K-WANG

+086-15305925923
Service expert in industrial control field!
NameDescriptionContent
Adequate Inventory, Timely Service
pursuit of excellence 
Ship control system
Equipment control system
Power monitoring system
Current position:
新闻动态
newS
   
Brand

GE IC697MDL651 5 VDC (TTL) Input (32 Points)

From: | Author:Wang | Time :2024-12-19 | 211 visit: | 🔊 Click to read aloud ❚❚ | Share:

GE IC697MDL651 5 VDC (TTL) Input (32 Points)

Fault and No Fault contacts can be used to detect fault or lack of fault conditions on a
discrete (%I or %Q) or analog (%AI or %AQ) reference, or they can be programmed with
the Series 90-70’s built-in fault-locating references (see below). Unless they are used
ONLY with fault-locating references, fault memory for their use must be set up using
the CPU Configuration functions of the Logicmaster 90-70 software.
A Fault contact will detect a fault in a discrete or analog input or output, or a hardware
component of the system. The contact passes power flow if the reference has a fault.
Example:%AI0034 %M00053
When used with a %I, %Q, %AI, or %AQ reference, a fault associated with the

–[F AULT]– contact must be cleared to remove it from the fault table and stop the con tact passing power flow.
Clearing such a fault with a Hand–held Monitor does not remove it

from the fault table or stop the contact passing power flow.
No Fault Contacts will also detect faults in discrete or analog inputs and outputs. A No
Fault Contact passes power flow if its associated reference does not have a circuit fault.
Example:
%I00167 %Q00168
Fault Locating References
Both Fault and No Fault contacts can be programmed with fault–locating references to

identify faults associated with system hardware. These fault references are for informa tional purposes only.
The PLC does not halt execution if one of these reference faults

occurs. For a Genius device, the format of the fault–locating reference is M_rsbmm,
where r is the rack number 0 to 7, and s is the slot number of the Bus Controller; b is the
bus number, and mm is the Device Number (serial bus address) of the affected Genius
device (00 to 31). For example, M_46128 represents rack 4, slot 6, bus 1, module 28. For
more information about fault–locating references, please refer to the Logicmaster 90–70
Software User’s Manual.


The I/O Fault Table can contain up to 32 faults. Additional faults cause the table to over flow, and faults are lost.
The system reference IO_FULL (%S00010) is set to indicate that

the fault table is full.
As faults occur, the first 16 are logged into the table and remain there until the table is
cleared again; none of these 16 faults will be dropped if the table overflows. For faults 17

through 32, the Fault Table operates as a First–In–F irst–Out stack. When fault 33 oc curs, fault 17 is dropped from the table.
Clearing the Fault Table removes all the fault

listings.
Fault 1
Fault 16
Fault 17
Fault 33
Faults overflow here
New faults are added here
Clearing Faults
You must clear the I/O Fault Table from Logicmaster 90 for the fault to be cleared in the
PLC CPU and for the associated fault contact to be cleared. Clearing faults with a Hand–
held Monitor alone does not remove them from the Fault Table, or cause any associated
–[F AULT]– contacts to stop passing power flow.

Clearing the Fault Table causes the Bus Controller to send a Clear All Circuit Faults back ground message to all blocks on the bus.
Faults can be cleared from the Fault Table ei ther from the programmer screen or by the application program.

Clearing the fault table removes the faults it contains; it does not clear fault conditions in
the system. If the condition that caused a fault still exists and is detected, the fault will
be reported again.
Removing I/O Force Messages from the I/O Fault Table

When a point is forced on a Genius block with a Hand–held Monitor, a fault is regis tered in the Series 90 I/O Fault Table.
Subsequent forces on the same block do not gen erate additional messages. Only when all forces are removed from the block does the

