K-WANG

+086-15305925923
Service expert in industrial control field!
NameDescriptionContent
Adequate Inventory, Timely Service
pursuit of excellence 
Ship control system
Equipment control system
Power monitoring system
Current position:
新闻动态
newS
   
Brand

EATON KD, HKD, KDC, CKD, CHKD K-frame molded case circuit breakers

From: | Author:Wang | Time :2026-03-11 | 230 visit: | 🔊 Click to read aloud ❚❚ ▶ | Share:

EATON KD, HKD, KDC, CKD, CHKD K-frame molded case circuit breakers

Product Basic Core Information

Applicable models and configurations: The circuit breaker models are KD, HKD, KDC, CKD, CHKD, all of which are K-frame Series C, compatible with Digitrip OPTIM trip units, and support Powernet communication and/or regional interlocking functions; The OPTIM 750/1050 model is additionally equipped with auxiliary switches, alarm/lock switches, and other internal accessories need to be factory installed.

Rated and Application: Maximum rated voltage of 600 VAC, only applicable to AC scenarios; The maximum continuous current of the trip unit is three specifications: 125A, 250A, and 400A.

Certification standard: Complies with the US UL 489 standard and meets the (P1) requirements of international IEC 157-1.

100% rated operating model: CKD and CHKD models can operate continuously at 100% frame rating if they meet the following conditions: using 90 ℃ insulated wires and AL9CU terminals, installed in a 24 "high x 15" wide x 6 "deep enclosure, which does not require additional ventilation.

Supporting materials: Selection data, trip unit operation manual, wiring diagram and other materials (such as numbers 29-120K, 29C890, etc.) can be obtained from Eaton.


Full process installation specifications

The installation process includes pre inspection → accessory installation → fixation → wiring → protection → parameter setting. All steps must be carried out under power-off, and the key requirements are as follows:

Pre-check

Check the circuit breaker nameplate and system requirements, and confirm that the equipment is not damaged during transportation;

Before removing the circuit breaker cover, it must be placed in the trip or OFF position.

Installation of internal accessories

The rated plug and internal accessories need to be installed before fixing the circuit breaker, refer to the separate instructions for the accessories;

When reinstalling the cover plate, the threaded forming screws should be aligned with the original threads to avoid thread damage that may cause the cover plate to be loosely fixed.

Terminal installation

The wire terminal is fixed with a 7/32 inch socket wrench, with a torque of 6-8 lb. - ft. (8-11 N.m.);

When connecting aluminum wires, a suitable joint compound must be applied to prevent the terminals from overheating and causing accidental tripping or equipment damage.

Circuit breaker fixing

Surface installation should be drilled according to Figure 2-2, while panel installation only requires support holes at the load end. Concealed cover installation should be cut according to the dimensions shown in Figure 2-3;

Tighten the installation screws and washers firmly and not exceeding 28 lb. in. (3 N.m.);

The side of the circuit breaker is labeled with a wiring diagram of the accessories. If it is not visible after installation, it needs to be recorded in advance.

Wiring specifications

The control power supply is 24VDC, the trip unit load is 45mA, and the positive and negative poles must be connected to the corresponding terminals (No. 6+24V/No. 5 NEG). Reversing the connection will damage the electronic protection function;

The regional interlocking function requires the removal of the factory jumper between terminals 2 and 3. If it is not removed, it will be in a self interlocking state;

The four wire system requires the installation of a neutral current sensor at the neutral pole, arranged according to the dimensions shown in Figure 2-6.

Rated plug selection

The release unit needs to be matched with the corresponding rated plug, with specifications as shown in the table below:

The rated current of the trip unit can be selected according to the rated plug specifications

125A 63A、70A、90A、100A、110A、125A

250A 125A、150A、160A、175A、200A、225A、250A

400A 200A、225A、250A、300A、350A、400A

Terminal torque and protection

The torque of the wire/load terminal is determined according to the model, and the core specifications are shown in the table below:

Terminal model material applicable wire torque value (lb. in./N.m.)

