K-WANG

+086-15305925923
Service expert in industrial control field!
NameDescriptionContent
Adequate Inventory, Timely Service
pursuit of excellence 
Ship control system
Equipment control system
Power monitoring system
Current position:
新闻动态
newS
   
Brand

TOSHIBA VF-AS3 inverter RS485 communication function

From: | Author:Wang | Time :2025-11-17 | 272 visit: | 🔊 Click to read aloud ❚❚ | Share:


TOSHIBA VF-AS3 inverter RS485 communication function

Document Overview and Security Standards

Document positioning: Special description of the RS485 communication function of VF-AS3 frequency converter, which needs to be used in conjunction with the main manual (E6582062). The core goal is to achieve remote data exchange between the frequency converter and the controller (PLC/computer) or frequency converter.

Core safety requirements:

Specific safety requirements and risk warnings

Cable operation prohibits live plugging and unplugging of RS485 cables, which may cause equipment failure

Interface restrictions prohibit Ethernet from being connected to RS485 interface for abnormal communication or hardware damage

Storage life: EEPROM write times ≤ 100000 times, RAM unlimited EEPROM overload failure

Communication timeout parameters (F803/F823) must be set for timeout settings. The device cannot stop in case of communication failure


Hardware wiring and transmission specifications

1. RS485 interface definition

VF-AS3 provides 2 RS485 interfaces, and the pin functions are shown in the table below (key pins are bolded):

Interface Type Pin Signal Name Function Description Wiring Requirements

Connector1 (default 2-wire) 4 RXA+/TXA+non-polar transmission and reception data must be connected, shared by 2-wire/4-wire

5 RXB -/TXB - polarity transmission and reception data must be connected, shared by 2/4 wires

8 (3) SG signal ground must be connected to prevent interference

1/2/6- Prohibit connection to avoid short circuit

7 Power prohibits connection to prevent power conflicts

Connector2 (supports 2-wire/4-wire) 4 RXA+/TXA+2-wire transceiver/4-wire receiver [F829]=0 (2-wire) takes effect

5 RXB -/TXB -2-wire transceiver/4-wire receiver [F829] takes effect when=0 (2-wire)

Effective when TXA 4-wire system sends [F829]=1 (4-wire)

Effective when TXB 4-wire system sends [F829]=1 (4-wire)

8 SG signal ground must be connected

2. Wiring specifications

Cable selection: shielded twisted pair, conductor cross-sectional area ≥ AWG24 (0.22mm ²), characteristic impedance 100-120 Ω.

Required resistance:

Terminal resistance: 120 Ω/1/2W, only connected to devices at both ends of the bus.

Up and down resistance: 510 Ω/1/2W, each node needs to be connected to enhance signal stability.

Distance requirement: The distance between communication cables and main circuit cables should be ≥ 20cm to avoid interference; In the 4-wire system, the transmission (TXA/TXB) and reception (RXA/RXB) need to be twisted separately.

3. Transmission specifications

Project Specification Default Values Remarks

Transmission method half duplex - only receive/send at the same time

Synchronization start and end synchronization - identify the beginning and end of the frame by 3.5 bytes of blank time

Baud rate 9600/19200/38400bps. After changing 19200bps, power off reset is required to take effect

No/even/odd parity check. After the parity check is changed, it needs to be powered off and reset to take effect

Data bit ASCII: 8-bit (JIS X0201); Binary/MODBUS: 8-bit --

Stop bit reception: 1 bit; Send: 2 bits - compatible with devices with 1/1.5/2 stop bits

Error detection Toshiba protocol: checksum; MODBUS:CRC16 - -

Detailed Explanation of Communication Protocol

1. Toshiba inverter protocol (default, [F807]/[F827]=0)

Supports ASCII, Binary, and block communication modes. The core is to access parameters through the "communication number", and commands include R (read), W (write RAM+EEPROM), P (write RAM), S (inter inverter), etc.

