ABB REF610 feeder protection relay Fault recording and communication function

From: | Author:Wang | Time :2025-05-27 | 194 visit: | Share:

ABB REF610 feeder protection relay Fault recording and communication function 

Fault recording function

1. Fault record types and storage

Event record:

Up to 100 events can be recorded, including protection phase start/trip, digital input status changes, communication anomalies, etc. Each event contains a timestamp (accurate to milliseconds), event code, and relevant parameter values (such as fault current, phase imbalance, etc.).

Events are sorted by priority, with the highest priority being internal relay failure (IRF), followed by trip events, and finally start/alarm events.

Fault Record (FR):

Record detailed data of the last 5 faults, including three-phase current, ground current, thermal level, triggering stage, and duration at the time of the fault, and support reading through parameters V1-V24.

The data is stored in non-volatile memory (EEPROM), retained after power failure, and can be cleared through Master Reset.

2. Trigger and Query

Trigger condition:

Internal protection stage actions (such as overcurrent, ground fault), external digital input triggering, manual triggering (via SPA parameter M1).

Support setting trigger thresholds (such as current exceeding the set value) and edge triggers (rising/falling edge).

Query method:

Read event codes and data through HMI menu or serial communication (SPA/Modbus, etc.).

Support filtering by time sequence or event type, with fault codes corresponding to specific fault types (such as IRF code 4 indicating output relay PO1 fault).

3. Fault diagnosis and alarm

Internal Relay Failure (IRF):

When a permanent fault is detected (such as program memory error, hardware failure), the green LED flashes, the LCD displays a fault code (such as 30 indicating program memory failure), and all outputs are locked.

Warning:

Non fatal faults (such as low battery level, abnormal communication module), yellow LED activation, LCD display warning code (such as 1 indicating low battery), relay continues to operate but some functions may be limited.

External instructions:

Send fault warnings through signal output (SO2) or communication interface, supporting remote monitoring.


Communication function

1. Communication interface and protocol

Front end interface:

Infrared interface: supports wireless or cable connection (IrDA) ®  Standard), only used for SPA bus protocol, with a fixed baud rate of 9.6 kbps, used for local parameter configuration and data reading.

Backend interface (optional module):

Fiber optic (plastic/glass): Supports SPA bus, IEC 60870-5-103 protocol, anti electromagnetic interference, suitable for long-distance communication.

RS-485: Supports Modbus RTU/ASCII, DNP 3.0 protocols, can connect up to 32 nodes, and has a bus length of up to 1200 meters.

DNP 3.0 module: dedicated to DNP 3.0 protocol, supports 2-wire or 4-wire half duplex communication, suitable for smart grid systems.

2. Supported communication protocols

SPA bus:

ABB specific protocol, used for local parameter settings and firmware upgrades, supports password protection (SPA password V160 is required).

IEC 60870-5-103:

Compliant with power system communication standards, used for transmitting measurement values, status data, and event records, supporting cyclic queries (GI) and emergency reporting.

Modbus RTU/ASCII:

Industrial universal protocol, supporting function codes 01-04, 05-06, 15-16, etc., readable and writable registers (such as HR/IR) and coils (DI/CO).

DNP 3.0:

Supports event grading (Class 1-3) and non sold reporting, suitable for remote terminal unit (RTU) communication, configurable scaling factor and dead zone.

3. Data transmission and configuration

Parameter Mapping:

Analog quantities (such as current, heat level) and digital quantities (such as output status, DI signal) are mapped to Modbus registers (such as HR404 corresponding to L1 phase current).

User defined registers (UDRs) can be associated with any register, facilitating custom data mapping.

Communication parameters:

Baud rate: 9.6/4.8 kbps (SPA/IEC 103), configurable to 2.4/1.2/0.3 kbps (Modbus).

Parity check: none/odd/even, data bits: 7/8 bits, stop bits: 1/2 bits.

Network topology:

Supports Loop or Star topologies, fiber optic modules require terminal resistors (120 Ω) and bias resistors to be configured.

4. Time synchronization and remote control

Time synchronization:

Synchronize real-time clock with an accuracy of ± 2.5 ms (second pulse) through digital input (minute pulse/second pulse) or communication protocol (such as DNP 3.0).

Remote control:

Remote modification of protection parameters, triggering tests, resetting counters, or clearing event records through Modbus or SPA protocols.

Support remote tripping and reclosing control through communication modules.


Collaborative application of fault recording and communication functions

Remote fault diagnosis:

Fault events are uploaded in real-time to the monitoring system through the communication interface, and support reading fault codes and data (such as V168 warning codes and V169 IRF codes) from registers through Modbus function codes 03/04.

