ABB PM866AK01 Controller
Equipment Overview
Core function: PM866AK01 is a compact processor unit of ABB AC 800M series, with control, communication, and redundancy support capabilities, suitable for industrial automation control scenarios, and can be configured through 800xA Control Builder.
Hardware composition: including microprocessor, RAM memory, real-time clock, LED indicator lights, Initiat button, and CompactFlash interface; The base (TP830) is equipped with 2 RJ45 Ethernet ports (CN1, CN2) and 2 RJ45 serial ports (COM3, COM4), where COM3 is the RS-232C port with modem control signal and COM4 is the isolated configuration tool port.
Key features: Supports CPU redundancy (improves availability, covers CPU, CEX Bus, communication interfaces, and S800 I/O), DIN rail quick installation (sliding locking mechanism), each base has a unique Ethernet address (hardware identity identification, can be viewed on the TP830 base label).
Core advantages
Having ISA Secure certification, high reliability, and easy fault diagnosis.
Modular design, supporting gradual expansion and adapting to applications of different scales.
The protection level is IP20 and no additional casing is required; Obtained comprehensive EMC certification.
Support the use of BC810/BC820 to implement segmented CEX Bus, ensuring communication compatibility based on standard hardware such as Ethernet, PROFIBUS DP, etc.
Built in redundant Ethernet communication ports to enhance communication stability.
Technical Parameter
Basic information
Product Code: 3BSE076939R1 (PM866AK01)
Redundancy support: None
High integrity: None
Clock frequency: 133 MHz
Performance (1000 Boolean operations): 0.09 ms
Memory 64 MB: (Application available RAM: 51.389 MB)
Storage flash memory:; support
Processor type: MPC866
Redundant configuration switching time: maximum 10 ms
Software and Task Capability
Each controller supports 32 applications, and each application supports 64 programs and 128 charts.
The controller supports up to 32 tasks with 32 different cycle times, and the application cycle time can be as low as 1 ms.
The firmware storage flash is 4 MB.
Power supply and power consumption
Power input: 24 V DC (19.2-30 V DC).
24V current consumption: typical 210 mA, maximum 360 mA.
Power consumption: Typical 5.1 W, maximum 8.6 W.
Supports redundant power status input and built-in 3.6V lithium battery backup.
Communication and I/O capability
Ethernet channels: 2 (IEEE 802.3 standard, 10 Mbit/s, RJ-45 female head)
Control network protocols: MMS (Manufacturing Message Service) and IAC (Inter Application Communication)
Recommended Control Network Backbone: 100 Mbit/s Switched Ethernet
Two RS-232C interfaces: (one universal and one for service tools)
Number of CEX Bus communication modules: 12
CEX Bus maximum power supply current: 2.4 A
Modulabus I/O cluster with non redundant CPUs: 1 electrical+7 optical
Modular I/O cluster with redundant CPUs: 0 electrical+7 optical
Maximum I/O module capacity of Modulabus: 96 for a single PM866 and 84 for redundant PM866
Modulus scan rate: 0-100 ms (depending on the number of I/O modules)