+086-15305925923

K-WANG

Service expert in industrial control field!
NameDescriptionContent
Adequate Inventory, Timely Service
pursuit of excellence 
Ship control system
Equipment control system
Power monitoring system
Current position:
新闻动态
newS
   
Brand

ABB SYNCHROTACT®5 Operating Instructions

From:ABB | Author:Wang | Time :2025-01-02 | 1788 visit: | 🔊 Click to read aloud ❚❚ | Share:

ABB SYNCHROTACT®5 Operating Instructions

General information
1.1 Introduction
This User Manual is aimed at persons who have a basic knowledge of working with
electronic equipment, who understand electrical symbols in schematic diagrams, but
who know little or nothing about working with SYNCHROTACT 5 equipment.
The User Manual provides the information required in order to install, commission and
operate the SYNCHROTACT 5 device of types SYN 5201 and SYN 5202.
1.2 Marking of text sections
General warning
This symbol placed before the text indicates situations or conditions which can cause a
risk of death or serious injury. The text describes the procedure for preventing these
risks.
Dangerous voltages
This symbol indicates that, when handling the equipment, dangerous voltages occur
which can cause death or serious injury.
The sections of text marked with "Caution" contain information on situations which can
lead to material damage or equipment failure if the instructions are disregarded.
The sections of text marked with "Note" provide additional information. This must be
taken into consideration in order to prevent malfunctions.
Caution
Note
1.3 Purpose and use of the SYN 5201 and SYN 5202
The digital synchronizer can be used for the following applications:
• For automatic synchronization and paralleling of generators
• For automatic paralleling of synchronous and asynchronous lines, transmission lines
and busbars (incl. tap-changer matching).
• As a paralleling monitoring device (synchrocheck) for monitoring automatic or manual paralleling sequences including dead bus.


Brief description
The SYNCHROTACT 5 digital synchronizer is used for automatic synchronizing and
paralleling of generators with lines and for the paralleling of already synchronous lines.
The device is designed for system frequencies of either 50/60 Hz or 16 2
/3 Hz.
SYN 5201 is a single-channel synchronizing device whose component choice and
software design provides the highest security against incorrect paralleling.
SYN 5202 consists of two independent channels with different hardware and software.
This dual-channel property maximizes security against incorrect paralleling.
All parameters required for paralleling are stored in a parameter set. The paralleling
conditions and the characteristics of the voltage and frequency matchers are defined in
this set. With the option providing seven parameter sets, paralleling can be carried out
under different conditions or with different matcher characteristics using the same
device. Seven configurable digital inputs and outputs are available for the selection and
back indication of a parameter set.
The data which are important for commissioning and for control purposes can be
uploaded or downloaded using the PC tool SynView or, alternatively, via the keypad on
the front panel of the unit.
The following measured variables are generated from the two single-phase measuring
voltages:
Voltage U1, U2
U1 is the reference voltage e.g. line
U2 is the adjustable voltage e.g. generator.
Frequency f1, f2
f1 is the reference frequency
f2 is the adjustable frequency.
Voltage difference ΔU
ΔU = IU1I – IU2I
ΔU > 0 Adjustable voltage is lower
ΔU < 0 Adjustable voltage is higher
Slip s %100*121fs ff − =
s > 0 Adjustable frequency is less (e.g. generator is sub-synchronous)
s < 0 Adjustable frequency is greater (e.g. generator is oversynchronous)
Phase-angle difference α
21 ϕ ϕ α −=
α > 0 Adjustable frequency is lagging
α < 0 Adjustable frequency is leading
Acceleration ds/dt
[ ]ss dtdsxxx /%*2/
561∑==Δ=
(Every 0.5 s, an average value is formed from 56 measurements; sampling period: 9 ms)
ds/dt > 0 Adjustable frequency is reduced (e.g. generator accelerates)
ds/dt < 0 Adjustable frequency increases (e.g. generator is slowed down)
With SYN 5202, the measurement is carried out separately for each channel. It is
possible to carry out three-phase measurements in order to detect connection faults
(rotary field, polarity) and losses of phase.


Voltage measurement (SYN 5202: channel 1)
The two input voltages U1 and U2 are passed to the processor via high-impedance input
resistors, differential amplifiers, low-pass filters and A/D converters.
Voltage measurement channel 2 (SYN 5202 only)
The two input voltages U1 and U2 are passed through high-impedance input resistors
and differential amplifiers. The signal for the amplitude value is formed from this by
conversion and filtering . For zero-passage detection, the signal is filtered and passed
through a comparator. The signals prepared in this way are passed to the processor via
the A/D converter.