Bus Controller log an Unforce message in the I/O Fault Table.
Loss of Device Faults Caused by High Bus Error Rate
If the bus is experiencing a high error rate (possibly due to electrical interference or
damaged cable), Loss of Device faults may be logged into the Fault Table. Loss of Device
faults that are logged in conjunction with I/O Bus Faults can be usually be attributed to
the poor quality of the bus installation. The condition causing the bus errors should be
corrected as soon as possible.
  • Woodward 9905-373 - Digital Synchronizer And Load Controller
  • WOODWARD MAGNETIC PICKUPS - Sensor
  • WOODWARD GCP-30 - Steuertafel for Industrial Regulator Genset Control Package
  • WOODWARD GOVERNOR 9907-1183 REV A - 505 ENHANCED TURBINE CONTROL
  • WOODWARD 9907-173 REV B - Module Load Sharing 120 Volt
  • WOODWARD 9907-014 - 2301A controller
  • Woodward 9905-029 - SPM-A Synchronizer Module Rev C
  • WOODWARD 8440-1799 EASYGEN-350 REV B - Genset Controller
  • WOODWARD 5466-258 REV M - SIMPLEX DISCRETE I/O MODULE
  • Woodward 8440-1884 C - Controller Easygen 2500-5
  • Woodward 8441-1153 - Monitoring Unit 250VAC
  • WOODWARD 8406-120 REV G - EGCP-2 DIGITAL CONTROL
  • Woodward 8273-584 - Atlas-ii Digital Control
  • Woodward 8272-582 - APM Motor Control 8272582
  • Woodward 9905-377 Rev. A - 2301A Load Sharing and Speed Control
  • WOODWARD 8272-517 - Pm Motor Control
  • WOODWARD 9905-797 REV.B - DIGITAL SYNCHRONIZER AND LOAD CONTROL DSLC-D
  • WOODWARD 8272-582 - APM MOTOR CONTROL
  • Woodward Seg FP2-8-24 - Emergency Power Telecommunications Module NP2
  • WOODWARD 2001-12E2U1B1S1A - Fuel Shut Off Valve Stop Solenoid Valve 2000-4505
  • Woodward 8440-1884 K - Genset Controller Easygen-2500-5
  • Woodward 9905-760 - Linknet Termination Module
  • Woodward 8404-009 - Proact Digital Plus Front Panel Rev. H
  • Woodward 8271-651 - Digital Speed Reference
  • Woodward 3077-474C - 8605895 5501-031 D Circuit Module
  • WOODWARD 5466-257 REV.-C - NETCON 5000 MODEL REMOTE TRANSCEIVER I/O MODULE
  • Woodward 8273-101 Rev: A - 2301D Digital Load Sharing and Speed Control
  • WOODWARD 8272-799 - 2301A SPEED CONTROL WITH REMOTE REFERENCE REV:C
  • Woodward 8272-517 - PM Motor Control
  • Woodward 8290-048 8290048 Rev. F - Generator Load Sensor
  • woodward 8273-1012 rev c - 2301e Load Sharing and Speed Control
  • WOODWARD 9905-797 - DIGITAL SYNCHRONIZER AND LOAD CONTROL FOR 3 PHASE GENERATORS
  • WOODWARD 8280-3014 - 723 PLUS DIGITAL CONTROL REV NEW
  • WOODWARD 8440-1884 REV G - GENSET CONTROLLER EASYGEN-2500-5/P1
  • Woodward 8272-683 K - Digital Reference
  • WOODWARD 9907-014 - SPEED CONTROL 2301A REV H
  • Woodward Type UG-8 P/N 037260 - Governor R.P.M 1075-1650 Motor KM58-20
  • WOODWARD 9905-970 - LINKNET 6 CHANNEL 100 OHM RTD Rev:J
  • Woodward 9907-1183 Rev C - Steam Turbine Digital SCREEN 505E Turbine Control
  • Woodward 8440-1614 - GCP-30 Genset Control Package, Rev: F, Type 1, E231544
  • Woodward DC11006-304-024 - ACTUOTOR DYNA ACTUATOR - BARBER-COLMAN
  • Woodward 9905-971 - LINKNET 6 CHANNEL 100 OHM RTD Rev:K
  • Woodward DYNK-10249 - Actuator Controller Kit - DYNA 2000
  • Woodward LR21035 - MFR1 MULTI FUNCTION RELAY REV F
  • Woodward 8440-1831 - EASYGEN 3200-5 P/N: REV. G Gererator Controller
  • Woodward 8272-516 - PM MOTOR CONTROL REV J
  • Woodward 8440-2080 - EASYGEN 2000 genset controller EASYGEN-2300-5/P1
  • Woodward 505DE - Digital Control System
  • Woodward 701 - Digital Speed Control 18-40 VDC 4-20 MA
  • Woodward 8440-1799 - EASYGEN-350 REV B
  • Woodward 8272-582 - Apm Motor Control 100-220v AC/DC
  • Woodward 5501-031 D - 3077-474C 8605895 Circuit Module
  • Woodward XD1-T - XD1T55SAT TRANSFORMER DIFFERENTIAL PROTECTION RELAY
  • Woodward 8272-517 - PM Motor Control 220vac
  • Woodward 8934-658 - Repair Kit UG8D Governor
  • Woodward 5437 18 - module netcon derivative analog rev.A
  • Woodward 8272-171 A - Pm Motor Control
  • Woodward MRN3-1/2 - SEG mains uncoupling relay MRN314D mains decoupling relay