ASCII mode:

Format: (INV-NO CMD communication number DATA&SUM) CR (INV-NO: 2 bits, 00-99; SUM optional).

Example: Assuming a frequency of 60Hz (communication number FA01, 60Hz=1770H), the command is (00PFA011770) CR, and the response is (00PFA011770) CR.

Binary mode:

Format: INV-NO CMD communication number DATA SUM (header code "/", INV-NO: 1 bit, 00H-3FH; SUM must be selected.

Example: Read output frequency (communication signal FD00), command is 2F 52 FD 00 82, response is 2F 52 FD 00 17 70 05 (60Hz).

Block communication:

Function: Read and write multiple preset parameters in a single communication ([F870]/[F871] set write parameters, [F875] - [F879] set read parameters).

Format: The computer sends the X command, and the frequency converter sends the Y command back. It supports up to 2 write parameters and 5 read parameters.

2. MODBUS-RTU protocol ([F807]/[F827]=1)

Only partial instructions are supported, with binary data and frame synchronization relying on 3.5 bytes of blank time. The core instructions are shown in the table below:

Example of Applicable Scenarios for Instruction (Hex) Function (Read Output Frequency FD00)

03H reads 1/multiple parameters (indirect reading ≤ 5, direct reading ≤ 8). Computer sends: 01 03 FD 00 00 01 B5 A6; Inverter Return: 01 03 02 17 70 B6 50

06H single write data write 1 parameter write FA01=1770H (60Hz): 01 06 FA 01 17 70 E6 C6

10H block write data write multiple parameters (such as [F870]/[F871]) write FA00+C400 (forward rotation)+ FA01=1770H:01 10 18 70 00 02 04 C4 00 17 70 6D AF

Write and read data simultaneously at 17H+read and write FA00+read FD01/FD00:01 17 18 75 00 02 18 70 00 02 04 C4 00 17 70 XX XX

2BH reads model information, manufacturer/model/version, VFAS3-2037P: 01 2B 0E 01 00 70 77; Return to "TOSHIBA" "VFAS3-2037P" "0100"

CRC calculation: 16 bits, initial value FFFFH, polynomial A001H, with the lower bits first (e.g. the CRC for command 01 03 FD 00 00 01 is B5 A6).


Core function: Communication between frequency converters

Implementing master-slave control of multiple frequency converters through RS485 (without PLC), only supporting Toshiba protocol, core parameters [F806]/[F826] (master-slave mode).

1. Master slave setting

Role parameter setting (F806/F826) function

Main station 3 (sends frequency command)/4 (sends output frequency)/5 (sends torque command)/6 (sends output torque) continuously sends S command (normal)/s command (fault), no response

Receive master station commands from station 0 (0Hz in case of failure)/1 (continue operation in case of failure)/2 (emergency stop in case of failure), but do not respond

2. Speed proportional control

The sub station frequency is proportionally converted by the main station command and supports two-point correction ([F810] - [F814]):

No correction: Slave frequency (Hz)=(Master command (%) x Slave maximum frequency)/10000 (1%=100).

Two point correction: Slave station frequency=[(Point 2 frequency - Point 1 frequency)/(Point 2 command - Point 1 command)] × (Master station command - Point 1 command)+Point 1 frequency.

Example: The master station sends 50% (5000), the maximum frequency of the slave station is 90Hz, and without calibration, the slave station frequency=(5000 × 9000)/10000=45Hz.


