K-WANG

+086-15305925923
Service expert in industrial control field!
NameDescriptionContent
Adequate Inventory, Timely Service
pursuit of excellence 
Ship control system
Equipment control system
Power monitoring system
Current position:
新闻动态
newS
   
Brand

SIEMENS SINAMICS G120 Control Unit CU240E

From: | Author:Wang | Time :2025-11-27 | 892 visit: | 🔊 Click to read aloud ❚❚ ▶ | Share:

SIEMENS SINAMICS G120 Control Unit CU240E

Detailed installation process explanation

1. Installation of core prerequisites

The control unit (CU240E) and power module need to work together and cannot operate separately; If installed incorrectly, it may cause the frequency converter to start unexpectedly, so the installation must be completed by certified personnel who have received training in the installation of such systems.

The default control and monitoring signal source for the control unit is the wiring terminal, which can be modified during debugging through parameters P0700 (command signal source) and P1000 (set value signal source).

2. Equipment structure and status indication

(1) Key Structure

Status indicator: includes a red SF (system fault) indicator light and a green RDY (ready) indicator light.

Core interfaces: analog input interface, power module interface, control terminal, bus termination switch, shielding layer card, option interface (supporting BOP basic operation panel and other options).

(2) Definition of Core Terminals in Wiring Diagram

Terminal Number Function Description Terminal Number Function Description

1 +10V 15 PTC-

2 OV 16 DI4

3 AIO 17 DI5

4 AI0- 18 NC

5 DIO 19 NO(DO0)

6 DI1 20-23 COM, NCC, NO, COM (DO1 related)

7 DI2 24 NO(DO2)

8 DI3 25 COMJ

9 U24V 26 AO1+

10 AI1+ 27 AO1-

11 AI1- 28-29 RS485 -A、UOV

12 AO0+ 30 RS485 -B

13 AO0- - -

14 PTC+ - -

3. Technical parameters of wiring terminals

Design type: Cage spring clamping design, compatible with cable specifications of 0.2~1.5 mm ² (24~14 AWG).

I/O interface configuration: 6 digital inputs (DI), 3 digital outputs (DO), 2 analog inputs (AI), 2 analog outputs (AO), and 1 PTC interface.

Cable requirements: The maximum length of the control cable should not exceed 10 meters (32.8 feet); Unshielded cables can work, but it is recommended to use shielded cables to meet the EMC (electromagnetic compatibility) requirements of CE standards.

4. Bus connection (USS protocol)

Connection method: RS485-UPS bus connection is made through terminals 29 (RS485-A) and 30 (RS485-B).

Transmission rate: The maximum baud rate is 115200 baud.

Terminal switch: The bus terminal switch is located below terminals 29 and 30 and needs to be set according to the bus topology requirements.

5. Installation and disassembly operations

Installation: The control unit is fixed on the power module by card mounting, and the installation and operation of all G120 control units and G120 power modules are completely consistent, without distinguishing models.

Disassembly: Press the release button on the top of the power module to remove the control unit from the power module.


Pre power on inspection (14 mandatory items)

Before powering on, the following checks need to be completed one by one to ensure that the system has no safety hazards and can be started normally:

Check the serial number, check the core requirements of the project

1. The environmental conditions meet the technical requirements of the frequency converter/motor (such as temperature, humidity, dust prevention, etc.)

2. Installation firmness: The frequency converter and motor are installed firmly without looseness

3. The installation and cooling installation methods are correct, and there is sufficient cooling air supply around the equipment

4. There are no safety issues with the readiness status of the motor and application equipment, and the motor can rotate freely (without jamming or obstruction)

The grounding and protection measures of the frequency converter are good, and there are no hidden dangers of poor grounding

6. Matching of power supply voltage: The input power supply voltage meets the rated input voltage requirements of the frequency converter

7 Fuse configuration: The fuse model for the input power supply is selected correctly and installed in place

8. The motor wiring and steering motor wiring are correct, and the steering direction meets expectations when starting

9. The wiring of the motor and power supply is good, and the tightening torque should be tightened according to the technical requirements

10 motor phase sequence: The motor phase sequence is not reversed (incorrect phase sequence may cause serious damage to connected equipment)

11. Cable routing: Separate the motor power cable from other control cables to avoid interference

12. The control signal wiring is correct and meets the corresponding technical requirements

13. There are no tools or foreign objects around the environmental cleaning equipment that may cause damage to the system operation

14. Unique power supply: The frequency converter is the only power supply device for the motor (to avoid multiple power supply conflicts)

Debugging the entire process (taking STARTER software as an example)

1. Debugging core prerequisites

The frequency converter (power module+control unit) cannot be directly applied after arrival and must be debugged before being put into use.

