+086-15305925923

K-WANG

Service expert in industrial control field!
NameDescriptionContent
Adequate Inventory, Timely Service
pursuit of excellence 
Ship control system
Equipment control system
Power monitoring system
Current position:
新闻动态
newS
   
Brand

Watlow CLS200 series controller

From: | Author:Wang | Time :2025-11-10 | 331 visit: | 🔊 Click to read aloud ❚❚ | Share:

Watlow CLS200 series controller

Product Overview and Core Features

1. Product positioning and circuit configuration

The CLS200 series controller is an industrial grade multi loop control device that provides 4 (CLS204), 8 (CLS208), or 16 (CLS216) completely independent control loops. It can be used as an independent controller (operated through a 2-line 16 character display screen and touch keyboard) or as a core component of a computer monitoring data acquisition and control system, supporting local or remote control through EIA/TIA-232 or EIA/TIA-485 serial communication interfaces.

2. Core functional features

Multi type sensor compatibility: directly connect multiple thermocouples (J, K, T, S, R, B, E types) without hardware modification, with reference compensation, linearization, measurement offset calibration, disconnection/short circuit/reverse connection detection functions, supporting Fahrenheit/Celsius display; Support 3-wire 100 Ω platinum resistance RTD (0.00385 curve), calibration resistors need to be configured for CLS204/CLS208; Automatic calibration of linear analog input (requires installation of calibration resistors), input two points to automatically calibrate according to user units.

Flexible output control: Each circuit includes dual outputs for heating and cooling, with independent configuration of output parameters; Supports multiple control and output modes, with control outputs set to ON/OFF, TP, DZC, and SDAC modes. Each circuit can have up to 2 outputs set to ON/OFF, P, PI, or PID control, and supports reverse/forward actions.

Alarm and Monitoring: Supports high/low process alarm and high/low deviation alarm. Each loop alarm can independently activate digital output or group activate output; The global alarm output is activated upon any alarm trigger and needs to be manually confirmed before being turned off; The CPU watchdog timer output can monitor system faults, keep the relay closed during controller operation, and trigger notifications when the microprocessor shuts down.

Communication and Storage: Supports Modbus RTU protocol, connects PLC, operation interface terminal, and third-party software through EIA/TIA-232/485 interface; The memory can store up to 8 tasks, which can be called locally or remotely through numerical input. Each task includes operating conditions such as set values and alarms.

Other practical functions: support non-linear output curve selection; The self-tuning function can quickly optimize PID parameters; Pulse counter input (up to 2000Hz) can accurately control motor or belt speed; Low power shutdown function, automatically shuts down and all outputs when the input voltage is below the safe value detected 🔶 1-163, 1-164, 1-165, 1-166 🔷。

Installation Guide

1. Preparation and safety requirements before installation

Environmental requirements: The controller should be installed in a location without excessive temperature (not exceeding 50 ℃/122 ℉), low dust, and unauthorized operation, to avoid electromagnetic and radio frequency interference. Sensor wiring should be kept away from high-voltage lines, power switch equipment, and motors.

Safety warning: Cut off the power supply throughout the entire process before installation to prevent electric shock; The controller may malfunction to 0% or 100% power output state, requiring the installation of independent external safety shutdown devices (such as FM certified high/low process limit controllers and mechanical contactors), and the safety devices must be independent of the process control equipment. If the malfunction may result in death or injury, FM certified safety devices must be used.

Tool preparation: It is recommended to use a 1/8-DIN rectangular punch (such as Greenlee 600-68), curved saw and metal file (stainless steel/thick panel), nibbler and metal file (aluminum/light panel), as well as a cross screwdriver, 1/8 inch (3mm) straight screwdriver (for wiring), and multimeter.

2. Installation steps of core components

(1) Controller installation

Panel opening: A hole of 1.80 inches (46mm) x 3.63 inches (92mm) (tolerance ± 0.02 inches/1mm) needs to be opened on the panel, and the panel thickness should not exceed 0.2 inches (5mm).