SYN 5201

SYN 5202
Frequency matcher with variable intervals
The function INVERSE f changes the way the frequency matcher functions. The pulses
are now always the same length, but the intervals are inversely proportional to the slip.
Pulse length: adjustable by means of the parameter tp fmin: tp = tp fmin
Pause interval: is calculated according to the following formula (can not be set as a
parameter):
2.2.3 Monitoring of paralleling conditions
The monitoring of the paralleling conditions can be divided into these parallel-functioning
blocks:
• voltage-carrying lines
• no-voltage lines
Paralleling of two voltage-carrying lines
The monitoring of the paralleling conditions enables a paralleling command (CHK
RELEASE) if the following conditions are fulfilled simultaneously:
• the phase-angle difference is within the tolerance band
• the slip is within the tolerance band
• the voltage difference is within the tolerance band
• the voltage does not fall below minimum voltage
• the maximum voltage is not exceeded
• the device is in operating status (OPERATING)
• nominal frequency deviation ≤ 5 Hz
Paralleling of no-voltage lines (dead bus)
A special case for the monitoring is the paralleling of no-voltage lines. A paralleling
command release is only issued if the external release signal is active and the
measuring logic enables the release at the same time. The release by the measuring
logic can be enabled if both voltages are within one of the permitted ranges. The dead
bus range can be defined as permissible for one, the other or both measuring voltages
by means of the parameters U1not, U2not and 1*2not.
The monitoring of the paralleling conditions (CHK RELEASE) releases the paralleling
command if the following conditions are fulfilled simultaneously:
• the releasing signal for dead bus (digital input) is issued
• the zero voltage(s) does not exceed the set threshold U0max
• the current voltage does not fall below the minimum voltage
• the current voltage does not exceed the maximum voltage
• the current zero voltage situation corresponds to a configuration permitted by means
of U1not, U2not, 1*2not
• the device is in Operating status (OPERATING)
2.2.4 Command generation
The command generation makes a distinction between asynchronous and synchronous
sources or no-voltage lines. Two modes, one for asynchronous and one for synchronous
sources, run in parallel, so that a source can be asynchronous or synchronous at any
time. The paralleling command is issued in the mode in which all conditions are fulfilled
first.
In SYN 5202 the actuation of the paralleling relays takes place separately in both
channels.
Asynchronous sources
It is called asynchronous sources, if the two lines to be paralleled (or generator and line)
are asynchronous before the circuit breaker is closed.
From the slip s, the acceleration ds/dt, the line frequency f1 and the set paralleling time
t on, the command generation calculates the necessary lead angle αv by which the
paralleling command is shifted forward in time so that the main contacts close exactly on
phase coincidence (see following figure)
  • Metso XZB10025-011T12 - Moog Valve 9650962700
  • Metso XZB10025-010T12 - Moog Valve 9650965300
  • Metso-SP Transmitter Cable - Operating Unit with 10m Cable
  • Harkila Metso Hybrid - Hunting Jacket Willow Green
  • Metso ND8221/S1 - Neles Valve Positioner
  • Metso METSO10119 - ScreenCheck Component
  • Metso LK-2025 - Linkage Kit
  • Metso A416733 - IQweight External Air Gap Temperature Sensor
  • Metso RKC22MT - Automation Component
  • Metso A413281 - Automation Board
  • Metso LCP9HLY - Stainless Steel Enclosure
  • Metso NP704S/B1S1 - Pneumatic Positioner with I/P Converter
  • Metso BAH3 - Slurry Seal Type
  • Metso A413531-03 - PLC Module Chassis Rack
  • Metso P4610004 - MCAI Communicator Controller
  • Metso QN2AN03HDM - Quartz Valve Positioner Stonel
  • Metso RKW-352-XZ - Automation Component
  • Metso A4300081 - Kajaani LCD Display
  • Metso A428026 7B - Kajaani Rectifier Unit 1
  • Metso 202218 - Kajaani Sensor Power Supply SR 902660
  • Metso 9150 316SS CSTL - Jamesbury 150-2" BN50 Valve
  • Metso 81806 - IOP101 Module
  • Metso STOM000272 - Paper Bushing CR38
  • Metso 1975413 - Chain Hoist Links
  • Metso IMO G053-191597 - Minor Seal Kit
  • Metso VAL0087418 - Cylinder Valmet NTS6LV
  • Metso A413061 - DMU Board VPA 420355-4B
  • Metso P2620-80/25-100 - Automation Component
  • Metso VAL0035292 - Automation Component