Debugging method: ① Download a set of valid parameters through BOP or STARTER; ② Gradually complete debugging through BOP or STARTER (this guide focuses on the STARTER software debugging method, refer to the control unit operation guide for other methods).

Hardware matching requirements: ① The rated current of the frequency converter shall not be less than the rated current of the motor; ② The output voltage level of the frequency converter matches that of the motor.

2. Debugging preparation work

(1) Equipment and software preparation

Software: Install STARTER debugging software on the PC, which can be obtained from the supply package of PC connection components or downloaded from the latest version through the link.

Hardware: Connect the frequency converter to the PC through the PC connection component (order number: 6SL3255-0AA00-2AA0).

3. Specific debugging steps

(1) Step 1: Create a STARTER project

Power on the frequency converter, start the STARTER debugging software, select "new project", and follow the project wizard to operate.

Enter an easily recognizable project name (such as "Basic Debugging"), and click "Continue" to add comments.

Set PG/PC interface:

Click on 'Change and test...'. If the 'PC COM Port (USS)' interface already exists in the 'PG/PC interface', click on 'properties' directly; If it does not exist, click "Select..." and install "PC COM Port (USS)" in "Install/Remove Interfaces". After successful installation, click "Properties".

Configure interface parameters: Select COM ports (COM1/COM2/COM3) and baud rate (default 38400), click the "Read" button to confirm the values; If the baud rate test area displays "???", the serial port needs to be replaced; Select "Automatic mode" under the "RS485" tab and click "OK" to return.

Insert frequency converter: Name the frequency converter (such as "SINAMICS_G120_CU240E", no spaces or special characters allowed), click "Continue" to enter the summary prompt dialog box, and then click "Complete" to end the project creation.

(2) Step 2: Connect to the frequency converter online

After the project was created, STARTER was in "Offline mode" and did not establish a connection with the inverter.

Click the online connection button to pop up the online/offline data comparison dialog box: the left side shows online frequency converter data, and the right side shows offline project data.

Click on 'Load HW configuration to PG' to upload the hardware configuration of the online frequency converter to the PC. Close the dialog box to complete the online connection, and switch the software status from 'Offline mode' to 'Online mode'.

(3) Step 3: Start debugging

After successful online connection, if it is the first time debugging, a fault message F00395 will pop up (indicating that the frequency converter has not been debugged). Select the message and click "Acknowledge" to confirm and start debugging.

Double click the inverter object to enter the debugging wizard, and configure parameters according to the following process:

Control structure configuration: Confirm basic parameters such as control mode (default V/f linear characteristics), driver dataset (DDS 0), command dataset (CDS 0), etc.

Frequency converter function selection: It is recommended to choose "Identification of all parameters including the saturation curve" (automatic recognition of parameters including saturation curve). This function will perform motor data recognition once after the drive is enabled, and the motor may rotate no more than 1/4 turn. When the subsequent drive is enabled, it will optimize the rotation of the motor.

Motor data calculation: It is recommended to select "Restore factory setting and calculate motor data only", or choose "Calculate motor data only" or "Exit motor commissioning".

Summary confirmation: The debugging wizard will display the configured driver data (control structure, set values/command source default values, motor data, etc.) at the end. You can click "Copy text to clipboard" to backup, and click "Continue" to proceed to the next step.

Motor parameter recognition startup:

Click on 'Control panel', then click on 'Assume control priority' (if connected via BOP link RS232, this button will change to 'Return').

Click "Enable" to activate the ON/OFF button, and then click the ON button to start motor parameter recognition. During the recognition process, if the relevant buttons are disabled, an alarm 541 "Motor Identification Active" will be displayed.