Communication related parameters

The core parameters need to be set through the panel or communication, and some require power-off reset to take effect. The key parameters are shown in the table below:

Parameter number, parameter name, function adjustment range, default value, effective method

F800/F820 RS485 baud rate set communication rate 0=9600bps, 1=19200bps, 2=38400bps 1 power-off reset

F801/F821 RS485 verification setting verification method 0=none, 1=even, 2=odd 1 power-off reset

F802 frequency converter number set unique address 0-247 0 immediately

F803/F823 communication timeout setting timeout detection duration 0.0 (disabled), 0.1-100.0s 0.0 immediately

F804/F824 timeout operation timeout action 1=continue running, 4=trip immediately, 6=trip immediately after deceleration, 1=trip immediately

F807/F827 protocol selection: Toshiba/MODBUS 0=Toshiba, 1=MODBUS 0 power off reset

F829 RS485 (2) wiring 2-wire/4-wire switch 0=2 wire, 1=4 wire 0 immediately


Troubleshooting and Appendix

1. Common faults and solutions

Possible causes and solutions for the fault phenomenon

Communication unresponsive 1. Baud rate/checksum/protocol mismatch; 2. Wiring error; 3. Mismatch of frequency converter numbers. 1. Unified parameters (such as 19200bps+even parity+Toshiba protocol); 2. Check the A+/B -/SG wiring and connect the resistor; 3. Confirm that INV-NO is consistent with [F802]

Err5 tripped (communication timeout) 1. Cable disconnected; 2. The timeout period is too short; 3. The main station has no data transmission. 1. Check the cable; 2. Increase [F803]/[F823] (if set to 1.0s); 3. Confirm that the main station is sending commands normally

Write parameter error (N0000): 1. During operation, write prohibited parameters (such as maximum frequency); 2. Parameter locking ([F700]=2/4) 1. Write after shutdown; 2. Set [F700]=0 (unlock)

2. Appendix Information

Appendix 1 (Data Code Table): Provide JIS ASCII codes such as "41H=A" and "30H=0" for ASCII mode data parsing.

Appendix 2 (Response Time): The calculation method is "Data communication time (bytes x bits/baud rate)+frequency converter processing time (maximum 10ms)", for example: 19200bps, 8 bytes, 11 bits, communication time=(8 x 11)/19200 ≈ 4.6ms, total response time ≈ 14.6ms.

Appendix 3 (Model Table): Corresponding to the [FB05] parameter, for example, the FB05 value of VFAS3-2037P (200V/3.7kW) is 9 (decimal).

Key issues

Question 1: What hardware specifications must be followed when wiring RS485 communication for VF-AS3 frequency converter? What are the consequences of ignoring these regulations?

Answer: The hardware specifications that must be followed are as follows:

Cable selection: Use shielded twisted pair cables with a conductor cross-sectional area of ≥ AWG24 (0.22mm ²) and a characteristic impedance of 100-120 Ω. Avoid parallel connection with the main circuit cable (spacing ≥ 20cm) to prevent interference.

Resistance connection:

The devices at both ends of the bus must be connected to a 120 Ω/1/2W terminal resistor (to suppress signal reflection);

All nodes must be connected to 510 Ω/1/2W pull-up and pull-down resistors (to enhance signal driving capability).

Pin and wiring mode:

Connector1 only supports 2-wire system and must be connected to 4-pin (A+), 5-pin (B -), and 8-pin (SG). Connections to pins 1/2/6/7 are prohibited;

Connector2 supports 2-wire/4-wire (F829) switching): The 2-wire system is the same as Connector1, and the 4-wire system requires an additional 3-pin (TXA) and 6-pin (TXB) connection, with separate twisted transmission/reception wires.

Interface restrictions: Ethernet connection to RS485 interface is prohibited, and live plugging and unplugging of communication lines is also prohibited.

The consequences of ignoring norms:

No terminal resistance can cause signal reflection, resulting in communication packet loss or data errors;

No pull-down resistor can cause communication interruption in weak signal environments;

Cables that do not meet the requirements or are parallel to the main circuit can introduce electromagnetic interference, resulting in frequency/current monitoring deviations;

Live plugging or misconnection of Ethernet can damage the RS485 interface circuit and cause equipment failure.


Question 2: How to read the output frequency (communication signal FD00) of VF-AS3 frequency converter through the 03H instruction under the MODBUS-RTU protocol? It is necessary to clarify the instruction format, CRC calculation process, and response parsing.