TA300K/T300K Aluminum/Copper 3-350 AWG 275/31

TA350K/T350K Aluminum/Copper 250-500 AWG 375/42

TA402K Aluminum 500-750 AWG 550/62

Ladder type terminals (TA400K/TA401K, etc.) must be equipped with matching terminal shields and warning labels must be affixed to the upper part of the circuit breaker cover plate;

When wiring, it is necessary to maintain the original factory electrical clearance and creepage distance to prevent high voltage hazards.

Parameter Settings

Insert the Digitrip OPTIMZER handheld programmer into the programming port, set the INCOM address and trip unit current parameters;

Parameters can also be set through the circuit breaker interface module or IMPACC Series III software.

Manual operation method

The manual operation of the circuit breaker is achieved through the operation handle and PUSH-TO-TRIP button, without additional electric operation requirements. Key rules:

operating handle

There are three positions: ON, OFF, and release. The cover plate is engraved with ON/OFF, and the handle color bar is marked with red=ON, green=OFF (reset), and white=release;

Reset after tripping: simply turn the handle to the extreme OFF position. The reset button is only used to reset the fault indicator light and does not affect the mechanical reset of the circuit breaker.

PUSH-TO-TRIP button

Used to trigger the trip function and regularly test the flexibility of the operating mechanism;

Use a small screwdriver to operate, designed for mechanical triggering.

Safety principle: After the circuit breaker is tripped, it is strictly prohibited to close it again until the fault is identified and eliminated.


Inspection and on-site testing

This series of circuit breakers is designed for maintenance free use and only requires limited regular inspections and testing. All operations must be performed with power off. The core requirements are:

Daily inspection (4-1 to 4-7)

Cleaning: Use a lint free dry cloth/brush/vacuum cleaner to remove dust, do not blow debris into the interior of the circuit breaker, and investigate the source of pollution;

Mechanical testing: repeatedly turn the handle to ON/OFF to ensure that the mechanism is not stuck. If it is stuck, replace the circuit breaker;

Trip test: Press PUSH-TO-TRIP in the ON position and repeatedly trip reset close. If the reset fails, replace the circuit breaker;

Component inspection: Check the cover plate, handle, and base for cracks, paint peeling, and discoloration. If they are severely damaged, replace them;

Terminal inspection: Check that the terminals are not loose or overheated (discoloration/insulation melting/arc erosion). If there are no problems, do not tighten them randomly. If there is overheating, clean/replace the terminals and restore them to their original factory condition;

Installation component inspection: tighten loose installation screws;

Environmental inspection: Check for chemical corrosion, personal/fire hazards in the installation area.

General on-site testing

Execute according to NEMA standards and test the functionality of the Digitrip OPTIM trip unit using the OPTIMIZER handheld programmer.

Grounding fault trip unit test (mandatory requirement)

Regulatory requirements: According to NEC 230-95-C, the grounding fault protection system must undergo performance testing when newly installed, and written test records must be retained in accordance with UL 1053 requirements for inspection by inspection agencies;

Test power supply: Use a 0-24V low-voltage, high current AC source, and do not only test through neutral sensors (the trip unit is powered by phase current, not neutral current);

Trip test: Apply a current of 125% of the ground fault setting value to any phase, and the circuit breaker should trip within 1 second. The alarm indicator light (if any) should be activated, and the three phases should be tested separately;

Non trip verification:

Four wire system (with neutral sensor): current flows in from one phase, neutral sensor flows out, circuit breaker does not trip, and three phases are tested separately;

Three wire system (without neutral sensor): Current flows between any two phases without tripping the circuit breaker, and all phase combinations are tested separately;

Attention: On site testing is only for functional verification and cannot be used for on-site calibration. Temporary wiring for testing must be restored to its original state before power can be transmitted.


