Bently Nevada 3500/65 145988-02 Channel Temperature Monitor
Description
The 3500/65 monitor provides 16 channels of temperature
monitoring and accepts both resistance temperature
detector (RTD) and isolated tip thermocouple (TC)
temperature inputs. The monitor conditions these inputs and
compares them against user-programmable alarm
setpoints.
The monitor is programmed using the 3500 Rack
Configuration Software. You can configure the 16-Channel
Temperature Monitor to accept isolated tip thermocouples,
3-wire RTD, 4-wire RTD, or a combination of TC and RTD inputs.
In Triple Modular Redundant (TMR) configurations, you must
install temperature monitors in groups of 3 adjacent
monitors. In this configuration the monitor uses 2 types of
voting to ensure accurate operation and to avoid singlepoint failures.
Specifications
Inputs
Power
Consumption 3 watts nominal
Signal
Accepts from 1 to 16 RTD or
isolated tip TC transducer
signals.
Input
Impedance
Greater than 1 MΩ for each
lead input.
Transducers
TCs
Type E
-100°C to +1000°C,
(-148°F to +1832°F)
Type J
0°C to +760 °C
(32°F to +1400 °F)
Type K
0°C to +1370°C
(32°F to +2498°F)
Type T
-160°C to +400°C,
( -256°F to +752°F)
RTDs
100 Ω 3-wire and
4-wire platinum
RTD (α =
0.00385)
-200°C to +850°C
(-328°F to +1562°F)
100 Ω 3-wire and
4-wire platinum
RTD (α =
0.00392)
-200°C to +700°C
(-328°F to +1292°F)
120 Ω 3-wire and
4-wire nickel
RTD
-80°C to +260°C
(-112°F to +500°F)
10 Ω 3-wire and
4-wire copper
RTD
-100°C to +260°C,
(-148°F to +500°F)
Platinum RTDs with α = 0.00385 are
the worldwide industrial standard
and are the recommended RTDs for
all applications.
Outputs
Front Panel LEDs
OK LED Indicates when the 3500/65 is
operating properly.
TX/RX LED
Indicates when the 3500/65 is
communicating with other
modules in the 3500 rack.
Bypass LED Indicates when the 3500/65
monitor is in Bypass Mode.
RTD
CurrentSource
Value
913 ± 7 µA @ 25°C per transducer
(1 supply for the 4-wire RTD and
2 supplies for the 3-wire).
Signal Conditioning
Specified at +25°C (+77° F). Full-scale
range for each channel is set in the
field via 3500 Configuration Software.
No calibration is required
RTDs and TCs
Resolution 1°C or 1 °F.
Accuracy
Internal
Termination
Bulkhead Rack: ±3°C at +25°C
(±5.4°F at +77°F).
Standard Rack: ±3°C at +25°C
(±5.4°F at +77°F).
External
Termination
Bulkhead Rack: ±3°C at +25°C
(±5.4°F at +77°F)
Standard Rack: ±3°C at +25°C
(±5.4°F at +77°F)
Cold Junction Compensation
Sensor (used for TC
measurements) ±2°C at +25°C
(±3.6°F at +77°F).
Alarms
Alarm
Setpoints
You can use software
configuration to set Alert and
Danger setpoints for the value
measured by the monitor. Alarms
are adjustable from 0 to 100% of
full-scale for each measured
value. The exception is when the
full-scale range exceeds the range
of the sensor. In this case,
software will limit the setpoint to
the range of the sensor. Accuracy
of alarms are to within 0.13% of the
desired value. The 3500/65 16-
channel temperature monitor has
both under- and over-alarm
setpoints.
Alarm
Time
Delays
You can use software to program
alarm delays as follows:
Alert
Delay
From 1 to 60 seconds in 1-second
increments.
Danger
Delay
From 1 to 60 seconds in 0.5-
second increments.
Proportional Values
Proportional values are temperature
measurements used to monitor the machine.
The 16-channel temperature monitor returns
temperature proportional values.
Environmental Limits
Operating
Temperature:
-30°C to +65°C (-22°F to
+150°F)
Storage
Temperature:
-40°C to +85°C (-40°F to
+185°F)
Physical
Main Module
Dimensions
(Height x
Width x
Depth)
241.3 mm x 24.4 mm x 241.8 mm
(9.50 in x 0.96 in x 9.52 in)
Weight 0.91 kg (2.0 lbs.).
I/O Modules
Dimensions
(Height x
Width x
Depth)
241.3 mm x 24.4 mm x 99.1 mm
(9.50 in x 0.96 in x 3.90 in)
Weight 0.45kg (1.0 lb.).
Rack Space Requirements
Main
Module 1 full-height front slot
I/O Modules 1 full-height rear slot