Installation process: First, remove the bracket and collar of the processor module, and slide the module into the panel cut; Insert the installation collar onto the back of the module (with the screw groove facing back), loosen the screws of the installation bracket, insert the bracket into the installation groove (with the screw head facing back), tighten and fix it laterally; Ensure that the casing is installed in place and tighten the screws to secure the bracket against the collar.

Space requirements: The controller can extend up to 7.0 inches (178mm) behind the panel, and the screw bracket can extend up and down by 0.5 inches (13mm) each; If using a straight SCSI cable, an additional 1.6 inches (41mm) should be reserved behind the terminal board; If using a right angle SCSI cable, an additional 0.6 inches (15mm) need to be reserved.

(2) Installation of TB50 terminal board

TB50 is a screw terminal interface used to connect relays, encoders, and discrete I/O devices. It supports 18 AWG (0.75mm ²) wires and is connected to the controller through a 50 pin SCSI cable. There are two installation methods:

DIN rail installation: First, clamp the hook side of TB50 onto the rail, and then push the buckle side into place for fixation; Use a Phillips screwdriver to pry open the buckle during disassembly.

Bracket installation: First remove the DIN rail bracket of TB50, mark 4 installation holes, drill the # 6 (3.5mm) screw hole, and fix TB50 with 4 screws; The four small holes on the terminal board can be used to secure wiring with zip ties.

(3) Installation of power supply and DAC module

Power installation: If using a built-in power supply, choose a Class 2, isolated and regulated 12-24V DC (1A) power supply, and install it according to the instructions of the power supply manufacturer; The installation bracket with built-in power supply needs to reserve a gap of 0.3 inches (8mm) and be fixed with 2 # 10 (5.0mm) screws. Pay attention to using 6-32 and 1/4 inch screws to avoid damaging the power supply with excessively long screws.

Installation of Dual DAC/Serial DAC Module: The module is used to convert the open collector output of the controller into an analog signal. During installation, it is necessary to select a wall position close to the controller, mark and drill 4 # 8 (4.0mm) screw holes for fixation; The output signal range of the module is configured through jumper wires. The dual DAC requires independent power supply to isolate the digital and analog circuits. The serial DAC supports cascading multiple modules (up to 16), and the 5V DC output of the CLS200 power supply is required to power multiple modules 🔶 1-381 to 1-397, 1-773 to 1-794 🔷。

3. System cabling and testing

(1) Wiring specifications

Cable selection: It is recommended to use multi strand wires (solid lines are only used for fixed scenarios and are prone to poor contact during maintenance); Thermocouple extension wire uses 20 AWG (0.5mm ²); Shielded wires are used for analog input/output and RTD input, with one end of the shielding layer connected to the ground; Except for thermocouples, copper wires are used for other connections.

Anti interference measures: Separate the wiring of high and low voltage lines to avoid parallelism or bundling; If an electromechanical relay must be used, a 0.01 μ F (1000V AC) capacitor and a 47 Ω (0.5W) resistor absorption network should be connected in series at both ends of the normally open contact of the relay load, or a metal oxide varistor (MOV) and a bidirectional voltage regulator diode (Transorb) should be connected in parallel.

Grounding requirements: Avoid grounding loops, and the DC common terminal, analog common terminal, reference voltage common terminal, communication common terminal, etc. of the controller must not be connected or grounded to each other; CLS216 is a single ended input, and all sensor negative terminals are connected to the analog common terminal. Grounded or ungrounded thermocouples must be used uniformly, and special wiring is required for mixed current and low voltage inputs.

(2) Power supply and terminal connection

Power connection: Connect the DC common terminal of the power supply to the DC common terminal of CLS200 TB2 (-), and connect the positive terminal of the power supply to the DC positive terminal of TB2 (+); If an external power source is used to supply power to the load, the DC common terminal of the load power source must be connected to the DC common terminal of the controller power source; The grounding terminal of TB2 must be connected to the controller casing and grounded; Finally, connect the 120/240V AC power supply to the power source.