After recognition is complete, the alarm is cancelled and the button is restored to its active state. Click on "Give up control priority!" and pay attention to the warning message that pops up.

Parameter saving: Open the SINAMICS project, click the "Copy RAM to ROM" button, and save the debugging parameters to the EEPROM of the inverter to avoid parameter loss.

(4) Step 4: Application debugging and disconnection

After basic debugging is completed, application debugging can continue through the STARTER navigation dialog box, or specific functional modules (such as input/output, setpoint channels, closed-loop control, etc.) can be fine tuned directly.

After debugging, click the disconnect button and select the save method in the pop-up save dialog box: ① Save the inverter project to the PC; ② Upload parameter settings to PC; ③ Save the parameters from RAM to EEPROM, and disconnect the PC from the inverter after completion.

4. Factory reset operation

(1) Function Description

All frequency converter parameters can be restored to their factory settings through factory reset. During the reset process, the communication memory will be reinitialized, causing communication interruption between the PC and the frequency converter.

(2) Operation steps

Ensure that the frequency converter is online (if offline, click the "connect to target system" button).

Select the frequency converter that needs to be reset in the STARTER navigation area.

Click on the factory reset icon and follow the prompts to complete the reset operation.


Fault diagnosis system

1. Definition of faults and alarms

(1) Fault

Nature: The device is in a serious abnormal state, which can affect the safe operation of the system.

Handling mechanism: When a fault occurs, the frequency converter automatically stops through the OFF2 command, and the red SF (system fault) LED on the control unit lights up; The frequency converter can only be restarted after confirming the fault.

(2) Alarm

Nature: The equipment is in an extreme state (which may cause malfunctions) or a special temporary state (such as motor parameter identification), and does not affect the basic operation of the system.

Processing mechanism: No manual response is required, the alarm status will be automatically eliminated or continuously prompted as the working conditions change.

2. Common faults and their solutions

Fault code, fault cause, handling measures

F00001 overcurrent, motor power does not match frequency converter power. Check if the rated power of the frequency converter and motor are consistent to ensure matching

F00002 overvoltage, high power supply voltage or motor in power generation state. Check if the input power supply voltage is within the rated range and investigate the cause of the motor's power generation condition

F00003 undervoltage, power failure or low voltage. Check the stability of the power supply and troubleshoot power outages or voltage drops

F00004 frequency converter overheating, exceeding the upper temperature limit, check whether the motor load is overloaded, whether the carrier pulse frequency is set reasonably, whether the ambient temperature is too high, and install a cooling fan if necessary

F00005 frequency converter overload check whether the motor power matches, whether the load change cycle is reasonable, and optimize the load working conditions

F00041 motor parameter recognition failed. Check if the wiring from the motor to the frequency converter is correct and confirm if the motor nameplate data is accurately inputted

F00052 Power module hardware data read failure. Check if the connection between the control unit (CU) and the power module (PM) is secure and in good contact

F00062 MMC data is invalid. Copy MMC parameters again to ensure a complete and uninterrupted copying process

F00070 PLC setting value fault check parameter P2040 numerical setting to ensure that the setting value is correct and effective

F00071 USS setting value fault. Use STARTER software to check if the USS communication settings (such as baud rate, address, etc.) are correct

F00072 USS setting value fault check whether the communication status and parameter configuration of the USS main station are normal

F00090 Encoder Feedback Signal Loss Check if the encoder is securely installed and wired correctly, and re debug the encoder

After replacing the F0395 CU/PM with power on, copying the startup parameters, or confirming if the device replacement process is standardized due to EEPROM read errors, perform parameter copying or debugging again, and troubleshoot EEPROM faults

3. Common alarms and their meanings

Alarm code alarm meaning

The parameters and configuration settings of A0700 PROFIBUS master station are invalid, and the PROFIBUS configuration needs to be modified

A0702 PROFIBUS connection interrupted, check the connectors, cables, and PROFIBUS master station

A0703 cannot obtain the set value from the PROFIBUS master station (control word=0) or the set value is invalid. Check the output of the master station set value

At least one intermediate node of A0704 configuration is not working or has malfunctioned

A0705 cannot obtain actual value from frequency converter (no frequency converter fault)

A0706 r2041 No diagnostic information, there may be a PROFIBUS DP software malfunction