Answer: Taking "inverter number 1 (01H), baud rate 19200bps, even parity" as an example, the steps are as follows:

1. Instruction format (computer → frequency converter)

The MODBUS-RTU read instruction (03H) is fixed at 8 bytes and follows the following format:

Example value of byte position content description (Hex)

Inverter number 0-247, 0 is broadcast (no response) 01

2 instruction code reading data fixed as 03H 03

The output frequency communication signal of the 3-4 channel signal (high bit → low bit) is FD00H FD 00

5-6 word count (high position → low position) Read 1 parameter fixed as 0001H 00 01

7-8 CRC16 (low bit → high bit) Calculate B5 A6 according to polynomial A001H

Final instruction: 01 03 FD 00 00 01 B5 A6.  

2. CRC16 calculation process (taking the first 6 bytes of the instruction "01 03 FD 00 00 01" as an example)

Initial value: FFFFH;

XOR byte by byte:

FFFF XOR 01H = FFFEH;

FFFEH XOR 03H = FFFDH;

FFFDH XOR FD H = FF00H;

FF00H XOR 00H = FF00H;

FF00H XOR 00H = FF00H;

FF00H XOR 01H = FEFFH;

Left shift 8 times per byte, XOR A001H when encountering the lowest bit 1, and the final calculation result is B5A6H (low bit B5H comes first, high bit A6H comes back).

3. Response analysis (frequency converter → computer)

The normal response is 7 bytes, in the following format:

Byte position content description example value (Hex) parsing result

1. The frequency converter number is consistent with the instruction 01-

The instruction code is consistent with the instruction (03H) 03-

3 data bytes 1 parameter=2 bytes 02-

4-5 output frequency (high bit → low bit) unit 0.01Hz 17 70 1770H=6000 → 60.00Hz

CRC B6 50 for 6-7 CRC16 response data-

If the output frequency is 60Hz and the response is 01 03 02 17 70 B6 50, the actual frequency obtained by analysis is 6000 × 0.01=60.00Hz.


Question 3: What are the key requirements for parameter settings between the master and slave stations in VF-AS3 frequency converter communication (master-slave mode)? How to achieve a proportional change in the frequency of the slave station following the master station (for example: the master station sends a 50% command, and the slave station outputs 45Hz)?

Answer:

1. Key parameter settings for master and slave stations (both require Toshiba protocol, [F807]/[F827]=0)

Example of Key Parameter Setting Requirements for Roles (45Hz Output from the Slave Station)

The main station [F806]/[F826] is set to 3 (frequency command)/4 (output frequency), with only one main station [F826]=3 (frequency command)

The master station [F800]/[F820] is consistent with the slave station, with a default of 19200bps 1 (19200bps)

The master station [F801]/[F821] is consistent with the slave station, and defaults to even parity 1 (even parity)

Set station [F806]/[F826] to 0 (fault 0Hz)/1 (fault continues)/2 (fault emergency stop) [F826]=0

Set from station [F823] (timeout) to 0.1-100s (loss of control due to disconnection of defense cable) and 1.0s

Set 21 (Connector1)/22 (Connector2) 22 (using Connector2) from the FMOd (frequency command source)

Set the target maximum frequency from the slave station [FH] (maximum frequency), for example, 90Hz 90.0Hz (9000 × 0.01Hz)

2. Proportional control implementation (without two-point correction, [F810]=0)

Main station instruction calculation: The main station frequency instruction is in units of "%" (1%=100). If a slave station needs to output 45Hz, the main station instruction=(slave station target frequency x 10000)/slave station maximum frequency=(45 x 10000)/90=5000 (i.e. 50%).

Main station sends command: The main station sends S command (53H) through Binary mode, in the format of/INV-NO 53H signal DATA SUM, where:

INV-NO: FFH (broadcast, all received from slave stations);

Communication number: FA05 (Connector2 frequency command);

DATA:5000(50%,Hex=1388H);

Instruction example: 2F FF 53 FA 05 13 88 XX (XX is the SUM value).

