adjustable range rated voltage ± 5%

Comparison of excitation systems
LX‑G
Main stator output → AVR → excitation winding
Applicable: Ordinary resistive/linear loads
LX‑E
Dual power supply of main stator and auxiliary winding → AVR
Applicable: Heavy load, impact load
LX‑H
PMG permanent magnet generator independent power supply → AVR
Applicable: Nonlinear loads such as thyristors and rectifiers, with the most stable voltage
Standard specifications
Project standard value
Cooling method: self ventilated
Protection level IP20 (optional IP21~23)
Insulation level F
Phase number/wire system three-phase, 3-wire/4-wire
Power factor 0.8 lagging
Number of poles: 4 poles
Environmental temperature -5 ℃~+40 ℃
Altitude ≤ 1000m
Ball bearings or roller bearings
Standard IEC
Power Range (Typical)
LX‑G/E:11.5kVA ~ 500kVA
LX‑H:600kVA ~ 2250kVA
Supports dual formats of 50Hz/400V and 60Hz/440V
Divided into two levels: continuous power and backup power
Structural components
The core components include:
Stator/rotor winding and iron core
Rotating rectifier (brushless key)
Excitation armature, excitation magnetic field
Bearings, end caps, fans, junction boxes
LX-H permanent magnet secondary excitation machine with PMG
Optional configurations
Protection level: IP21~IP23
Parallel operation components (AVR synchronization)
Bearing/stator temperature sensor and display
Space heater (anti condensation)
Anti high humidity and anti salt spray coil treatment
Low temperature scheme (-5 ℃~-20 ℃)
Speed generator, double bearing, special coupling
Single phase output configuration (models 46C and below)
Key issues
Question 1: What are the core differences between the LX-G/LX-E/LX-H models? What loads are suitable for each?
answer:
LX-G: Main stator excitation, low cost, suitable for ordinary linear loads.
LX-E: Strong excitation of auxiliary winding, suitable for heavy and impact loads.
LX-H: PMG permanent magnet independent excitation has the strongest anti harmonic ability and is most suitable for nonlinear loads such as thyristors and rectifiers.
Question 2: What are the short-circuit and overspeed capabilities of LX series generators? Why does LX-G not support strong short-circuit capability?
answer:
Overspeed: All models can withstand 120% rated speed for ≥ 2 minutes.
Short circuit: 50Hz=250%/2s; 60Hz=300%/2s (excluding LX-G).
LX-G adopts direct power supply from the main stator without auxiliary strong excitation winding, which cannot maintain high-power short-circuit current.
Question 3: What is the transient voltage index of the LX series? What is the significance for practical use?
answer:
Sudden increase of 100% rated current (power factor ≤ 0.4), maximum voltage drop ≤ 25%, and restore to within * * ± 3% * * of steady-state voltage within 2 seconds.
Meaning: Ensure minimal voltage drop and fast recovery when starting with a large load, protect equipment from tripping or restarting, and improve power supply stability.