+086-15305925923

K-WANG

Service expert in industrial control field!
NameDescriptionContent
Adequate Inventory, Timely Service
pursuit of excellence 
Ship control system
Equipment control system
Power monitoring system
Current position:
新闻动态
newS
   
Brand

Alstom MV7306P21 frequency converte

From: | Author:Wang | Time :2025-05-16 | 332 visit: | Share:

Alstom MV7306P21 frequency converte

Technical specifications

(1) Electrical parameters

Power range: Supports 24-60Vdc, 48-150Vdc, 130-250Vdc or 100-250Vac, 50/60Hz. The fluctuation range of power supply voltage is ± 20% in DC and -20% to+10% in AC, with ripple not exceeding 12%. The power outage withstand time is 50ms

Load capacity: Different load ports (such as P125, P126, P127) can withstand different powers, generally up to<3W dc or<8VA ac, and the maximum load can reach<5W dc or<12VA ac (depending on the port).

(2) Protection setting range

Phase overcurrent protection (taking P126 as an example)

Setting range I>: No or Yes can be selected, the current setting range is 0.1 In -25 In, and the accuracy is 0.01 In

Delay type: DT or IDMT (including multiple curves such as IEC-STI, IEC_SI, etc.).

Trip delay: 0-150s, accuracy 0.01s

TMS (time multiplier setting): 0.025-1.5, accuracy 0.025.

Reset feature: DT or IDMT, RTMS (reset time multiplier setting) 0.025-1.5, accuracy 0.025.

TReset (return time): 0.00 s-100 s, accuracy 0.01 s

I>and I>>... I>>>can set interlocks, select No or Yes.

Zero sequence overcurrent protection (P125, P126&P127)

Zero sequence current fundamental frequency and zero sequence voltage fundamental frequency monitoring.

Minimum operating zero sequence voltage: 1V (Uen: 57-130V); 3V(Uen: 220 - 480V)。

High sensitivity current setting (Cortec code P12-C-XX): Ie>range 0.002 Ien-1 Ien, accuracy 0.001 Ien, etc. (different sensitivities correspond to different ranges and accuracies).

Delay type, trip delay TMS、 The reset characteristics and other settings are similar to phase overcurrent protection.

Sensitivity angle (0 ° -359 °, accuracy 1 °) and trip zone (10 ° -170 °, accuracy 1 °) can be set.


Installation Guide

Installation environment requirements: The equipment should be installed in a dry, well ventilated environment, avoiding high temperature, high humidity, and strong electromagnetic interference areas. The recommended ambient temperature is within [specific temperature range], and the relative humidity should not exceed [specific humidity value].

Installation steps

Install the wiring board firmly onto the DIN rail, ensuring a secure installation and avoiding looseness.

Secure the interface unit and I/O module to the wiring board with bolts, paying attention to the correct installation direction and tightening the bolts to the specified torque.

Connect all on-site data wiring to ensure correct and secure connections, and avoid issues such as virtual connections and short circuits. When wiring, refer to the wiring diagram for operation.

Grounding requirements: The equipment casing must be reliably grounded, and the grounding resistance should be less than [specific resistance value] to ensure the safe operation and anti-interference ability of the equipment.


Operation Guide

Power on process: After checking the equipment wiring and installation, connect the auxiliary power supply, and the power indicator light should light up normally. Wait for the device self-test to complete. If any abnormalities are found during the self-test process, the corresponding fault indicator light will light up.

Human machine interface operation: Parameter settings, status monitoring, and other operations can be performed through the human machine interface. Voltage and other parameters can be set in the Configuration/General menu options, such as setting the voltage to 2Vpn+Vr (depending on actual needs).

Common operation examples: To set the phase current protection threshold, enter the corresponding protection setting menu, select the threshold type (such as fixed time limit, inverse time limit, etc.), set the setting value and other related parameters (such as trip delay, etc.).


Maintenance and upkeep

Daily inspection: Check the appearance of the equipment daily for any damage or deformation, ensure the status of the indicator lights is normal, and check for any abnormal sounds or odors. Regularly check whether the wiring is loose, and tighten it promptly if there is any looseness.

Regular maintenance: Conduct comprehensive maintenance every [specific time period], including cleaning the surface and internal dust of the equipment, and checking whether the components on the circuit board are damaged or show signs of aging. Perform functional testing on the equipment, such as phase current protection testing, phase voltage protection testing, etc., to ensure that all functions of the equipment are normal.