Disturbance Recorder:

When a fault is triggered, it automatically records the analog signals (such as current waveforms) and digital signals before and after the fault, and supports downloading them to a PC for analysis through a communication interface (COMTRADE format).

Firmware Upgrade and Configuration Management:

Upgrade relay firmware remotely through communication interface, or batch configure multiple device parameters through SPA bus to improve maintenance efficiency.


Key parameters and limitations

Fault record capacity: 100 events+5 detailed fault records (FR)

Communication baud rate range: SPA/Modbus: 0.3-9.6 kbps; IEC 103: 9.6 kbps; DNP 3.0: configurable up to 38.4 kbps

Maximum number of nodes: RS-485/DNP 3.0: 32; Fiber optic ring network: no explicit restrictions (depending on topology)

Data transmission delay: Typical response time of 20-100 ms (Modbus), disturbance record download time depends on the amount of data


  • Kollmorgen PSR4/5A-220 - Servo Power Supply Module
  • Kollmorgen pcb-r0461000-31 - Board
  • Kollmorgen Opt x2 Pro 7 - Display
  • Kollmorgen AKM31H-ANC2EG00 - Motor
  • Kollmorgen AKI-CDT-MOD-15T-000 - HMI Module
  • Kollmorgen ERH-26 - Resistor
  • Kollmorgen M.1016.2536 - Axis Cable
  • Kollmorgen PRD-0019100E-00 - Servo Drive Boards
  • Kollmorgen 00D12A02110-1 - Motor
  • Kollmorgen M.1016.9514 - Interface Cable
  • Kollmorgen S21260-SRS - Drive
  • Kollmorgen M.1016.2566 - I/O Cable
  • Kollmorgen D062A-12-1210 - Motor
  • Kollmorgen M.1016.2565 - Cable
  • Kollmorgen M.1302.6402 - Sercos Cable
  • Kollmorgen ps-1 - Power Supply
  • Kollmorgen Step Motors & Controls - Product Catalog
  • Kollmorgen AKM21E-CKBNEH00 - Servo Motor
  • Kollmorgen BDS5A-106-01010/03011A2-030-001 - Servo Driver
  • Kollmorgen S30361-SE - Servo Drive
  • Kollmorgen EM1-98 - Module
  • Kollmorgen DMC50720EXT24V - Servo Drive
  • Kollmorgen EM-1 - Module
  • Kollmorgen AKM21G-ENSN2-02 - AC Servo Motor
  • Kollmorgen CF-SS-RHAE-03 - Cable
  • Kollmorgen M.3000.1408 - Cable
  • Kollmorgen EB-204-B--91-001 - Brushless Motor
  • Kollmorgen SERVOSTAR 606 - Servo Drive
  • Kollmorgen C-78530-2 - Power Supply Board
  • Kollmorgen M.1016.2261 - Memory Module
  • Kollmorgen C-78167-3 C-78166-2 - Pulse Generator Board
  • Kollmorgen B-202-C-23 - Servo Motor
  • Kollmorgen EM2-27 - Module
  • Kollmorgen AKM31H-ANCN2-00 - Servomotor
  • Kollmorgen AKM32E-ANC2R-00 - Servomotor
  • Kollmorgen C-78799-2 - Board
  • Kollmorgen PSR4/5A-112 - Power Supply
  • Kollmorgen M.1302.8619 - Resolver Cable
  • Kollmorgen TPAR-3330-34 - Drive Unit
  • Kollmorgen M21NSXA-LNS-NS-05 - Step Motor
  • Kollmorgen S72401-NA - Servo Drive
  • Kollmorgen 12310-000-3/3-02-2 - Circuit Board
  • Kollmorgen M.1302.8447 - Encoder Cable
  • Kollmorgen TPAR-3340 - Velocity Drive Amplifier
  • Kollmorgen B-202-B-21 - Servo Motor
  • Kollmorgen SBD2-16-1102-29360BA29/160-16 - Servo Drive Board
  • Kollmorgen VP-507BEAN-03 - Power Cable
  • Kollmorgen S72402-PBNAPM - Servo Drive
  • Kollmorgen CE03550 - Servo Drive
  • Kollmorgen LE03565-JW02 - Servo Drive
  • Kollmorgen A.F.031.5/07 - Sercos Interface Board
  • Kollmorgen C-78087-1 - Board
  • Kollmorgen 610 - Servo Drive
  • Kollmorgen M21NRXC-JNN-NS-02 - Step Motor
