+086-15305925923

K-WANG

Service expert in industrial control field!
NameDescriptionContent
Adequate Inventory, Timely Service
pursuit of excellence 
Ship control system
Equipment control system
Power monitoring system
Current position:
新闻动态
newS
   
Brand

EATON KD, HKD, KDC, CKD, CHKD K-frame molded case circuit breakers

From: | Author:Wang | Time :2026-03-11 | 6 visit: | Share:

EATON KD, HKD, KDC, CKD, CHKD K-frame molded case circuit breakers

Product Basic Core Information

Applicable models and configurations: The circuit breaker models are KD, HKD, KDC, CKD, CHKD, all of which are K-frame Series C, compatible with Digitrip OPTIM trip units, and support Powernet communication and/or regional interlocking functions; The OPTIM 750/1050 model is additionally equipped with auxiliary switches, alarm/lock switches, and other internal accessories need to be factory installed.

Rated and Application: Maximum rated voltage of 600 VAC, only applicable to AC scenarios; The maximum continuous current of the trip unit is three specifications: 125A, 250A, and 400A.

Certification standard: Complies with the US UL 489 standard and meets the (P1) requirements of international IEC 157-1.

100% rated operating model: CKD and CHKD models can operate continuously at 100% frame rating if they meet the following conditions: using 90 ℃ insulated wires and AL9CU terminals, installed in a 24 "high x 15" wide x 6 "deep enclosure, which does not require additional ventilation.

Supporting materials: Selection data, trip unit operation manual, wiring diagram and other materials (such as numbers 29-120K, 29C890, etc.) can be obtained from Eaton.


Full process installation specifications

The installation process includes pre inspection → accessory installation → fixation → wiring → protection → parameter setting. All steps must be carried out under power-off, and the key requirements are as follows:

Pre-check

Check the circuit breaker nameplate and system requirements, and confirm that the equipment is not damaged during transportation;

Before removing the circuit breaker cover, it must be placed in the trip or OFF position.

Installation of internal accessories

The rated plug and internal accessories need to be installed before fixing the circuit breaker, refer to the separate instructions for the accessories;

When reinstalling the cover plate, the threaded forming screws should be aligned with the original threads to avoid thread damage that may cause the cover plate to be loosely fixed.

Terminal installation

The wire terminal is fixed with a 7/32 inch socket wrench, with a torque of 6-8 lb. - ft. (8-11 N.m.);

When connecting aluminum wires, a suitable joint compound must be applied to prevent the terminals from overheating and causing accidental tripping or equipment damage.

Circuit breaker fixing

Surface installation should be drilled according to Figure 2-2, while panel installation only requires support holes at the load end. Concealed cover installation should be cut according to the dimensions shown in Figure 2-3;

Tighten the installation screws and washers firmly and not exceeding 28 lb. in. (3 N.m.);

The side of the circuit breaker is labeled with a wiring diagram of the accessories. If it is not visible after installation, it needs to be recorded in advance.

Wiring specifications

The control power supply is 24VDC, the trip unit load is 45mA, and the positive and negative poles must be connected to the corresponding terminals (No. 6+24V/No. 5 NEG). Reversing the connection will damage the electronic protection function;

The regional interlocking function requires the removal of the factory jumper between terminals 2 and 3. If it is not removed, it will be in a self interlocking state;

The four wire system requires the installation of a neutral current sensor at the neutral pole, arranged according to the dimensions shown in Figure 2-6.

Rated plug selection

The release unit needs to be matched with the corresponding rated plug, with specifications as shown in the table below:

The rated current of the trip unit can be selected according to the rated plug specifications

125A 63A、70A、90A、100A、110A、125A

250A 125A、150A、160A、175A、200A、225A、250A

400A 200A、225A、250A、300A、350A、400A

Terminal torque and protection

The torque of the wire/load terminal is determined according to the model, and the core specifications are shown in the table below:

Terminal model material applicable wire torque value (lb. in./N.m.)