Troubleshooting and handling: If the equipment malfunctions, troubleshooting can be carried out based on the fault indicator light and human-machine interface prompt information. If an overcurrent fault occurs, check whether the load is overloaded and whether the protection setting value is reasonable. The common faults and their solutions are as follows:

Power failure: Check if the power input is normal, if the fuse is blown, and if the power module is damaged.

Communication failure: Check if the communication line connection is normal and if the communication protocol settings are correct.

Protection action: Analyze the reasons for the protection action, such as overcurrent, overvoltage, etc., and reset the protection after troubleshooting.


Precautions

It is strictly prohibited to perform dangerous operations such as plugging and unplugging modules while the equipment is running, in order to avoid equipment damage or electric shock to personnel.

When setting parameters, be careful to avoid incorrect settings that may cause abnormal device operation. After modifying important parameters, necessary testing and verification are required.

Equipment maintenance should be carried out by professionals. Non professionals are not allowed to disassemble the equipment without authorization to avoid irreparable damage.


Product positioning and core advantages

positioning

MV7000 is a water-cooled medium voltage inverter launched by GE, suitable for power conversion scenarios in the fields of oil and gas, ships, heavy industry, etc. It supports 3-81MW power output, with a maximum output voltage of 13kV, high reliability, high power density, and flexible configuration capability.

Core advantages

Leading power density: Using pressure bonded IGBT (PPI) technology, only 18 IGBTs can achieve 15MW output, with a power density of 1.5MVA/m ³ and compact equipment size (such as MV7306-3L with a width of only 4400mm).

High reliability: With a cumulative operation of over 14 million hours and an installed capacity of over 15GW, it supports N+1 redundancy design and can continuously conduct in case of faults, reducing downtime.

Flexible configuration: Provides two rectifier configurations: diode front end (DFE) and active front end (AFE), supporting 12/24/36 pulse harmonic control and complying with IEEE 519 standard without the need for additional filters.

Energy saving and efficient: Four quadrant operation supports energy feedback to the power grid, and the common DC bus system can recover braking energy. In AFE mode, the power factor reaches 1, and the system efficiency is as high as 99%.


Key technical characteristics

hardware design

Modular structure: The inverter cabinet adopts double-sided cooled IGBT modules, and the control hardware supports drawer style installation, making maintenance convenient (forward access design).

Transformer free design: AFE configuration does not require an input transformer, saving costs and space, and improving efficiency.

Cooling system: Integrated water cooling system, supporting redundant pump configuration, suitable for harsh environments such as ships and high vibration scenarios.

control and protection

Vector control: Equipped with Power Electronics Controller (PECe) as standard, it supports flux vector control. The speed adjustment accuracy is less than 0.5% without an encoder and less than 0.1% with an encoder.

Protection function: It has overcurrent, overvoltage, undervoltage, and motor stalling protection, supports voltage drop ride through of the power grid (continuous operation at a minimum of 70% rated voltage), and enables rapid start-up of rotating loads.

Communication protocol: Standard interfaces such as Profinet, Modbus, Ethercat, etc., supporting remote monitoring (Visor Connect system).

Harmonics and Energy Efficiency

Low harmonic: DFE configuration supports 12/24/36 pulse rectification, AFE configuration can achieve sine wave input, with harmonic content lower than IEEE 519 standard.

Energy recovery: During four quadrant operation, energy can be fed back to the grid, reducing cable losses and supporting reactive power compensation.


Application scenarios and industry adaptation

major industries

Oil and gas: liquefied natural gas (eLNG) trains, injection compressors, multiphase pumps, pipeline compressors.

Ships: cruise ships, LNG carriers, offshore drilling platforms, naval support vessels.

Heavy industry: metal rolling mill, testing bench, water pump, mine hoist, wind turbine, STATCOM (Static Var Compensator).

Typical applications

High precision control scenarios: such as steel rolling flatness control and precise power supply for offshore oil and gas exploration.

Energy saving scenario: Variable frequency speed regulation of water pumps and fans, replacing traditional mechanical couplings, with an energy-saving rate of over 30%.

Renewable energy: frequency conversion of wind farm inverters and energy storage systems.

Alstom (GE) make, 94VB Numerical Voltage & Frequency Protection Relay ...