  • Kollmorgen DBL3H00250-BR2-000-S40 - Servo Motor
  • Kollmorgen C-78182-1 - Board
  • Kollmorgen 610-AS - Servo Drive
  • Kollmorgen PRD-PE210EOH-00 - Controller
  • Kollmorgen ESD-1024-315-G - Encoder
  • Kollmorgen VP-507BEAN-M3 - Power Cable
  • Kollmorgen C-78178-1 - Board
  • Kollmorgen TT-2043-1011-B - DC Motor
  • Kollmorgen VP-507BEAN-01 - Power Cable
  • Kollmorgen M-405-A-A1 - Servo Motor
  • Kollmorgen Prd-0017000L-30 - Robot Axis Control Module
  • Kollmorgen S70601-SENA-NA-0X9 - Servo Drive
  • Kollmorgen C-78166-1 - Board
  • Kollmorgen S20360-VTS - Servo Drive Data Cable
  • Kollmorgen S403AM-SE - Servo Drive
  • Kollmorgen VFS5-275-00120/2604A-015 - Servodrive
  • Kollmorgen MT304TB1-R2F4 - Servo-Motor
  • Kollmorgen 601 - Servo Drive
  • Kollmorgen CR10704 - Servo Drive
  • Kollmorgen PSR4/5A-112 - Industrial Drive
  • Kollmorgen PRD-MZ40ASIz-62 - Servo Drive
  • Kollmorgen M.1016.2514 - Axis Cable
  • Kollmorgen EM2-19 - Module
  • Kollmorgen M.1301.5566 - Cable
  • Kollmorgen LR10665 - Servo Driver
  • Kollmorgen AKI-CDA-MOD-04T - Operator Terminal Display
  • Kollmorgen PRD-B032010z-11 - Servo Board
  • Kollmorgen M.1302.8606 - Endat Cable
  • Kollmorgen M.1016.2513 - Axis Cable
  • Kollmorgen MW1000512 - Linear Magnet Way
  • Kollmorgen B-606-BA-91-TR501-008 - Servomotor
  • Kollmorgen urs3310a-300-x23 - Servo Motor
  • Kollmorgen CR06561 - Servo Drive
  • Kollmorgen il03030a1104 - Direct Drive Linear Motor
  • Kollmorgen 6SM-56-S-3000 - Servo Motor
  • Kollmorgen KXA-48-8-16/AUX - PCB Card
  • Kollmorgen 443M-C - Servo Drive
  • Kollmorgen DBL4H00260-0R2-000-S40 - Servo Motor
  • Kollmorgen PRD-AG50100B-00 - Servo Board
  • Kollmorgen s30601-na - Servo Drive
  • Kollmorgen M.1302.0944 - Encoder Cable
  • Kollmorgen M.1016.2725 - Connector
  • Kollmorgen C-78684-1 - Board
  • Kollmorgen PROFIBUS dp 001106712385 - Profibus Module
  • Kollmorgen 768-026902-01 - Board
  • Kollmorgen AKM42E-GNC2R-00 - Servo Motor
  • Kollmorgen AKD-P00306-NBEC-0069 - Servo Drive
  • Kollmorgen SPAE1115-503 - Power Supply Drive
  • Kollmorgen AKM52G-ANCSEJ02 - Servo Motor
  • Kollmorgen BE25A20IE-K41 - Brushless Servo Amplifier
  • Kollmorgen C-78167-3 - Pulse Generator Board
  • Kollmorgen C-78770-3 - Board
  • Kollmorgen A-80387-2 - PCB
  • Kollmorgen 3EF-50 - Line Filter
  • Kollmorgen RP0601 - Power Block Industrial Drive
  • Kollmorgen SE20200 - Servo Amplifier
  • Kollmorgen ESA10/75HT - Servo Amplifier & DC Motor
  • Kollmorgen M.1302.1115 - Power Cable
  • Kollmorgen AKM43G-EKCNR-01 - Servo Motor
  • Kollmorgen IC11075A1T5P1 - Linear Actuator
  • Kollmorgen 60WKS-CE240/12PB - Servo Amplifier
  • Kollmorgen AKM32D-ANC2R-00 - Servo Motor
  • Kollmorgen CR03260 - Servo Drive
  • Kollmorgen ICD10-100A4TRC1-2K01702 - Linear Direct Drive
  • Kollmorgen DGE-25-850-ZR-LV-RF-KG-KF-GA - Linear Actuator
  • Kollmorgen M.1302.5835 - Encoder Cable
  • Kollmorgen CR10250 - Servo Drive
  • Kollmorgen SR20200-00000 - Servo Drive
  • Kollmorgen M.1302.1114 - Power Cable
  • Kollmorgen NEAT-310M - Stepping Motor Controller
  • Kollmorgen A-78703-2 - Board
  • Kollmorgen RK-V 6SM/DBL/K - Servo Cable
  • Kollmorgen PRD-0W13000F-11 - Circuit Board
  • Kollmorgen A.F.031.5 - Sercos Interface Board