Safety Warning and Disclaimer

Core safety requirements: All installation, maintenance, and testing operations must be powered off and verified to have no voltage to avoid high voltage causing death/serious injury/property damage;

Material protection: Do not use corrosive commercial cleaning agents to prevent damage to nameplates and molded parts;

Nuclear application reminder: This instruction applies to general commercial scenarios, and additional instructions for nuclear facility safety related applications need to be obtained from Eaton;

Disclaimer: Eaton shall not be liable for any misuse or installation of the product. This statement is not exhaustive and does not provide any express or implied warranties. Eaton shall not be liable for any special, indirect, or consequential damages.

  • Siemens 6SL3244-0SA01-1AA0 - SINAMICS G120 Control Unit
  • DANFOSS 175Z2688 - COATEDE CONTROLUNIT VLT5000
  • SIEMENS 6FM1721-3AA20 - Positioning Module
  • REXORTH VTS0605 PVAR S21 - Drive Module
  • BECKHOFF 2915-0000 - Control Module
  • COOPER EATON CGLine 400 40071347901 - CEAG CG Controller
  • SIEMENS 3UF5031-3AN00-1 - SIMOCODE DP Basic Unit
  • SIGMATEK DNC305 05-011-305 - Drive Controller
  • Multivac MV1 10249768 - Control Module
  • SCHNEIDER ELECTRIC MES114 59646 & 59645 - Circuit Breaker Accessory
  • CAMILLE BAUER CAPAX 44-580-0012 - Transmitter
  • HENGSTLER VT360P LS1/TOK - Encoder
  • BURKERT 8792 - 24V DC IP65 / IP67 Positioner
  • SENSOPART V10-OB-A1-W6 - Vision Sensor
  • ALLEN-BRADLEY 1762-L40BXB SER.C REV.J - MicroLogix 1200 Controller
  • HITACHI CPU22-02HC 33025801-2 - CPU Module
  • HITACHI AGH-0 33034810-2 - Control Board
  • PHILIPS AIH110 VER 1.0 - Control Module
  • BAUMULLER DO8000 - Drive Controller
  • B&R PS477 3PS477.9 Rev.C0 - Power Supply
  • ABB ALFA LAVAL 200-CISB - Communication Interface 2 x SatBus
  • Moeller MI4-570-TA1 - HMI Operator Panel
  • ABB ACH550-01-06A9-4+B055 - Variable Frequency Drive
  • ABB TPU2 3HNE00313-1 REV 12 - Teach Pendant Unit
  • Schneider Electric BRS368H130ABA - Stepper Motor
  • Foxboro FCM100E P0972ZA - I/A Series Communication Module
  • Siemens 6ES7 450-1AP00-0AE0 6ES7450-1AP00-0AE0 - Simatic S7 Version:04 Counter Module
  • Schneider Electric ATV320U07N4W - Altivar Machine Drive
  • Priva TouchPoint Flush V06:02 5060002 - Control Panel
  • Lenze ESMD402L4TXA - 4kW SMD Inverter Drive
  • Lenze ESMD402L4TXA - 4kW SMD Inverter Drive
  • Schneider Electric PM210 PM210MG - Powerlogic Power Meter
  • ASCOM U982-DB/1C U982 - Power Supply / Communication Module
  • DYADIC SYSTEMS SCN5-010-050-S03-NA - Servo Cylinder
  • Reliance Electric GMI-S04 - AC/AC CONVERTER 380/400V 50/60Hz 3.9/5.2A
  • Pro-Face GLC150-BG41-XY32KF-24V 3080060 PFXGLC150BDBP - Touch Screen HMI
  • ROFIN RSL TERMINAL V2 0185.01/03 - TERMINAL