  • Metso A413721 - Automation Component
  • Metso ST600 - Automation Component
  • Metso P4500001 - Automation Component
  • Metso SDBX/RA2 - CAT x KVM Extender
  • Metso D201126-DI8 - Digital Input Module
  • Metso D201189L - AI8H Analog Module
  • Metso NA004418 LK1016 - Wafersphere Actuator Mounting Bracket
  • Metso RKN172MTT - Repair Kit
  • Metso MM0311584 - Air Filter Kit RadialSeal
  • Metso 181517 - IOP301 Isolated Analog Input Module
  • Metso RAU3906506 - Automation Component
  • Metso 181208 - IOP332 Digital Input Module
  • Metso A413760 - AIF2C PCB Module
  • Metso 006 1089 36 - Shaft Bearing Seal
  • Metso A413046 - Automation Component
  • Metso VKJ650 - Automation Brake Component
  • Metso LK-1875 - Linkage Kit
  • Metso D201193L - FI4S24 Frequency Input Module
  • Metso D200533 - BIU82 Binary Input Module
  • Metso 500838-M1 - Impeller Pump Release Collar Assembly
  • Metso 2.00SB2ALUS19A - Pneumatic Cylinder 1.375 Stroke
  • Metso D201351 - RES Reserve Module
  • Metso A416100 - IQMoisture Spare Part Kit Halogen Lamp
  • Metso Slurry Pump - Back Liner
  • Metso 7088010042 - Bronze Lantern Ring
  • Metso IMC-101-M-SC - Industrial Media Converter
  • Voith S1-S1-CAM-ENCL - Metso Pump Cmare Housing & Bracket
  • Metso A4430726V1.1 - Kajaani Connection Box CI 4-9-10
  • Metso A413016 - NCU2 PLC Board
  • Metso D202213P - MBMT80 Base
  • Metso A413135 - AOU-4 Analog Output Board
  • Metso NP 724A - Pneumatic Valve Positioner
  • Metso A413246 - Automation Controller Module
  • Konaflex VKJ-650 - Disc Brake Set Pair
  • Metso WIN3096535D - Core Chuck
  • Metso D201380 - MBR Base with IBC & IPS
  • Metso D202213L - MBMT80 Base Module
  • Metso 181571 - IOP337 PLC Module
  • Metso MF0588336 - Main Hydraulic Filter
  • Metso 181504 - IOP303 RTD Input Module
  • Metso A413240 - PIC2 Board
  • Denver 566534PS - Case Liner Gland Side SRL Frame 2
  • Metso 181508 - IOP322 Digital Input Module 120V
  • Metso 181520 - IOP351 Relay Output Module Form A/B
  • Metso 181220 - IOP351 Relay Output Module
  • Metso A413150 - BOU 8 Binary Output Module
  • Metso 128400-M1 - Impeller
  • Metso D201379 - MBB Base with IBC & IPS
  • Metso 205181 - T/B MTD PRWSW Assembly
  • Metso QPX1C/K15 - Jamesbury Quadra-Powr X Actuator Valve
  • Harkila Metso Winter - Hunting Jacket Willow Green
  • Metso NE724A/A-L - Electro-Pneumatic Positioner
  • Metso PACP-100-80-31 916 - Automation Component
  • Metso 81814 - Automation Component
  • Metso ER-12-01-M-CT - Automation Board
  • Metso ELO24 - Automation Board
  • Metso A413000 - Valmet Neles CPU PLC Board
  • Metso XL-2213-0525 - Mainframe Bushing
  • Metso D100097 - ECR Extension Module
  • Metso 804511 - Filter Housing Assembly
  • Metso S420154 - Automation Rack Chassis
  • Metso M851232 - Automation Module
  • Metso D100532 02 - Automation Board
  • Neles QPX1C/M - Ball Valve with Quadra-Powr X Actuator
  • Metso 181535 - IOP322 Isolated Analog Output Module
  • Metso RKN-184-XTZ - Ball Valve Seat Repair Kit 4"
  • Metso N22022621 - Metal Plate
  • Metso 181560 - IOP341 Positioner Module
  • Metso LT 1213 S - Filter Service Kit for CAT C12 Engine
  • Aq-Matic 0032-99000 - Valve Diaphragm
  • Metso D200535 - BOU8 Output Board
  • Metso EDS-305-M-SC - Ethernet Switch
  • Metso 80424 - IOP110 Analog Output Module
  • Metso IOP351 - Relay Output Module Form A/B
  • Metso 181572 - IOP342 Module
  • Metso 1-1-2A3600TT - Ball Valve 1.5"
  • Metso A413154 - BOU8-4 Output Module
  • Metso A413140 - Valmet BIU 8 Board
  • Metso D201139 - IPS Power Supply type DDC7940
  • Metso PGH P411382-2000 - Metal Feed/Filtrate Hose
  • Valmet 503201404 - Automation Board
  • Metso 181507 - IOP331 Controller Module
  • Metso A413141 - BIU82 Binary Input Module
  • Metso KSD7447686 - Pneumatic Cylinder 5" Bore
  • Metso APL3003850 - Automation Component
  • Metso D201135L - Automation Controller
  • Metso A413125 - AIU8 Analog Input Module
  • Metso A413325 - IPU Power Unit
  • Metso 181573 - IOP346 PLC Module
  • Metso A413143 - BIU84 Binary Output Module Card
  • Metso A413152 - BOU82 Output Module
  • Metso PDP603 - Distributed Processing Unit 181555
  • Metso PDP601 - Distributed Processing Unit 181555
  • Metso A413040 - DCS Board DCU
  • Metso A413082 - CPU Processor Module
  • Valmet TI4W3 - Temperature Input Module
  • Valmet FI4S24 - Frequency Input Module
  • Metso 1064669615 - Fulcrum Bar
  • Valmet 181206 - IOP330 Digital Input Module