Slave frequency conversion: After receiving instructions from the slave station, calculate the frequency according to the formula: Slave frequency (Hz)=(Master station instruction (%) x Slave station maximum frequency)/10000=(5000 × 9000)/10000=4500 → 45.00Hz, achieving proportional following.

  • ABB PFSA240 Roll DC Supply Unit 3BSE073476R1 Industrial Stressometer Power Supply Module for Rolling Mill Systems
  • ABB PFSA107-Z42 DTU Stressometer Digital Transmission Unit High Precision Strip Tension Measurement Module
  • GE AT868-2-1-1 Ultrasonic Flow Transmitter AquaTrans AT868 Dual Channel Industrial Flow Meter
  • ABB SCC-C 23070-0-10232110 Industrial Control Module Automation System Communication Controller
  • APPLIED MATERIALS 0041-96185 - Heater Assy with 0150-45776 0190-60492 AMAT
  • APPLIED MATERIALS 0021-33426 - SHIELD INNER SINGLE 300MM NO COIL AMAT
  • APPLIED MATERIALS 0140-01905 - HARNESS ASSY DUAL IHC PRESS CONT ADAPTER 16798 AMAT
  • APPLIED MATERIALS 0051-01848 - LINE VAC EXHAUST CH Y LEAK CHECK PORT EPI AMAT
  • APPLIED MATERIALS 0010-02863 - P5000 150mm Teos Susceptor AMAT
  • APPLIED MATERIALS 0010-14056 - ASSY INJECT NOZZLE STANDARD AMAT
  • APPLIED MATERIALS 0020-34694 - LINER GDP R2 OXIDEGECO AMAT
  • APPLIED MATERIALS 0195-07416 - SYCAMORE-X CMP POLISHER I/O ASSEMBLY AMAT
  • APPLIED MATERIALS 0200-09036 - WAFER LIFT PIN AMAT
  • APPLIED MATERIALS 0021-39090 - FLANGE 10" CONFLAT ADAPTOR AMAT
  • APPLIED MATERIALS 0100-99011 - GAS INTERLOCK AMAT
  • APPLIED MATERIALS 0100-11002 - digital I/O card AMAT
  • APPLIED MATERIALS 0190-40000 - PNEUMATIC MANIFOLD CHAMBER 32903 AMAT
  • APPLIED MATERIALS 0021-39792 - PERF PLATE OX. 200 MM TEOS 21896 AMAT
  • APPLIED MATERIALS 0040-04896 - BELL JAR QUARTZ Q-KOTE 200MM AMAT
  • APPLIED MATERIALS 0020-20653 - BASE HEATER AMAT
  • APPLIED MATERIALS 0190-75057 - Lift Cylinder Assy AMAT
  • APPLIED MATERIALS 0010-70345 - Applied Materials 0042-01927
  • APPLIED MATERIALS 0100-91024 - PWBA PRE-ACCEL VENDOR I/F PCB 9500 IMPLANT AMAT
  • APPLIED MATERIALS 0041-56144 - HEATER PEDESTAL ASSEMBLY ENP FCVD EDGE AMAT
  • APPLIED MATERIALS 0090-00836 - SOURCE MOTOR ASSY 0040-24074 GFB5G10 FBLM5120W AMAT
  • MKS 0190-63631 - MASS FLOW VERIFIER MFVA-33168 AMAT
  • APPLIED MATERIALS 0100-35070 - ASSY PCB RF GENERATOR INTERFACE AMAT
  • APPLIED MATERIALS 0010-32221 - ASSEMBLY ROUGH THROTTLE VALVE DRIVE 300MM AMAT
