K-WANG
GE MLJ synchronous inspection relay
Product Overview
Core functions
MLJ is a digital synchronous inspection relay mainly used to detect the synchronization conditions of two electrical systems (such as the generator and the power grid, and the two sections of the power grid). By measuring the voltage difference (Δ V), frequency slip (Δ f), and phase angle difference (Δθ) between the bus voltage (VB) and the line voltage (VL), it determines whether the circuit breaker closing conditions are met and outputs a closing permission signal.
Typical application scenarios
Generator and system grid connection
Reconnect the two regions of the system
Manual closing or automatic reclosing of circuit breakers
Verify synchronization conditions to avoid equipment damage caused by asynchronous closing
Core functions and working principles
1. Synchronous inspection unit
Measurement parameters:
Voltage difference (Δ V): The absolute difference in voltage between the bus and the line, ranging from 2-90V (default 15V).
Phase angle difference (Δ θ): The phase difference between two voltages, ranging from 2-60 ° (default 10 °).
Frequency slip (Δ f): The frequency difference between two voltages, ranging from 10-500MHz (default 20mHz).
Working mode:
Continuous mode: Continuous monitoring of synchronization conditions, with a delay of 0.1-99.0s (default of 0.1s) before allowing the output to close.
Manual mode: Monitoring is triggered by external signals, and after a delay of 0.1-99.0s (default 10.0s), the output allows for closing.
Allowable conditions for closing: Δ V, Δ θ, and Δ f are all less than the set values and continuously meet the set delay.
2. Undervoltage unit
Independently monitor the voltage status (live/dead) of lines and busbars, supporting three combination modes:
DLDB (Loss of Line - Loss of Power Bus)
DLLB (Lost Line - Live Bus)
LLDB (Live Line - Dead Bus)
Voltage thresholds can be set: line/bus live threshold (VL ↑/VB ↑, 40-245V), and power-off threshold (VL ↓/VB ↓, 10-180V).
3. Input/output unit
Digital input: 3-channel DC input, including circuit breaker status (allowing synchronous check when open), manual mode trigger, and enable signal.
Output contacts: 5-way relay contacts, including 2-channel closing permission (default normally open), 1-channel alarm (default normally closed), and 2-channel configurable auxiliary contacts (supporting signal outputs such as synchronization, undervoltage, and power loss).
4. Self check and Communication
Continuously monitor memory (ROM/RAM/EEPROM), analog circuits, etc., output alarms and display error codes when faults occur (e.g. 8.0 indicates ROM failure).
Supports RS-485 communication (optional fiber optic interface), baud rate 0.3-38.4kbaud (default 9.6kbaud), and supports Modbus protocol.
Technical specifications
Electrical parameters
Rated voltage: 63-220Vac (continuous withstand 440Vac).
Auxiliary power supply: 24-48Vdc, 48-125VDC, 110-250Vdc (± 20% fluctuation).
Measurement accuracy: Voltage ± 2% or 0.5V; Angle ± 1 ° (at 20-220Vac); Frequency slip ± 5mHz.
Contact capacity: Closing allows contact 4000VA (maximum 440Vac/300Vdc), auxiliary contact 1760VA.
Environmental and Physical Characteristics
Working temperature: -25 ° C to+55 ° C, storage temperature: -40 ° C to+70 ° C.
Humidity: ≤ 95% (no condensation).
Shell: Made of steel plate material, supporting panel installation or MID system integration, weighing approximately 3kg.
Operation interface and navigation
1. Front end devices
Button: Three vertically arranged buttons, from top to bottom, are ENTER (confirm/enter),+(add/next), and - (decrease/previous).
Display: A 3-digit 7-segment LED display screen used to show parameter values, status codes, and settings.
Indicator lights: 3 LED indicator lights, namely:
READY (green): The relay is ready and the protection function is enabled.
52 (red): The conditions for closing are met.
27 (red): The undervoltage condition is met.
2. Switching between working modes
Reading mode: default power on mode, displaying real-time data and status. Press ENTER to cycle through the various functional items (F0-F12).
Setting mode: In read mode, press ENTER and - simultaneously to enter and modify parameters. After setting up, press+and - simultaneously to return to read mode; If there is no operation for 2 minutes, it will automatically return.
Calibration mode: In reading mode, press ENTER and+simultaneously to enter and display the average values of line voltage and bus voltage for calibration.
Read mode function (F0-F12)
The main functions of cycling through the ENTER key include:
Functional code description
The F0 relay status displays a two digit error code (such as 0.0 indicating normal, 8.0 indicating ROM fault), with the decimal point constantly lit to distinguish the status from the numerical value.
Real time display of RMS voltage value in V for F1-F2 line voltage (VL)/bus voltage (VB).
F3 voltage difference (Δ V) displays the absolute difference between VL and VB, measured in V.
F4 phase angle difference (Δ θ) displays the phase difference between two voltages (0-180 °), and overflow (three horizontal lines) is displayed when the voltage is less than 9V.
F5 frequency slip (Δ f) displays the frequency difference in mHz, and overflow is displayed when the voltage is less than 9V.
Record and store the VL, VB, Δ V, Δ θ, and Δ f values when the last closing condition is met for F6-F10.
The F11 test function display screen is fully lit and flashing, and the LED lights up simultaneously to verify the hardware's normal operation; When the digital input is activated, the corresponding LED flashes.
The F12 line/bus status is indicated by the upper and lower segments of the display screen: the upper segment is lit up to indicate "live", the lower segment is lit up to indicate "power-off", and the middle segment is lit up to indicate that the voltage is between the threshold values.
Set mode parameter configuration
After entering the setting mode, switch the setting items with the+/- keys, press ENTER to enter the modification, and press ENTER again to confirm after adjustment. The main settings are as follows:
1. Basic configuration (0-1, 6-1, 6-2)
0-1 frequency: Choose 50Hz or 60Hz (default 50Hz).
6-1 Communication Address: Set Modbus address (1-255, default 1).
6-2 baud rate: Select the communication rate (0.3-38.4kbaud, default 9.6kbaud).
2. Synchronize check parameters (1-1 to 2-2)
1-1 voltage difference (Δ V): 2-90V (step size 0.5V, default 15V).
1-2 phase angle difference (Δ θ): 2-60 ° (step size 1 °, default 10 °).
1-3 frequency slip (Δ f): 10-500MHz (step size 10mHz, default 20mHz).
1-4 continuous mode delay: 0.1-99.0s (step size 0.1s, default 0.1s).