K-WANG



Product Overview
Megatiker M4 is a high-end thermomagnetic molded case circuit breaker, and MS4 is a matching isolation switch, designed for high-power distribution scenarios, with high breaking capacity, easy installation, and multiple expansion features.
Product series and model range
1. Circuit breaker M4 (T743/T742/T744 series)
Rated current: 250/320/400/500/630A
Breaking level: F (36kA), N (50kA), H (70kA), L (100kA)
Polar numbers: 3P, 4P, 3P+N/2
2. Isolation switch MS4
Rated current: 400A, 630A
Extremes: 3P, 4P
Model: T743S400/630, T744S400/630
Size and weight
Overall dimensions
3P:140×260×105mm
4P:183×260×105mm
Weight (fixed type)
Configure 3P ≤ 400A 3P ≥ 500A 4P ≤ 400A 4P ≥ 500A
Circuit breaker 5.20kg 5.40kg 6.55kg 6.85kg
Isolation switch 5.00kg 5.25kg 6.40kg 6.68kg

Electrical and mechanical characteristics
General Parameters
Rated insulation voltage: 800V
Rated working voltage: 690VAC
Power frequency: 50/60Hz
Working temperature: -25~+70 ℃
Mechanical lifespan: 20000 cycles; Motor operation: 10000 times
Electrical lifespan (In): 4000 cycles; (0.5In): 8000 times
Breaking capacity (415VAC)
Level Icu (kA) Ics (% Icu)
F 36 100
N 50 100
H 70 100
L 100 70
Release parameters
Heat setting Ir: 0.8~1 × In
Magnetic tuning Ii: 5~10 × In
4P neutral wire protection: 100% phase polarity
Installation and wiring
Installation method: panel vertical/horizontal, reverse feeding
Wiring Type: Front Wiring, Rear Flat Wiring, Cage Terminal
Maximum cable: 300mm ² (hard)/240mm ² (soft)
Torque: 24Nm
Power consumption parameters (per pole)
Rated current phase pole power consumption (W) neutral pole power consumption (W)
250A 19.2 19.2
320A 16.4 16.5
400A 25.6 18.9
500A 23.6 28.7
630A 37.3 21.2
Capacity reduction characteristics
Temperature derating: rated current decreases gradually above 50 ℃
Altitude derating: voltage and current derating above 2000m
Structural derating: Plug in, pull-out, and leakage modules all require derating
Attachment system
Release device: shunt, undervoltage, delayed undervoltage, leakage module
Signal accessories: auxiliary contacts, fault signal contacts
Operating attachments: rotating handle, motor operating mechanism, padlock
Structural attachments: insertion/extraction base, terminal cover, phase insulation
Certification standards
Compliant with: IEC/EN 60947-2 (Circuit Breaker), 60947-3 (Switch)
Certification: CE, CCC, EAC, Classification Society (LR/RINA/BV)
Environmental Protection: REACH, RoHS, RAEE
Key issues
Question 1: What is the breaking level and corresponding breaking capacity of M4 circuit breaker, and how to select different levels?
Answer: M4 is divided into four levels: F (36kA), N (50kA), H (70kA), and L (100kA), all measured at 415VAC; Choose F/N for ordinary power distribution, and H/L for high industrial short-circuit risk scenarios.
Question 2: What are the adjustment ranges for thermal and magnetic trip of M4 circuit breaker, and what protection functions do they correspond to?
Answer: Thermal trip Ir=0.8~1 × In, used for overload long delay protection; Magnetic release Ii=5~10 × In, used for short-circuit instantaneous protection.
Question 3: How to reduce the capacity of M4 in high altitude and high temperature environments, and what is the most influential installation form?
Answer: When the altitude is greater than 2000m, the voltage and current are synchronously reduced in capacity; Temperature>50 ℃, current decreases; The combination of pull-out and leakage module has the most significant reduction in capacity, and the lowest reduction for the 630A model can be as low as 378A * *.

KONG JIANG
Add: Jimei North Road, Jimei District, Xiamen, Fujian, China
Tell:+86-15305925923