  • HONEYWELL R7241E1077 - Burner Control / Amplifier
  • SEW MM22C-503-00 8241201 - 2.2kW Movimot Drive
  • Brand Digital III 50mL - Burette
  • Danfoss 195N0039 VLT2811PS2B20STR1DBF00A00C0 - 2.4kVA VLT Drive
  • SONY LG10-2 EK1 - Digital Gauge Indicator
  • EMERSON SKD3400750 - 7.5kW AC Drive
  • SIEMENS 6AV6 542-0AG10-0AX0 - MULTIPANEL HMI
  • TELEMECANIQUE ATV21HU55N4 - ALTIVAR21 5.5KW Variable Speed Drive
  • MITSUBISHI A985GOT-TBA-EU - GOT900 Touch Screen HMI
  • SCHNEIDER LXM32AD30N4 - Lexium 32 Servo Drive
  • SICK PSR01-1501 M20Z-02550A122 - Safety Laser Scanner
  • GECMA CHALLENGER 15-2-FMO - LITE TOUCH Monitor
  • Uniop EK02 6ZA982 - HMI Operator Panel
  • TELEMECANIQUE ATV18U54M2 - SQUARE D ALTIVAR 18 3kW Drive
  • Schneider Electric ATV312HU75S6 - 7.5kW Altivar 312 Drive
  • Siemens 6GK7243-5DX30-0XE0 6GK7 243-5DX30-0XE0 - Communications Processor
  • Schneider Electric LV432455 VIGI630 - 3POLE Earth Leakage Module
  • Rexroth PSI 6100.750 L1 R911170694-107 - frequency inverter / inverter
  • SWEDISH MICROWAVE AB Ku-Band BDC 138010-45-D0 - Block Downconverter
  • METTLER TOLEDO IND429 IND429-BB30 - Weighing Terminal
  • Siemens 6SL3210-5HE10-4UF0 - Sinamics V90 Servo Drive
  • B&R X20CP0482 Rev.D0 - X20 CPU Module
  • Mitsubishi FR-E720S-110SC-EC FRE720S110SCEC - 31A~11A Drive With Filter
  • ABB ACH580-01-026A-4 - Variable Frequency Drive
  • Siemens 6SL3210-1KE13-2AP1 - SINAMIC G120CDP 1.1kw Drive
  • Schneider Electric TM250D 4P3D LV431440 - Compact NSX250 Circuit Breaker
  • RELIANCE ELECTRIC GD.722.81.00-A 802288-74C - MAXITRON Servo Control Card
  • Uniop EK02 6ZA982 - HMI Operator Panel
  • Siemens 6SE9113-7JA13 - MICRO MASTER Junior 1.5kW Inverter
  • Mitsubishi FR-E720S-110SC-EC FRE720S110SCEC - 31A~11A Drive with Filter
  • Johnson Controls FEC2621 MS-FEC2621-0 - Field Equipment Controller
  • BENDER IR475LYT-429 - A-ISOMETER Insulation Monitor
  • Berger lahr D550 RS15 22.550-00-30b - Stepper Drive
  • Rexroth PSI 6100.750 L1 R911170694-107 - Frequency Inverter / INVERTER
  • KOYO 205 D2-06B-1 D2-240 H2-ECOM D2-08ND3 F2-08TRS - DIRECT LOGIC PLC WITH MODULE
  • TELEMECANIQUE ATV18U54M2 ATV18U54M - SQUARE D ALTIVAR 18 3kW Drive
  • Lenze 471-E1.D - Board / Controller Speed
  • Mitsubishi FR-A740-00038-EC - Frequency Inverter
  • Johnson Controls IOM3723 MS-IOM3723-0 - Input/Output Module
  • CURTIS 1238-5602 - AC Motor Controller
  • FOXBORO P0912XX REV.A - 220VAC Power Supply
  • Siemens 6SE9113-7JA13 - MICRO MASTER Junior 1.5kW Inverter
  • Mitsubishi FR-A740-00038-EC - Frequency Inverter
  • KOYO 205 D2-06B-1 D2-240 H2-ECOM D2-08ND3 F2-08TRS - DIRECT LOGIC PLC WITH MODULE
  • AUTZ M406D-00101 - Servo Motor
  • Lauer PCS095 PG095.508.BB - Operator Panel
  • ABB SCOP45SB/DX232 - SattCon OP45 SB Operator Panel