  • HIMA X-AO1601 Termination Boards
  • HIMA X-AI3251 Digital Output Module
  • HIMA X-DO3251 Digital Output Module
  • HIMA X-DI3202 Termination Board
  • HIMA X-DI6451 Digital Input Module
  • XYCOM 96574-001 - Circuit Board Card Rev A
  • XYCOM 99212A-001 - Control Board Card CPX-7
  • XYCOM 99222-001 - Circuit Board Card Rev A
  • XYCOM 97780-002 - Circuit Board for Operator Panel Screen
  • XYCOM XVME-164/1 - Circuit Board 61116
  • XYCOM CMX-7D - Power Supply Circuit Board PN99865-001
  • XYCOM 10330-00800 - Digital I/O Board Circuit Card
  • XYCOM 8450-HU - Husky Monitor 98916-001
  • XYCOM XVME-428/2 - IASCM Communication Board
  • XYCOM 3512KPT - Industrial PC Operator Interface
  • XYCOM Checkpoint Cognex - Inspection Machine Vision Camera
  • XYCOM XVME-080 - IPROTO Intelligent Prototyping Module
  • XYCOM IV-1653 - Ironics VMEbus CRT Circuit Board
  • XYCOM M032000220 - Control Board
  • XYCOM 4850A - Operator Interface Panel 91855-001
  • XYCOM 9462 - HMI Operator Interface Panel 9462-016214001
  • XYCOM 9465 KPM - Monitor Industrial PC 9465-219114103
  • XYCOM 9486 - Monitor-Miniflex Portrait 9486-0343
  • XYCOM MVME-490/1 - Circuit Board Tegal 6550 Etcher
  • XYCOM 1300 - Node Module 1300-000100000
  • XYCOM 3510 T - Operator Interface
  • XYCOM 3512 KPM - Operator Interface Part No 3512-A1F114103
  • XYCOM 4615KPM - Operator Interface
  • XYCOM 8320 - Operator Interface Display Panel 94321-002
  • XYCOM 4105 - Operator Interface P/N 91904-001
  • XYCOM PM101683E - Operator Interface PM101683 E
  • XYCOM 301993 - Operator Panel 89086-501 Raycon
  • XYCOM 2000 - Operator Panel 97957-001
  • XYCOM 9410KP - Operator Touchscreen HMI 51338-STN
  • XYCOM 9987 - Operator Workstation CPU Board
  • XYCOM 94144-002 - CPU Board Rev V
  • XYCOM 9487 - Programmable Interface HMI Panel PC
  • XYCOM 70956-411 - PLC Module Card Ethernet Card MESA 4I29X
  • XYCOM PM101587 - Operator Panel
  • XYCOM XT1502-BB-RB - Display Panel XT 1502
  • XYCOM PM3510 - Operator Interface Terminal
  • XYCOM PM8450 - Operator Interface Repair Evaluation
  • XYCOM PM8480 - Operator Interface PM101269
  • XYCOM 8000-SKM - Power Supply Board Module
  • XYCOM 510084 - Power Supply Board
  • BENTLY NEVADA 3500/15 133292-01 Power Supply Module
  • ABB PM877 3BDH000777R1 Central_Unit Controller
  • GE Hydran M2-X Enhanced Monitoring
  • ABB REG316 1mrk000809-GA Numerical Generator Protection
  • ABB RED670 1MRK004810 Line differential protection
  • GE SR750-P5-G5-S5-HI-A20-R-E Feeder protection system
  • ABB PFTL301E-1.0KN 3BSE019050R1000 PillowBlock Load cells
  • Kollmorgen S33GNNA-RNNM-00 - Brushless Servo Motor
  • Kollmorgen 6sm56-s3000-g-s3-1325 - Servo Motor
  • Kollmorgen AKM52K-CCCN2-00 - Servo Motor
  • Kollmorgen PSR3-230/75-21-202 - Power Supply
  • Kollmorgen akm24d-anc2r-00 - Servo Motor
  • Kollmorgen AKM22E-ANCNR-00 - Servo Motor
  • Kollmorgen S60300-550 - Servo Drive
  • Kollmorgen B-204-B-21 - Servomotor
  • Kollmorgen AKM21E-BNBN1-00 - Servo Motor
  • Kollmorgen TT2953-1010-B - DC Servo Motor