  • SANYO DENKI 0190-14713 - P30B06040HXS8RM AC SERVO MOTOR BL SUPER AMAT
  • APPLIED MATERIALS 0190-14224 - FLEX DIST PANEL AMAT
  • APPLIED MATERIALS 0190-23897 - SPECIFICATION EXMP SYNCNET STAND ALON 14535 AMAT
  • APPLIED MATERIALS 0010-04542 - HEATER ASSY 200MM FC WXZPLUS OSCR 15607 AMAT
  • APPLIED MATERIALS 0190-51414 - AC SERVO DRIVER SGDV-OCA05AY890AA AMAT
  • APPLIED MATERIALS 0020-31747 - P5000 LOADLOCK LID WAFER TXR CHMBR 0020-32930 12573 AMAT
  • APPLIED MATERIALS 0620-01727 - CABLE ASSY SIGNAL RBN 50PIN DSUB EMI RES 17781 AMAT
  • APPLIED MATERIALS 0190-A9510 - IP POWER SUPPLY 33361 AMAT
  • APPLIED MATERIALS T1101-05-000-30 - CRYO TIGER COMPRESSOR AMAT
  • APPLIED MATERIALS 0040-13338 - LINK 1 UPPER 7.2 DEGREE OFFSET CR 300MM 38177 AMAT
  • APPLIED MATERIALS 0190-06926 - Cable SQS R/A TO SQS R/A #2 AMAT
  • APPLIED MATERIALS 0200-00705 - EDGE RING THIN 200MM AMAT
  • APPLIED MATERIALS 0190-01399 - INLINE O3 SNSR ULTRA FULL FLOW HI-CON 6627 AMAT
  • APPLIED MATERIALS 0190-21054 - RF MATCH CABLE ASSEMBLY PRECLEAN 2 AMAT
  • APPLIED MATERIALS 0041-12156 - REFLECTOR PLATE INJECT 300MM RADIANCE PLUS 29763 AMAT
  • MKS 0100-03680 - PCB CHMBR DIST 0090-09483 AS00363-16 35465 AMAT
  • APPLIED MATERIALS E11355460 - Plasma Detector E11355470 Rev.B AMAT
  • APPLIED MATERIALS 0021-33981 - LOWER SHIELD AMAT
  • APPLIED MATERIALS 0100-00583 - GAS PANEL CONTROLLER DIST AMAT
  • APPLIED MATERIALS 0010-54820 - IPC VALVE ASSEMBLY FM 1/2" INTER-PLATEN SPRAY AMAT
  • APPLIED MATERIALS 0020-31747 - P5000 LOADLOCK LID WAFER TXR CHMBR 0020-32930 12573 AMAT
  • APPLIED MATERIALS 0020-40566 - BLANK-OFF POSITION E-F ENP AMAT
  • APPLIED MATERIALS 0021-31023 - Flange Spacer Automatch Single RPS Producer SE AMAT
  • APPLIED MATERIALS 0020-21225 - WEIGHT RING 300MM TITAN PROFILER AMAT
  • APPLIED MATERIALS 0190-A9510 - IP POWER SUPPLY 33361 AMAT
  • APPLIED MATERIALS 0100-90618 - PCB H1 GROUND PDU MOTHER BOARD 0100-90036 AMAT
  • APPLIED MATERIALS 0010-04542 - HEATER ASSY 200MM FC WXZPLUS OSCR 15607 AMAT
  • APPLIED MATERIALS 0020-31658 - CLAMP VESPEL OX-MLR-NIT 200MM AMAT
  • APPLIED MATERIALS 0021-09974 - WINDOW SAPPHIRE PUMPING PLATE AMAT
  • APPLIED MATERIALS 0051-01849 - LINE VAC EXHAUST ELBOW CH Y FAC TRAY EPI 30 AMAT
  • APPLIED MATERIALS 0010-29842 - 300mm DBR High Temp Belt Wrist Titanium AMAT
  • APPLIED MATERIALS 1410-01166 - Heating Jacket AMAT
  • APPLIED MATERIALS 0620-01727 - CABLE ASSY SIGNAL RBN 50PIN DSUB EMI RES 17781 AMAT