  • SEW Eurodrive MCH42A0030-5A3-4-00 MDX60A0030-5A3-4-00 - 4.8kVA Movidrive Inverter
  • BENDER IR475LYT-429 - A-ISOMETER Insulation Monitor
  • Johnson Controls FEC2621 MS-FEC2621-0 - Field Equipment Controller
  • Johnson Controls IOM3723 MS-IOM3723-0 - Input/Output Module
  • Berger lahr D550 RS15 22550-00-30b - Stepper Drive
  • SIEMENS 6FX1120-4BD03 6FX11204BD03 5702049304.00 E-Stand: A - Sinumerik Module
  • Allen-Bradley 1771-NIV B - HIGH RESOLUTION ISOLATED ANALOG SERIES Module
  • HONEYWELL XFC2D06001 - Flow Computer / Controller
  • Contraves Varidyn Compact ADB 380.90M - DC Drive 380v - 400v 90A 50kVA
  • Red Lion Control GEM52000 - Control Module
  • Siemens 6ES5 955-3NC13 - modular power supply TYPE:DIN41752
  • Danfoss ICV50 G20Mn50T / 027H5200 - Valve zaw
  • Eberle PLS508 P-814 / 2X EA-88 / A-812 / MT-81 / S-11 - PLC with Modules
  • Siemens 6ES7 314-6CF01-0AB0 6ES7314-6CF01-0AB0 - SIMATIC CPU314C-2 DP
  • EBERLE EM-525-87 EM52487 - ICE DETECTOR BASE UNIT
  • Telemecanique / Schneider TSXRKZ02 - TSX Micro automation plus 7module
  • B&R 5DLSDL.1001-00 - Display Link Receiver
  • Siemens 6FX1120-4BD03 6FX11204BD03 5702049304.00 E-Stand: A - Sinumerik Module
  • ALLEN-BRADLEY 1771-NIV A - HIGH RESOLUTION ISOLATED ANALOG SERIES Module
  • ALLEN-BRADLEY 1771-NIV B - HIGH RESOLUTION ISOLATED ANALOG SERIES Module
  • Contraves Varidyn Compact ADB 380.90M - DC Drive 380V - 400V 90A 50kVA
  • Contraves Varidyn Compact ADB 380.90M - DC Drive 380V - 400V 90A 50kVA
  • Ropex RES-202 - Resistron Temperature Controller
  • HONEYWELL XFC2D06001 - Flow Computer / Controller
  • Telemechanics ATV452U40 - DIMMER ALTIVAR5 SERIES 452 4kW 5HP Frequency Inverter
  • VEGA VEGAPLUS61 PS61.XXAGPHAMAX - Radar Level Sensor
  • BRANSON ULTRASONIC TRANSDUCER - Ultrasonic Transducer
  • Danfoss ICV50 G20Mn50T / 027H5200 - Valve Valvola Zaw
  • Schneider Electric 2001549/1 GALAXY PW 5102851200 NT07 - panler card
  • REXROTH VT3006-36 A - Proportional Valve Amplifier
  • Allen-Bradley 1746-OBP16 SERIES:C - SLC 500 OUTPUT MODULE
  • SCHNEIDER LXM32MD12N4 - Lexium 32 Servo Drive
  • Schneider Electric ATV630U22N4 - 2.2KW Altivar Process Drive
  • Allen-Bradley 1746-OBP16 SERIES:C - SLC 500 OUTPUT MODULE
  • Vanderlande 0E2550-00002... - Bagtrax Integrated Power Module 400V 32A
  • B&R X20CP0410 Rev.D0 - X20 CPU Module
  • VANDERLANDE 0E2550-00002 02EDD2B0100 - BAGTRAX Integrated Power Module 400V 32A
  • Rexroth R061205010 - Linear Bushing / Bearing
  • INDRAMAT TVM1.2-50-220/300-W0-220/380 - Power Supply Module
  • Vanderlande 0E2550-00002... - Bagtrax Integrated Power Module 400V 32A
  • HOMAG KEB 07F5S1A-YA00 09E5T60-1001 - Combivert Inverter WITH KEYPAID AND FILTER
  • Siemens 3RW3047-1BB14 - Soft Starter
  • Sumitomo AF-500 AF502-A40 - 0.4kW Transistor Inverter
  • Sumitomo AF-500 AF502-A40 - 0.4kW Transistor Inverter