ABB 3BHE009681R0101 High Voltage Inverter Spare Parts
Description Type test value Reference• Common mode 2.5 kV
Electrostatic discharge test IEC 61000-4-2
IEC 60255-26
IEEE C37.90.3-2001
• Contact discharge 8 kV
• Air discharge 15 kV
Radio frequency interference test
10 V (rms)
f = 150 kHz...80 MHz
IEC 61000-4-6
IEC 60255-26, class III
10 V/m (rms)
f = 80...2700 MHz
IEC 61000-4-3
IEC 60255-26, class III
10 V/m
f = 900 MHz
ENV 50204
IEC 60255-26, class III
20 V/m (rms)
f = 80...1000 MHz
IEEE C37.90.2-2004
Fast transient disturbance test IEC 61000-4-4
IEC 60255-26
IEEE C37.90.1-2002
• All ports 4 kV
Surge immunity test IEC 61000-4-5
IEC 60255-26
• Communication 1 kV, line-to-ground
• Other ports 4 kV, line-to-ground,
2 kV, line-to-line
Power frequency (50 Hz)
magnetic field immunity test
IEC 61000-4-8
• Continuous
• 1...3 s 300 A/m
1000 A/m
Pulse magnetic field immunity test 1000 A/m
6.4/16 µs
IEC 61000-4-9
Damped oscillatory magnetic field
immunity test
IEC 61000-4-10
• 2 s 100 A/m
• 1 MHz 400 transients/s
Voltage dips and short
interruptions
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
IEC 61000-4-11

Description Type test value Reference
Power frequency immunity test Binary inputs only IEC 61000-4-16
IEC 60255-26, class A
• Common mode 300 V rms
• Differential mode 150 V rms
Conducted common mode
disturbances
15 Hz...150 kHz
Test level 3 (10/1/10 V rms)
IEC 61000-4-16
Emission tests EN 55011, class A
IEC 60255-26
CISPR 11
CISPR 12
• Conducted
0.15...0.50 MHz <79 dB (µV) quasi peak
<66 dB (µV) average
0.5...30 MHz <73 dB (µV) quasi peak
<60 dB (µV) average
• Radiated
30...230 MHz <40 dB (µV/m) quasi peak,
measured at 10 m distance
230...1000 MHz <47 dB (µV/m) quasi peak,
measured at 10 m distance
1…3 GHz <76 dB (µV/m) peak
<56 dB (µV/m) average,
measured at 3 m distance
3…6 GHz <80 dB (µV/m) peak
<60 dB (µV/m) average,
measured at 3 m distance
Table 8: Insulation tests
Description Type test value Reference
Dielectric tests 2 kV, 50 Hz, 1 min
500 V, 50 Hz, 1 min,
communication
IEC 60255-27
IEEE C37.90-2005
Impulse voltage test 5 kV, 1.2/50 μs, 0.5 J
1 kV, 1.2/50 μs, 0.5 J,
communication
IEC 60255-27
IEEE C37.90-2005
Insulation resistance
measurements
>100 MΩ, 500 V DC IEC 60255-27
Protective bonding resistance <0.1 Ω, 4 A, 60 s IEC 60255-27