  • APPLIED MATERIALS 0010-70345 - Applied Materials 0042-01927
  • APPLIED MATERIALS 0090-00836 - SOURCE MOTOR ASSY 0040-24074 GFB5G10 FBLM5120W AMAT
  • APPLIED MATERIALS 0190-46837 - INFRARED THERMOMETER COMM BOX RAYMI3COMM 30009 AMAT
  • APPLIED MATERIALS 0020-31886 - FLANGE INSULATION UNIBODY .400 THK AMAT
  • APPLIED MATERIALS 0010-05920 - CONTROLLER CCM PROD ETCH CS-PM CARD CAGE AMAT
  • APPLIED MATERIALS 0242-30292 - KIT 20 SCCM MFC W/HRDWR UNIBODY 6449 AMAT
  • APPLIED MATERIALS 0040-41061 - JIG FOUR PT LEVELING TOOL TXZ 300MM AMAT
  • APPLIED MATERIALS 0020-30287 - ADAPTER RING PUMPING PLATE 200MM COMMO AMAT
  • APPLIED MATERIALS 0041-12156 - REFLECTOR PLATE INJECT 300MM RADIANCE PLUS 29763 AMAT
  • APPLIED MATERIALS 0010-37866W - ASSY INT ISRM MODULE FULL SCAN SMG AMAT
  • APPLIED MATERIALS 0090-08137 - 300MM TXZ DLI HEATER CONTROLLER MODULE AMAT
  • APPLIED MATERIALS 0040-20006 - ARM WELDMENT SOURCE STD 8464 AMAT
  • APPLIED MATERIALS 0090-07392 - Dual RF filter AMAT
  • APPLIED MATERIALS 0190-06926 - Cable SQS R/A TO SQS R/A #2 AMAT
  • APPLIED MATERIALS 0020-70279 - LIFTER 150MM WAFER ORIENTER P5000 AMAT
  • APPLIED MATERIALS 0190-35652 - SERIPLEX MUX I/O PCB AMAT
  • APPLIED MATERIALS 0100-11002 - digital I/O card AMAT
  • APPLIED MATERIALS E11355460 - Plasma Detector E11355470 Rev.B AMAT
  • APPLIED MATERIALS 0010-19188 - ASSY COOLDOWN LIFT 34703 AMAT
  • APPLIED MATERIALS 0100-00975 - PCB STEPPER CONTROLLER 2 8099 AMAT
  • APPLIED MATERIALS 0190-16236 - MOTOR ENCODER ASSY ROBOT WRIST MIRRA CMP AMAT
  • APPLIED MATERIALS 0040-48671 - LEFT GUIDE 300MM L-DOOR 37961 AMAT
  • MKS 0100-03680 - PCB CHMBR DIST 0090-09483 AS00363-16 35465 AMAT
  • APPLIED MATERIALS 0190-01399 - INLINE O3 SNSR ULTRA FULL FLOW HI-CON 6627 AMAT
  • APPLIED MATERIALS 8330 - Pair Of Side viewport Panels AMAT
  • APPLIED MATERIALS 0190-75057 - Lift Cylinder Assy AMAT
  • APPLIED MATERIALS 0100-02016 - PCB ASSY ANALOG SYNC DETECT 904-125N AMAT
  • Abaco Systems 0090-08517 - VMICPCI-7326 PCB 38085 AMAT
  • APPLIED MATERIALS 0100-20069 - ASSY WAFER ORIENTER BOARD 0100-02797 AMAT
  • ELEKTRO-AUTOMATIK EA-PS 9036-070 - S01 POWER SUPPLY 625-795365 AMAT
  • APPLIED MATERIALS 3310-00139 - CAPACITANCE PIRANI GAUGE C-SEAL MOUNT 15-PIN AMAT
  • APPLIED MATERIALS 0010-00510 - ASSY BEARING STD 36806 AMAT
  • APPLIED MATERIALS 0041-13895 - FACEPLATE 26MIL CENTERHOLE RF CAP 300MM SACVD 13964 AMAT