  • Woodward 9905-373 - Digital Synchronizer and Load Control 18-40 VDC Rev P
  • Woodward 5431-640 C - Dual Dynamics 1000 Series Speed Control Module
  • Woodward 5501-031 D - 3077-474C 8605895 Circuit Module
  • Woodward 9907-247 - 828 DIGITAL CONTROL
  • Woodward 8440-1855-G - EASYGEN-2200-5 /P1 12/24VDC GENSET CONTROLLER
  • Woodward NC3-2-8 (NO) - GENERATOR CONTROLLER
  • Woodward 8271-467 K - 2301 LOAD SHARING AND SPEED CONTROL PART NO:
  • Woodward 8440-2177 A - SPM-D2-10 Digital Synchronising Controller
  • Woodward LXMG1614E-14-11 - CCFL and UV Lamps Inverter Module
  • Woodward 8270-990 - signal converter
  • Woodward 9905-068 - LOW VOLTAGE 2301A LOAD SHARING & SPEED CONTOL P/N:
  • Woodward 8901-051 - BOOSTER SERVOMOTOR, SINGLE CYLINDER, 2:1
  • Woodward 8444-1024 D - MWS4-55M CONTROL MODULE UNIT
  • Woodward 5448-914 - GCP-20 Genset Control GCP-20 REV D P/n:
  • Danfoss BHA-1 018-1942 - Hydraulic Actuator
  • Woodward 9905-001 L - SPM-A SYNCHRONIZER
  • Woodward 5464-850 - Module
  • Woodward 5501-371 - Micronet Simplex Mpu Aio Rev C
  • Woodward 8272-132 B - POWER SENSOR
  • Woodward 9907-028 - SPM-A Synchronizer
  • Woodward SA-3678-AM-2 - Overspeed Electric Governor, Model ESSE2-AM
  • Woodward E8250-502 - GOVERNOR ACTUATOR
  • Woodward 8440-1884 J - Controller EASYGEN-2500-5
  • Woodward 5441-693 - DIGITAL I/O MODULE -MISSING PART
  • Woodward SA-4450 - Speed Controller APECS 3100 For Magnetic Pickup
  • Woodward 9903-466 - 701 DIGITAL SPEED CONTROL REV G
  • Woodward 1765-843 - Governor Speed Adjusting Motor P/N Type: SMM40 220V AC 50/60Hz
  • Woodward 9905-760 - Linknet Termination Module
  • Woodward 9907-247 - 828 DIGITAL CONTROL UNIT REV K
  • Woodward 5484-721 - motor
  • Woodward 8440-1734 - MFR-2 Rev.A Multi Function Relay MFR-2
  • Woodward CSC3SUWA - Controller
  • Woodward 8440-1667 - REV B SPM-D1010B/XN
  • Woodward 8406-120 - egcp-2 digital control
  • Woodward DPG-2201-002 - DIGITAL CONTROLLER REV D
  • Woodward 8272-516 - Pm Engine Control Rev J
  • Woodward 8440-1831 - EASYGEN 3200-5 P/N: REV. K - WITHOUT ACCESSORIES
  • Woodward 8273-101 - LOAD SHARING & SPEED CONTROL
  • Woodward 8440-1855-G - EASYGEN-2200-5 /P1 12/24VDC GENSET CONTROLLER
  • Woodward 9907-247 - 828 DIGITAL CONTROL UNIT REV K
  • Woodward LR21035 - MFR1 MULTI FUNCTION RELAY REV J
  • Woodward 8404-009 - PROACT DIGITAL PLUS FRONT PANEL REV J
  • Woodward 9905-204 - Rev N SPM-A synchronizer
  • Woodward 8521-367 - UG-8 P/N r R.P.M 750-1280 Governor / UG8
  • Woodward 9907-175 - Load Sharing Module Rev. B
  • Woodward 5464-645 - DRIVER MODULE REV A 2C ACT DRIVE
  • Woodward 8404-009 - PROACT DIGITAL PLUS FRONT PANEL REV J
  • Woodward 9907-175 - Load Sharing Module Rev. B
  • Woodward 8406-102 - Rev A EGCP-2 Digital Control Engine Generator 8406102
  • Woodward EASYGEN-2500-5 - Controller Genset
  • Woodward 8440-2082 - Controller
  • Woodward 8272-516 - PM MOTOR CONTROL REV J
  • Woodward 9905-373 - Digital Synchronizer and Load Control 18-40 VDC Rev P
  • Woodward 5501-429 - Actuator Controller 25mA 2 Channel , (UPP)
  • Woodward 8440-1869 - SPM-D10 Synchronizing System Control-SPM-D10B/PSY4-F-D
  • Woodward 9907-175 - Load Sharing Module Rev. A
  • Woodward 8200-224 - Servo Position Controller
  • Woodward 9906-619 - 723 PLUS DIGITAL CONTROL ( 8280-604 )
  • Woodward 8440-1519 - EASYGEN PART NO: REV: 4
  • Woodward 5501-371 - REV C MODULE- MICRONET SIMPLEX MPU & AIO FTM
  • Woodward EASYGEN-3200-5/P1 - Generator Controller Module Rev F
  • Woodward 8440-1884K - GENERATOR CONTROLLER EASYGEN-2500-5 REV,K
  • Woodward 5466-353 - REV C NETCON MAIN CHASSIS TRANSCEIVER
  • Woodward 9905-001 - SPM-A SYNCHRONIZER REV.L
  • Woodward 9907-838 - Speed control panel 9907-838 9907838
  • Woodward 9907-164 - 505 Digital Governor Turbine Control
  • Woodward 8273-465 - ATLAS W/O PC104 MODULE
  • Woodward 8200-1504 - Peak200 Steam Turbine Control Front Panel Mount HVAC Rev:E
  • Woodward 8272-582 - Apm Motor Control 100-220v AC/DC
  • Woodward 8440-1884 C - Controller Easygen 2500-5