TA300K/T300K Aluminum/Copper 3-350 AWG 275/31

TA350K/T350K Aluminum/Copper 250-500 AWG 375/42

TA402K Aluminum 500-750 AWG 550/62

Ladder type terminals (TA400K/TA401K, etc.) must be equipped with matching terminal shields and warning labels must be affixed to the upper part of the circuit breaker cover plate;

When wiring, it is necessary to maintain the original factory electrical clearance and creepage distance to prevent high voltage hazards.

Parameter Settings

Insert the Digitrip OPTIMZER handheld programmer into the programming port, set the INCOM address and trip unit current parameters;

Parameters can also be set through the circuit breaker interface module or IMPACC Series III software.

Manual operation method

The manual operation of the circuit breaker is achieved through the operation handle and PUSH-TO-TRIP button, without additional electric operation requirements. Key rules:

operating handle

There are three positions: ON, OFF, and release. The cover plate is engraved with ON/OFF, and the handle color bar is marked with red=ON, green=OFF (reset), and white=release;

Reset after tripping: simply turn the handle to the extreme OFF position. The reset button is only used to reset the fault indicator light and does not affect the mechanical reset of the circuit breaker.

PUSH-TO-TRIP button

Used to trigger the trip function and regularly test the flexibility of the operating mechanism;

Use a small screwdriver to operate, designed for mechanical triggering.

Safety principle: After the circuit breaker is tripped, it is strictly prohibited to close it again until the fault is identified and eliminated.


Inspection and on-site testing

This series of circuit breakers is designed for maintenance free use and only requires limited regular inspections and testing. All operations must be performed with power off. The core requirements are:

Daily inspection (4-1 to 4-7)

Cleaning: Use a lint free dry cloth/brush/vacuum cleaner to remove dust, do not blow debris into the interior of the circuit breaker, and investigate the source of pollution;

Mechanical testing: repeatedly turn the handle to ON/OFF to ensure that the mechanism is not stuck. If it is stuck, replace the circuit breaker;

Trip test: Press PUSH-TO-TRIP in the ON position and repeatedly trip reset close. If the reset fails, replace the circuit breaker;

Component inspection: Check the cover plate, handle, and base for cracks, paint peeling, and discoloration. If they are severely damaged, replace them;

Terminal inspection: Check that the terminals are not loose or overheated (discoloration/insulation melting/arc erosion). If there are no problems, do not tighten them randomly. If there is overheating, clean/replace the terminals and restore them to their original factory condition;

Installation component inspection: tighten loose installation screws;

Environmental inspection: Check for chemical corrosion, personal/fire hazards in the installation area.

General on-site testing

Execute according to NEMA standards and test the functionality of the Digitrip OPTIM trip unit using the OPTIMIZER handheld programmer.

Grounding fault trip unit test (mandatory requirement)

Regulatory requirements: According to NEC 230-95-C, the grounding fault protection system must undergo performance testing when newly installed, and written test records must be retained in accordance with UL 1053 requirements for inspection by inspection agencies;

Test power supply: Use a 0-24V low-voltage, high current AC source, and do not only test through neutral sensors (the trip unit is powered by phase current, not neutral current);

Trip test: Apply a current of 125% of the ground fault setting value to any phase, and the circuit breaker should trip within 1 second. The alarm indicator light (if any) should be activated, and the three phases should be tested separately;

Non trip verification:

Four wire system (with neutral sensor): current flows in from one phase, neutral sensor flows out, circuit breaker does not trip, and three phases are tested separately;

Three wire system (without neutral sensor): Current flows between any two phases without tripping the circuit breaker, and all phase combinations are tested separately;

Attention: On site testing is only for functional verification and cannot be used for on-site calibration. Temporary wiring for testing must be restored to its original state before power can be transmitted.


Safety Warning and Disclaimer

Core safety requirements: All installation, maintenance, and testing operations must be powered off and verified to have no voltage to avoid high voltage causing death/serious injury/property damage;

Material protection: Do not use corrosive commercial cleaning agents to prevent damage to nameplates and molded parts;

Nuclear application reminder: This instruction applies to general commercial scenarios, and additional instructions for nuclear facility safety related applications need to be obtained from Eaton;

Disclaimer: Eaton shall not be liable for any misuse or installation of the product. This statement is not exhaustive and does not provide any express or implied warranties. Eaton shall not be liable for any special, indirect, or consequential damages.