A0710 frequency converter detected a PROFIBUS communication fault, and the communication port on the control unit may have malfunctioned

A0711 PROFIBUS parameter is invalid, check P0918 address settings and parameter P2041

4. LED status indication diagnosis

The control unit displays the device status through two LED indicator lights, with the following specific meanings:

LED name, color, status, meaning

SF (system malfunction): The red lit device indicates a system malfunction related to software and hardware

SF (system fault) red off, no system fault

SF (system fault) flashing red (0.5Hz) fault not confirmed or fault ongoing

RDY (Ready) green light indicates that the frequency converter is ready to start running (does not mean it is currently running)

RDY (Ready) green goes out. The frequency converter is not ready (such as not powered on, faults not resolved, etc.)

RDY (Ready) green flashing (0.5Hz) device in standby or transition state


  • Siemens 6SL3244-0SA01-1AA0 - SINAMICS G120 Control Unit
  • DANFOSS 175Z2688 - COATEDE CONTROLUNIT VLT5000
  • SIEMENS 6FM1721-3AA20 - Positioning Module
  • REXORTH VTS0605 PVAR S21 - Drive Module
  • BECKHOFF 2915-0000 - Control Module
  • COOPER EATON CGLine 400 40071347901 - CEAG CG Controller
  • SIEMENS 3UF5031-3AN00-1 - SIMOCODE DP Basic Unit
  • SIGMATEK DNC305 05-011-305 - Drive Controller
  • Multivac MV1 10249768 - Control Module
  • SCHNEIDER ELECTRIC MES114 59646 & 59645 - Circuit Breaker Accessory
  • CAMILLE BAUER CAPAX 44-580-0012 - Transmitter
  • HENGSTLER VT360P LS1/TOK - Encoder
  • BURKERT 8792 - 24V DC IP65 / IP67 Positioner
  • SENSOPART V10-OB-A1-W6 - Vision Sensor
  • ALLEN-BRADLEY 1762-L40BXB SER.C REV.J - MicroLogix 1200 Controller
  • HITACHI CPU22-02HC 33025801-2 - CPU Module
  • HITACHI AGH-0 33034810-2 - Control Board
  • PHILIPS AIH110 VER 1.0 - Control Module
  • BAUMULLER DO8000 - Drive Controller
  • B&R PS477 3PS477.9 Rev.C0 - Power Supply
  • ABB ALFA LAVAL 200-CISB - Communication Interface 2 x SatBus
  • Moeller MI4-570-TA1 - HMI Operator Panel
  • ABB ACH550-01-06A9-4+B055 - Variable Frequency Drive
  • ABB TPU2 3HNE00313-1 REV 12 - Teach Pendant Unit
  • Schneider Electric BRS368H130ABA - Stepper Motor
  • Foxboro FCM100E P0972ZA - I/A Series Communication Module
  • Siemens 6ES7 450-1AP00-0AE0 6ES7450-1AP00-0AE0 - Simatic S7 Version:04 Counter Module
  • Schneider Electric ATV320U07N4W - Altivar Machine Drive
  • Priva TouchPoint Flush V06:02 5060002 - Control Panel
  • Lenze ESMD402L4TXA - 4kW SMD Inverter Drive
  • Lenze ESMD402L4TXA - 4kW SMD Inverter Drive
  • Schneider Electric PM210 PM210MG - Powerlogic Power Meter
  • ASCOM U982-DB/1C U982 - Power Supply / Communication Module
  • DYADIC SYSTEMS SCN5-010-050-S03-NA - Servo Cylinder
  • Reliance Electric GMI-S04 - AC/AC CONVERTER 380/400V 50/60Hz 3.9/5.2A
