K-WANG
ABB Panel 800 - PP865 version 5.1
Specification
Display: 15-inch TFT-LCD display with a resolution of up to 1024 x 768 pixels, which can clearly present rich and detailed picture content and provide users with a high-quality visual experience to meet the needs of industrial automation, electric power, rail transport and other fields that require high clarity of information display.
Touch technology: equipped with resistive touch screen, sensitive operation, users can conveniently control and interact with the equipment through touch, which can effectively improve the operational efficiency.
Power supply: The power supply voltage is + 24V DC (allowable range 20 - 30V DC). The power consumption varies under different operating conditions, for example, in normal operation, the power consumption is about 8 watts (24V power supply), to ensure stable power supply, while maintaining a low level of energy consumption.
Operating and Storage Temperatures: The operating temperature range is from - 40°C to + 70°C, and the storage temperature range is from - 40°C to + 85°C. It has excellent temperature adaptability, and can be stably operated or stored in a variety of extreme environmental conditions, which is suitable for different geographical areas and working environments.
Dimensions and weight: With overall dimensions of 180 x 120 x 100 mm and a weight of 1.9 kg, the unit is compact and lightweight, making it easy to manoeuvre and arrange during installation and use without taking up too much space.
Protection level: The protection level reaches IP65 or IP67, which can effectively protect against dust, water and oil, etc. It can adapt to the more severe industrial field environment, reduce the equipment failure caused by environmental factors, and improve the reliability and service life of the equipment.
Communication Interface: It has rich communication interfaces, including Ethernet interface for high-speed data transmission, which can be used for efficient network communication with other devices; RS485 interface supports multi-node connection, which is suitable for industrial field bus communication and can be connected to many industrial devices; USB interface is convenient for external storage devices or other peripheral devices for data transmission and extended functions.
Memory: The application flash memory is 12MB, and there is also a CF card slot, which can be inserted into the Compact Flash memory card to further expand the project memory, to meet the needs of different levels of complexity of the control application of the memory capacity, to ensure that a large amount of data storage and the smooth operation of the programme.
Input/Output: Supports a variety of digital and analogue input/output modules, which can be flexibly adapted to different types of sensors, actuators and other equipment to achieve the acquisition and control of various industrial signals, to meet the diversified needs of industrial control.
Detailed Summary:
Panel Overview: The Panel 800 Operator Panel is designed to meet the needs of man-machine communication with functions such as display and control of text, dynamic indications, time channels, alarms and recipe handling, mostly working in an object-oriented manner. Configuration is performed on a personal computer via Panel Builder 800, after which the project is transferred and stored in the panel. It can be connected to a wide range of automation devices such as PLCs, servos or drives. The panel is available in several versions, e.g. version 5.1 with firmware version 4.0.
Safety Precautions
Installation environment: The device is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous locations, with an upper ambient temperature limit of 40°C for horizontal installation and 50°C for vertical installation.
Operational Safety: There are safety requirements for installation, use, maintenance and disassembly, such as prohibiting operation in hazardous environments and allowing only qualified personnel to operate.
Battery Replacement: The product contains a battery that must be replaced in a non-hazardous area and with the specified type of battery.
Installation Guidelines
Space and process: The thickness of the mounting plate is 1.5 - 9.0mm, and a certain amount of space should be reserved around the panel during installation. The installation process involves unpacking, cutting the opening, fixing the panel and connecting the cables, paying attention to electrical earthing, cable type and voltage polarity when making connections.
Mode switches: The panel has four mode switches, located on the back, which should normally be in the OFF position and should only be operated by qualified personnel. Different combinations of switches correspond to different functions, such as operating mode, system recovery, image loading, service menu and self-test.
Module Installation: Internal Compact Flash memory card can be installed to expand project memory, power failure is required for installation; Profibus DP expansion module can also be installed, check the device and pay attention to static protection before installation.CB810 - USB to Ethernet Adapter is used for project-specific transmissions, connection and usage restrictions apply.