  • MOOG 76-264 - Servo Valve
  • MOOG 72-101 SER.1907R - Servo Valve
  • MOOG B52576-1 - Controls Valve Part
  • MOOG CN1000 - Servo Controller
  • MOOG CM-65-105-G-A04 - Servo Controller Evaluation
  • MOOG WSH53P32C108CS - Clamp Proportional Valve
  • MOOG ZFDRP06A4K0ASA - Check Valve
  • MOOG CCE40B64WX06A2 - Check Valve
  • MOOG CCE32B61WX06C3 - Check Valve
  • MOOG CCE25B62DAX - Check Valve
  • MOOG CCE25B61DX - Check Valve
  • MOOG CCE50C11WX06 - Hydraulic Proportional Cartridge Solenoid Valve
  • MOOG CCE50A6RH1X10 - Hydraulic Cartridge Valve HPN703404
  • MOOG CCE25B62DRX - Cartridge Valve XGB10016-000-01
  • MOOG Cce16 B6rma0v06/A12 - Throttle Valve Xeb15892-001-01
  • MOOG CB64541-001 - Crimp Connector 11+PE 24V
  • MOOG CB64539-001 - Crimp Connector 11+PE
  • MOOG RSE25BU6T2WX - Cartridge Valve HPN2946887
  • MOOG XPB10004-000-01 - Cartridge Proportional Valve
  • MOOG XEB11483-000-01 - Cartridge Proportional Valve
  • MOOG XCB10235-000-00 - Cartridge Valve
  • MOOG C43285-203 Rev. D - Control Board and Coil
  • MOOG BS23-28FC-04CHP - Servo Motor
  • MOOG G631-3005A - Servo Valve
  • MOOG BN34-35CD-04CHEP - Servo Motor
  • MOOG BN34-25CD-01LH - Servo Motor
  • MOOG BN23-28EF-01CHG - Servo Motor
  • MOOG BI160D - Servo Drive Evaluation
  • MOOG B97012-024 - Hydraulic Servo Valve D-71034
  • MOOG B80HXAGGNSF2 - Servo Valve Component
  • MOOG B64569-2V - 10 Micron Hydraulic Filter Element
  • MOOG B48333-801 - Hydraulic Component
  • MOOG B35829-008A - Linear Actuator
  • MOOG API090E - Servo Evaluation Component
  • MOOG SM23205D-DN-F1 - Animatics Smart Motor Servo
  • MOOG AC6023-24C - Servo Valve Component
  • MOOG AC4598-6 - Servo Valve Component
  • MOOG A72068-1 - Hydraulic Component
  • MOOG A32179-1 - Hydraulic Servo Valve
  • MOOG A11592 - Hydraulic Servo Valve D635-606C
  • MOOG A076-795 - ServoCon Valve A076795
  • MOOG A076-506 - Servo Valve A076506
  • MOOG A076-401R - Hydraulic Servo Valve
  • MOOG A076-103HRI-10 539 - Servo Valve
  • MOOG A076-102 - Servo Valve
  • MOOG A076-101A - Hydraulic Servo Valve
  • MOOG A05891-1 - Hydraulic Component
  • MOOG 963.364.8011A - Hydraulic Servo Valve
  • MOOG 963.364.8011 - Hydraulic Servo Valve
  • MOOG 897012-024 - Hydraulic Servo Valve
  • MOOG 7WEFS42P06C88B - Hydraulic Proportional Servo Valve
  • MOOG 79.212 - Servo Valve
  • MOOG 79.211 - Servo Valve
  • MOOG 78.5113 - Servo Valve
  • MOOG 78 Series - Servo Valve Series
  • MOOG 771F232 - Hydraulic Servo Valve
  • MOOG 771-117 - Hydraulic Servo Valve
  • MOOG 770-147E - Valve Assembly G2761AM002
  • MOOG 77-703 - Servo Valve
  • MOOG 77-553 - Servo Valve
  • MOOG 77-159 - Servo Valve
  • MOOG 77-123 - Servo Valve
  • MOOG 761-5077B - Electro-Hydraulic Servo Valve
  • MOOG 761-4088B5 - Hydraulic Servo Valve