  • Pro-Face GLC150-BG41-XY32KF-24V 3080060 PFXGLC150BDBP - Touch Screen HMI
  • ROFIN RSL TERMINAL V2 0185.01/03 - TERMINAL
  • HONEYWELL R7241E1077 - Burner Control / Amplifier
  • SEW MM22C-503-00 8241201 - 2.2kW Movimot Drive
  • Brand Digital III 50mL - Burette
  • Danfoss 195N0039 VLT2811PS2B20STR1DBF00A00C0 - 2.4kVA VLT Drive
  • SONY LG10-2 EK1 - Digital Gauge Indicator
  • EMERSON SKD3400750 - 7.5kW AC Drive
  • SIEMENS 6AV6 542-0AG10-0AX0 - MULTIPANEL HMI
  • TELEMECANIQUE ATV21HU55N4 - ALTIVAR21 5.5KW Variable Speed Drive
  • MITSUBISHI A985GOT-TBA-EU - GOT900 Touch Screen HMI
  • SCHNEIDER LXM32AD30N4 - Lexium 32 Servo Drive
  • SICK PSR01-1501 M20Z-02550A122 - Safety Laser Scanner
  • GECMA CHALLENGER 15-2-FMO - LITE TOUCH Monitor
  • Uniop EK02 6ZA982 - HMI Operator Panel
  • TELEMECANIQUE ATV18U54M2 - SQUARE D ALTIVAR 18 3kW Drive
  • Schneider Electric ATV312HU75S6 - 7.5kW Altivar 312 Drive
  • Siemens 6GK7243-5DX30-0XE0 6GK7 243-5DX30-0XE0 - Communications Processor
  • Schneider Electric LV432455 VIGI630 - 3POLE Earth Leakage Module
  • Rexroth PSI 6100.750 L1 R911170694-107 - frequency inverter / inverter
  • SWEDISH MICROWAVE AB Ku-Band BDC 138010-45-D0 - Block Downconverter
  • METTLER TOLEDO IND429 IND429-BB30 - Weighing Terminal
  • Siemens 6SL3210-5HE10-4UF0 - Sinamics V90 Servo Drive
  • B&R X20CP0482 Rev.D0 - X20 CPU Module
  • Mitsubishi FR-E720S-110SC-EC FRE720S110SCEC - 31A~11A Drive With Filter
  • ABB ACH580-01-026A-4 - Variable Frequency Drive
  • Siemens 6SL3210-1KE13-2AP1 - SINAMIC G120CDP 1.1kw Drive
  • Schneider Electric TM250D 4P3D LV431440 - Compact NSX250 Circuit Breaker
  • RELIANCE ELECTRIC GD.722.81.00-A 802288-74C - MAXITRON Servo Control Card
  • Uniop EK02 6ZA982 - HMI Operator Panel
  • Siemens 6SE9113-7JA13 - MICRO MASTER Junior 1.5kW Inverter
  • Mitsubishi FR-E720S-110SC-EC FRE720S110SCEC - 31A~11A Drive with Filter
  • Johnson Controls FEC2621 MS-FEC2621-0 - Field Equipment Controller
  • BENDER IR475LYT-429 - A-ISOMETER Insulation Monitor
  • Berger lahr D550 RS15 22.550-00-30b - Stepper Drive
  • Rexroth PSI 6100.750 L1 R911170694-107 - Frequency Inverter / INVERTER
  • KOYO 205 D2-06B-1 D2-240 H2-ECOM D2-08ND3 F2-08TRS - DIRECT LOGIC PLC WITH MODULE
  • TELEMECANIQUE ATV18U54M2 ATV18U54M - SQUARE D ALTIVAR 18 3kW Drive
  • Lenze 471-E1.D - Board / Controller Speed
  • Mitsubishi FR-A740-00038-EC - Frequency Inverter
  • Johnson Controls IOM3723 MS-IOM3723-0 - Input/Output Module
  • CURTIS 1238-5602 - AC Motor Controller
  • FOXBORO P0912XX REV.A - 220VAC Power Supply
  • Siemens 6SE9113-7JA13 - MICRO MASTER Junior 1.5kW Inverter
  • Mitsubishi FR-A740-00038-EC - Frequency Inverter
  • KOYO 205 D2-06B-1 D2-240 H2-ECOM D2-08ND3 F2-08TRS - DIRECT LOGIC PLC WITH MODULE
  • AUTZ M406D-00101 - Servo Motor
  • Lauer PCS095 PG095.508.BB - Operator Panel
  • ABB SCOP45SB/DX232 - SattCon OP45 SB Operator Panel