  • Kollmorgen pa8500 - Servo Power Supply
  • Kollmorgen BDS4A-210J-0001-207C2 - Servo Drive
  • Kollmorgen TTRB1-4234-3064-AA - DC Servo Motor
  • Kollmorgen MH-827-A-43 - Servo Motor
  • Kollmorgen AKM24D-ACBNR-OO - Servo Motor
  • Kollmorgen 00-01207-002 - Servo Disk DC Motor
  • Kollmorgen AKM21C-ANBNAB-00 - Servo Motor
  • Kollmorgen PSR3-208/50-01-003 - Power Supply
  • Kollmorgen 6SM56-S3000 - Servo Motor
  • Kollmorgen DBL3H00130-B3M-000-S40 - Servo Motor
  • Kollmorgen 6SN37L-4000 - Servo Motor
  • Kollmorgen AKM65K-ACCNR-00 - Servo motor
  • Kollmorgen 6SM56-L3000-G - Servo Motor
  • Kollmorgen AKMH43H-CCCNRE5K - Servo Motor
  • Kollmorgen PSR4/52858300 - Power Supply
  • Kollmorgen KBM-79H03-E03 - Direct Drive Rotary Motor
  • Kollmorgen AKM33E-ANCNDA00 - Servo Motor
  • Kollmorgen U9M4/9FA4T/M23 - ServoDisc DC Motor
  • Kollmorgen AKM13C-ANCNR-00 - Servo Motor
  • Kollmorgen AKM43L-ACD2CA00 - Servo Motor
  • Kollmorgen AKM54K-CCCN2-00 - Servo Motor
  • Kollmorgen M-605-B-B1-B3 - Servo Motor
  • Kollmorgen AKD-P00606-NBAN-0000 - Rotary Drive
  • Kollmorgen 6SM-37M-6.000 - Servo Motor
  • Kollmorgen A.F.031.5 - Sercos Interface Board
  • Kollmorgen 918974 5054 - Servo PWM
  • Kollmorgen U12M4 - ServoDisc DC Motor
  • Kollmorgen AKD-B00606-NBAN-0000 - Servo Drive
  • Kollmorgen MV65WKS-CE310/22PB - Servo Drive
  • Kollmorgen 65WKS-CE310/22PB - Servo Drive
  • Kollmorgen EM10-27 - Module
  • Kollmorgen S64001 - Servo Drive
  • Kollmorgen CR03200-000000 - Servo Drive
  • Kollmorgen 6SM57M-3000+G - Servo Motor
  • Kollmorgen BDS4 - Servo Drive
  • Kollmorgen AKD-P00306-NBEC-000 - Servo Drive
  • Kollmorgen AKD-B01206-NBAN-0000 - Servo Drive
  • Kollmorgen STP-57D301 - Stepper Motor
  • Kollmorgen 6SM37L-4.000 - Servo Motor
  • Kollmorgen 44-10193-001 - Circuit Board
  • Kollmorgen PRDR9SP24SHA-12 - Board
  • Kollmorgen PRD-AMPE25EA-00 - Servo Drive
  • Kollmorgen DBL3N00130-0R2-000-S40 - Servo Motor
  • Kollmorgen S406BA-SE - Servo Drive
  • Kollmorgen AKD-P00607-NBEI-0000 - Servo Drive
  • Kollmorgen AKD-P01207-NBEC-0000 - Servo Drive
  • Kollmorgen CR03550 - Servo Drive
  • Kollmorgen VSA24-0012/1804J-20-042E - Servo Drive
  • Kollmorgen N2-AKM23D-B2C-10L-5B-4-MF1-FT1E-C0 - Actuator
  • Kollmorgen 04S-M60/12-PB - Servo Drive
  • Kollmorgen H33NLHP-LNW-NS50 - Stepper Motor
  • Kollmorgen A-78771 - Interlock Board
  • Kollmorgen AKM43E-SSSSS-06 - Servo Motor
  • Kollmorgen AKD-P00607-NBEC-0000 - Servo Drive
  • Kollmorgen E21NCHT-LNN-NS-00 - Stepper Motor
  • Kollmorgen cr10704 - Servo Drive
  • Kollmorgen d101a-93-1215-001 - Motor
  • Kollmorgen BDS4A-203J-0001-EB202B21P - Servo Drive
  • Kollmorgen MCSS23-6432-002 - Connector
  • Kollmorgen AKD-P01207-NACC-D065 - Servo Drive
  • Kollmorgen CK-S200-IP-AC-TB - I/O Adapter and Connector
  • Kollmorgen CR10260 - Servo Drive
  • Kollmorgen EC3-AKM42G-C2R-70-04A-200-MP2-FC2-C0 - Actuator
  • Kollmorgen BDS5A-206-01010-205B2-030 - Servo Drive
  • Kollmorgen s2350-vts - Servo Drive
  • Kollmorgen AKM24D-ANC2DB-00 - Servo Motor