  • MOOG 760N1181B - Electro-Hydraulic Servo Valve 3000psi
  • MOOG 760N1087A - Servo Valve
  • MOOG 760N1085A - Servo Valve
  • MOOG 760K645B - Electro Hydraulic Servo Valve
  • MOOG 760C461A - Servo Valve
  • MOOG 760C262A - Servo Valve MOD 252.23C-01
  • MOOG 760A509A - Servo Valve
  • MOOG 760A508A - Servo Valve
  • MOOG 760A191A M3741851 - Flow Control Hydraulic Servo Valve
  • MOOG 760-851A - Servo Hydraulic Valve
  • MOOG 760-795A - Attica Servo Valve
  • MOOG 760-748A - Directional Control Valve
  • MOOG 760-508A - Servo Valve
  • MOOG 760-101 - Servo Valve
  • MOOG 76-263C - Hydraulic Valve
  • MOOG 76-185 M2021851 - Flow Control Hydraulic Servo Valve
  • MOOG 76-100 - Hydraulic Servo Valve
  • MOOG 74937-1 - Hydraulic Control Valve
  • MOOG 744F007 - Servo Valve 2019 Model
  • MOOG 744F006 - Servo Valve
  • MOOG 744 Series - Servo Valve Evaluation
  • MOOG 743-003D - Servo Valve
  • MOOG 743 Series - Servo Valve Evaluation
  • MOOG 730Y218-H P5 - Servo Valve
  • MOOG 73-797 - Hydraulic Servo Valve
  • MOOG 73-744 - Hydraulic Servo Valve
  • MOOG 73-233 - Hydraulic Servo Valve
  • MOOG 73-104 - Hydraulic Servo Valve
  • MOOG 73-103 - Hydraulic Servo Valve
  • MOOG 73-101 - 2 Stage Flow Control Servo Valve
  • MOOG 720B210062554 - Electronic Control Unit
  • MOOG 72-516 - 72 Series Servo Valve
  • MOOG 72-101 - Servo Valve 1906R
  • MOOG 642-515A - Proportional Valve T654R
  • MOOG 641-229B - Proportional Directional Control Valve
  • MOOG 631F172F5 - Hydraulic Servo Valve
  • MOOG 631-3015B - Hydraulic Servo Valve
  • MOOG 631 SERIES - Hydraulic Servo Valve
  • MOOG 630-1283D - Servo Valve S30HOGB4NNL
  • MOOG 62F120 - Hydraulic Servo Valve
  • MOOG 62-321 - Electro-Hydraulic Servo Valve
  • MOOG 62-314A - Hydraulic Servo Valve
  • MOOG 62-134 - Hydraulic Control Valve
  • MOOG 60B401H - Hydraulic Servo Valve
  • MOOG 60B023H - Hydraulic Servo Valve
  • MOOG 60-B021H - Hydraulic Control Valve
  • MOOG 60-297 - Hydraulic Control Valve
  • MOOG 505-50 - Hydraulic Servo Valve 5GPM
  • MOOG Jul-63 - Torque Motor Servo Component
  • MOOG 306A-133B - Power Supply Module
  • MOOG 306-235 - Power Supply Module
  • MOOG 305A-141C - Valve Driver Card
  • MOOG 304-131A - Signal Conditioning Module
  • MOOG 304-121A - Signal Conditioning Module
  • MOOG 218-121 - Hydraulic Servo Valve 15GPM
  • MOOG 211A-630 - Hydraulic Servo Valve 3000PSI
  • MOOG 211A-153 - Hydraulic Servo Valve
  • MOOG XCB 10826-000-00 - 2-Way Active Cartridge Valve
  • MOOG M-CEE25B6RS - 2 Way Cartridge Check Valve
  • MOOG G761-3004B - Servo Valve H38JOGM4VPL
  • MOOG 192R S20F0FM4VBR - Electro-Hydraulic Servo Valve
  • MOOG 164003B00A72 - Servo Controller Module
  • MOOG 164-009E-10-B2-2 - Servo Controller Module
  • MOOG 164-009D-10-B1-2 - Servo Controller Module