  • APPLIED MATERIALS T1101-05-000-30 - CRYO TIGER COMPRESSOR AMAT
  • APPLIED MATERIALS 0050-10076 - WELDMENT DUAL HE MANF SACVD 20243 AMAT
  • MKS 0190-48179 - AS01294-05237-030 Hardened DeviceNet I/O Block AMAT
  • APPLIED MATERIALS 0240-75102 - 8" Transfer Blade 200mm End Effector AMAT
  • APPLIED MATERIALS 0110-90770 - Index Control PCB AMAT
  • APPLIED MATERIALS 0090-91209 - SOURCE SUPPRESSION CLAMPING BOX AMAT
  • APPLIED MATERIALS 0200-01427 - ISOLATOR CERAMIC CVD LOW K 300MM PROD AMAT
  • APPLIED MATERIALS 0021-03637 - FACEPLATE SILANE PRODUCER 200MM AMAT
  • APPLIED MATERIALS 0010-09837 - Wafer Lift Tungsten Precision 5000 AMAT
  • APPLIED MATERIALS 0101-57014 - PCB DEFLECTION-AMPLIFIER BOARD D-AMP 50-06 26296 AMAT
  • APPLIED MATERIALS 0190-36715 - PCB GP IO DISTRIBUTION AMAT
  • APPLIED MATERIALS 0660-00078 - PCB ASSY DNET ANALOG I/O CDN396 DIP-506-068 13392 AMAT
  • APPLIED MATERIALS 0190-B4670 - FIBER HARNESS DVD2-SBBI AMAT
  • APPLIED MATERIALS 1080-02356 - ACCELNET SINGLE AXIS SERVO DRIVE 800-2122 AMAT
  • APPLIED MATERIALS 0040-02937 - WATER MANIFOLD TXZ CIP 200 & 300MM AMAT
  • APPLIED MATERIALS 0040-08944 - LID ANNEAL ECP 200MM AMAT
  • SMC INOI-7134-111 - 4-PORT DEVICENET UPA MODULE Pressure Control AMAT
  • SMC INOI-7134-21 - 4-PORT DEVICENET UPA MODULE Pressure Control AMAT
  • APPLIED MATERIALS 0100-40024 - ASSY WPCBA LOADLOCK INTERCONNECT BOARD AMAT
  • APPLIED MATERIALS 0660-01635 - Chamber P2 Board A AMAT
  • APPLIED MATERIALS 0041-31945 - DOOR ENP ALUM SPD SLIT VALVE VITON LLK 3 AMAT
  • APPLIED MATERIALS 0040-48671 - LEFT GUIDE 300MM L-DOOR 37961 AMAT
  • APPLIED MATERIALS 0051-01849 - LINE VAC EXHAUST ELBOW CH Y FAC TRAY EPI 30 AMAT
  • APPLIED MATERIALS 0040-81661 - CATHODE FACILITY PLATE 35320 AMAT
  • APPLIED MATERIALS 0040-20006 - ARM WELDMENT SOURCE STD 8464 AMAT
  • APPLIED MATERIALS 0110-90770 - Index Control PCB AMAT
  • APPLIED MATERIALS 8330 - Pair Of Side viewport Panels AMAT
  • APPLIED MATERIALS 0040-81155 - LINER LOWER AMAT
  • APPLIED MATERIALS 0100-90618 - PCB H1 GROUND PDU MOTHER BOARD 0100-90036 AMAT
  • APPLIED MATERIALS 0040-47677 - FACEPLATE SIN XG DXZ DCVD AMAT
  • APPLIED MATERIALS 0020-31658 - CLAMP VESPEL OX-MLR-NIT 200MM AMAT
  • CTI-CRYOGENICS 0190-54040 - ON-BOARD IS CONTROLLER 34633 AMAT
  • APPLIED MATERIALS 0020-21665 - SHIELD AL/TI 8 INCH WAFER AMAT
  • APPLIED MATERIALS 0090-10397 - RF FILTER BOX AMAT