K-WANG



Overall positioning of the product
The MTL2000 series is a classic intrinsically safe (IS) isolated safety interface device used by MTL to connect Zone 0, IIC, T4/T6 hazardous area instruments and safety area control systems, replacing traditional Zener safety barriers. Its core advantages include:
Three party full isolation (input/output/power supply 250V)
No need for high integrity safety grounding
Built in triple protection for wire breakage, ground fault, and power failure
Supports 240V/120V AC or 24V DC power supply
35mm standard rail installation, compatible with MTL3000 series
Common Specification
Key indicators of parameter items
Isolation withstand voltage 1500V rms (safe zone) ↔ Dangerous Zone
Power supply version 240V AC/120V AC/24V DC
Working temperature -20~+60 ℃ (spacing ≥ 5mm); -20~+55 ℃ (close packed)
Installation method: 35mm guide rail/flat installation
Terminal maximum 4mm ² wire with identification position
Installation in a protected safety zone, compatible with an enclosure that can achieve IP65 rating
Certification of global intrinsic safety: Zone 0, IIC, T4/T6
Core models and functions
1) Switch/Relay Class (MTL22xx)
MTL2210B (1-channel switch relay)
Dangerous Zone 1 Switch Control Safe Zone 2 500VA Load
Support self-locking mode (motor start stop)
Response: 50ms; Contact: 2-pole conversion
Disconnection/Power Loss → Relay Power Loss (Safe State)
MTL2211 (2-channel switch relay)
Two independent inputs that do not interfere with each other
Each drive is 500VA, with dual contacts in parallel
Response: 50ms; LED status indicator
MTL2213 (3-channel switch/proximity sensor)
Compatible with NAMUR standard proximity sensors
Support phase reversal (alarm logic reversal)
100VA contact capacity per channel
MTL2215 (Safe Zone → Hazardous Zone Intrinsic Safety Output)
Safe zone switch signal → Control the intrinsic safety circuit of the hazardous zone
The contact is non energy storage type and can be directly connected to Zone 0
2) Analog class (MTL24xx)
MTL2441B (4-20mA relay power supply)
Power supply for 2/3 line transmitters in hazardous areas
Isolate relay 4-20mA signal to safe area
Accuracy:<20 μ A; Temperature drift:<1 μ A/℃
Maximum circuit resistance: 50 Ω Related calculations
MTL2442B (4-20mA isolated drive)
Safety zone 4-20mA → Isolation drive dangerous zone actuator
Maximum load: 800 Ω
Accuracy:<20 μ A; Response: 200ms stable

Protection mechanism
Wire breakage protection: Input line disconnected → Relay power loss/alarm
Ground fault protection: Ground resistance<1k Ω → safe action
Power failure protection: power failure → output reset to safe state
Intrinsic safety current and voltage limiting: ensuring that ignition energy is not generated in hazardous areas
Maximum cable parameters (key)
Model: Maximum capacitance Ca, maximum inductance La
MTL2210B 7μF 47mH
MTL2211 5.5μF 75mH
MTL2213 3μF 165mH
MTL2441B 0.17μF 5.1mH
MTL2442B 0.13μF 4.2mH
Key issue
Question 1: What are the core advantages of MTL2000 series compared to traditional Zener safety barriers?
Answer: The core advantage is the 250V electrical full isolation of input/output/power supply, which does not require high integrity safety grounding and significantly reduces construction costs; Simultaneously integrating triple protection of disconnection, ground fault, and power failure, the system is safer and the wiring is simpler.
Question 2: MTL2213 supports both switches and proximity sensors. How is it compatible with the NAMUR standard?
Answer: MTL2213 provides 7.7-9.0V and 1k Ω internal resistance for the sensor, according to the NAMUR DIN 19234 threshold judgment:
Current>2.1mA=sensor conducting
Current<1.2mA=sensor disconnected
Support phase reversal and flexible setting of alarm logic.
Question 3: How to use MTL2441B and MTL2442B together in analog circuits?
answer:
MTL2441B: Responsible for supplying power to hazardous area transmitters and isolating and relaying signals to safe areas;
MTL2442B: Responsible for isolating the 4-20mA signal in the safety zone and driving the actuator in the danger zone;
The combination of the two can achieve bidirectional isolation and transmission of signals across hazardous areas, while maintaining intrinsic safety and explosion-proof throughout the entire process.

KONG JIANG
Add: Jimei North Road, Jimei District, Xiamen, Fujian, China
Tell:+86-15305925923