ABB CP430T-ETH touch screen
State displayed in the hardware structureAfter loading the resource in the FieldController, the system or FieldController knows which mod ules and
field devices are configured. The components (modules, devices) themselves may not
have been installed yet, or the position of the installed component may not match the positions
(slots) or bus addresses configured. Such errors are signaled by colored state information.
System → Hardware structure
6.5.1 State in the tree view
In the tree view, state information is shown thus: active (black), faulty (red) and inactive (gray).
The color coding is applied to the object information (text) rather than the icon.
Color and state
transparent
(rear view) There is no module configured in this slot, nor is any module installed in the
station.
gray The module is configured and the correct module type installed.
red A module is configured in this slot, but not present in the FieldController.
yellow A module (e.g. type FI 830F) has been detected as installed in this slot, but
no configuration is available.
orange The module type configured in the hardware structure (e.g. FI 830F) does
not match the installed module type (e.g. 810F).

6.5.3 State of the basic unit
On insertion into the hardware structure the FieldController is displayed with its basic unit. The
FieldController basic unit indicates whether the unit is active, inactive or faulty. Where a fault is
indicated, this is generally due to the unit not being detected at all, i.e. not being installed or being
impossible to address via the system bus.
dark gray The basic unit is activated.
light gray The basic unit is not activated
red The basic unit cannot be addressed
6.5.4 Status of the FieldController modules
The detailed picture of the module shows more detailed information on the modules of the
FieldController, so that these can be identified more easily.
The status of modules in the FieldController is marked by a colored triangle.
No module found (red exclamation mark)
A module is configured in this slot, but not present in the FieldController.
Wrong module type (orange exclamation mark)
The module type configured in the hardware structure does not match the installed module type
Forced channels (green exclamation mark)
At least one of the module's channels has been forced. See Engineering Manual, System Configuration, Commissioning, Forcing inputs and outputs.
Config fault (red exclamation mark)
The Profibus-Master has detected a configuration fault. See Engineering Reference Manual,
Communications and Fieldbusses, Profibus, Profibus-DP States
Parameter fault (red exclamation mark)
The Profibus-Master has a detected a parameter fault. See Engineering Reference Manual,
Communications and Fieldbusses, Profibus, Profibus-DP States
Diagnostic value detected (blue exclamation mark)
A diagnostic value has been recorded for the slave or for a module of the slave. The diagnostic
value is shown in the list in the slave detail view, below the graphical representation. See Engineering Reference Manual, Communications and Fieldbusses, Profibus, Diagnostic Data.