  • SEW Eurodrive MCH42A0030-5A3-4-00 MDX60A0030-5A3-4-00 - 4.8kVA Movidrive Inverter
  • BENDER IR475LYT-429 - A-ISOMETER Insulation Monitor
  • Johnson Controls FEC2621 MS-FEC2621-0 - Field Equipment Controller
  • Johnson Controls IOM3723 MS-IOM3723-0 - Input/Output Module
  • Berger lahr D550 RS15 22550-00-30b - Stepper Drive
  • SIEMENS 6FX1120-4BD03 6FX11204BD03 5702049304.00 E-Stand: A - Sinumerik Module
  • Allen-Bradley 1771-NIV B - HIGH RESOLUTION ISOLATED ANALOG SERIES Module
  • HONEYWELL XFC2D06001 - Flow Computer / Controller
  • Contraves Varidyn Compact ADB 380.90M - DC Drive 380v - 400v 90A 50kVA
  • Red Lion Control GEM52000 - Control Module
  • Siemens 6ES5 955-3NC13 - modular power supply TYPE:DIN41752
  • Danfoss ICV50 G20Mn50T / 027H5200 - Valve zaw
  • Eberle PLS508 P-814 / 2X EA-88 / A-812 / MT-81 / S-11 - PLC with Modules
  • Siemens 6ES7 314-6CF01-0AB0 6ES7314-6CF01-0AB0 - SIMATIC CPU314C-2 DP
  • EBERLE EM-525-87 EM52487 - ICE DETECTOR BASE UNIT
  • Telemecanique / Schneider TSXRKZ02 - TSX Micro automation plus 7module
  • B&R 5DLSDL.1001-00 - Display Link Receiver
  • Siemens 6FX1120-4BD03 6FX11204BD03 5702049304.00 E-Stand: A - Sinumerik Module
  • ALLEN-BRADLEY 1771-NIV A - HIGH RESOLUTION ISOLATED ANALOG SERIES Module
  • ALLEN-BRADLEY 1771-NIV B - HIGH RESOLUTION ISOLATED ANALOG SERIES Module
  • Contraves Varidyn Compact ADB 380.90M - DC Drive 380V - 400V 90A 50kVA
  • Contraves Varidyn Compact ADB 380.90M - DC Drive 380V - 400V 90A 50kVA
  • Ropex RES-202 - Resistron Temperature Controller
  • HONEYWELL XFC2D06001 - Flow Computer / Controller
  • Telemechanics ATV452U40 - DIMMER ALTIVAR5 SERIES 452 4kW 5HP Frequency Inverter
  • VEGA VEGAPLUS61 PS61.XXAGPHAMAX - Radar Level Sensor
  • BRANSON ULTRASONIC TRANSDUCER - Ultrasonic Transducer
  • Danfoss ICV50 G20Mn50T / 027H5200 - Valve Valvola Zaw
  • Schneider Electric 2001549/1 GALAXY PW 5102851200 NT07 - panler card
  • REXROTH VT3006-36 A - Proportional Valve Amplifier
  • Allen-Bradley 1746-OBP16 SERIES:C - SLC 500 OUTPUT MODULE
  • SCHNEIDER LXM32MD12N4 - Lexium 32 Servo Drive
  • Schneider Electric ATV630U22N4 - 2.2KW Altivar Process Drive
  • Allen-Bradley 1746-OBP16 SERIES:C - SLC 500 OUTPUT MODULE
  • Vanderlande 0E2550-00002... - Bagtrax Integrated Power Module 400V 32A
  • B&R X20CP0410 Rev.D0 - X20 CPU Module
  • VANDERLANDE 0E2550-00002 02EDD2B0100 - BAGTRAX Integrated Power Module 400V 32A
  • Rexroth R061205010 - Linear Bushing / Bearing
  • INDRAMAT TVM1.2-50-220/300-W0-220/380 - Power Supply Module
  • Vanderlande 0E2550-00002... - Bagtrax Integrated Power Module 400V 32A
  • HOMAG KEB 07F5S1A-YA00 09E5T60-1001 - Combivert Inverter WITH KEYPAID AND FILTER
  • Siemens 3RW3047-1BB14 - Soft Starter
  • Sumitomo AF-500 AF502-A40 - 0.4kW Transistor Inverter
  • Sumitomo AF-500 AF502-A40 - 0.4kW Transistor Inverter