TB50 connection: Connect TB50 to the controller through a 50 pin SCSI cable, ensuring that the cable is securely inserted into the interface.

(3) System testing

TB50/TB18 test: After power on, the controller displays "SCALE CHECK SUM", followed by a bar chart; Measure the+5V DC voltage of TB50/TB18 with a multimeter (terminal 1 is positive, terminal 3/TB18 terminal 2 is common), and the voltage should be between 4.75-5.25V.

Digital output test: Connect a 500 Ω -100k Ω resistor between terminal 1 (+5V) of TB50/TB18 and the digital output terminal to be tested. Use the "MANUAL I/O TEST" menu to control the output switch. When the output is ON, the voltage is less than 1V, and when it is OFF, the voltage is 4.75-5.25V. The heating output is enabled by default and needs to be set to manual mode for 100% output before testing.

Digital input test: Disconnect the input wiring and enter the "DIGITAL INPUTS" test menu. When the input is not connected, it displays "H" (high level/open circuit). When the input terminal is connected to the controller common terminal (TB50 terminal 3/TB18 terminal 2), it displays "L" (low level/closed).


Operation Guide

1. Front panel and button functions

Panel layout: Includes a 2-line 16 character display screen and an 8-key keyboard. The display screen can display process variables, set values, output levels, and other information. The keyboard includes "Ramp/OAK" (slope/constant temperature control), "ALARM ACK" (alarm confirmation), "MAN/AUTO" (manual/automatic switching), "CHNG SP" (set value modification), "ENTER" (confirm/store), "BACK" (return/cancel), "YES" (up/add), and "NO" (down/reduce) keys.

Key function: The "YES" key is used to select menus/parameters, confirm YES/NO prompts, increase values, and stop scanning; The "NO" key is used to skip menus/parameters, reject YES/NO prompts, reduce values, stop scanning, and perform NO key reset (press and hold to restore default parameters when powered on); The 'BACK' key is used to cancel editing, return to the previous menu, and switch display modes; The 'ENTER' key is used to store modifications, enter the next parameter, and start scanning (press twice); The "CHNG SP" key is used to modify the set value; The "MAN/AUTO" key is used to switch between manual/automatic modes, adjust manual output, and start self-tuning; The 'RAMP/SOAK' key is used to allocate slope/constant temperature curves, select modes, and view curve status (controllers with this option only); The 'ALARM ACK' button is used to confirm alarms and reset global alarm outputs.

2. Core display mode

(1) Bar chart display (default upon startup)

Display content: The top displays up to 8 circuit numbers/names and alarm symbols (such as "<" for low process/deviation alarm, ">" for high process/deviation alarm, "F" for sensor failure), and the bottom displays control status symbols (such as "M" for manual, "A" for automatic, "T" for self-tuning).

Operation: Press the "YES"/"NO" keys to switch circuit groups, press "ENTER" twice to start scanning (each group displays for 3 seconds), press any key to stop scanning, press the "BACK" key to switch to task display (if enabled) or single circuit display.

(2) Single loop display

Display content: Display the process variables, engineering units, set values, control status (MAN/AUTO/TUNE/HEAT/COOL), and output percentages of a single circuit. If dual outputs are enabled, heating and cooling output percentages will also be displayed separately.

Operation: Press the "YES"/"NO" keys to switch circuits, press "ENTER" twice to start single circuit scanning (each circuit displays for 1 second), press any key to stop, press the "BACK" key to switch to task display or bar chart display.

(3) Alarm display

Trigger logic: When the process/deviation/sensor failure/system alarm is triggered, the controller automatically switches to the single loop display of the fault circuit, and the global alarm output is activated, displaying a 2-character alarm code (such as "FS" indicating thermocouple disconnection, "HP" indicating high process alarm). When the sensor fails, the output is set to the "sensor fault heating/cooling output" parameter value (default 0%), and the alarm code flashes. Other functions can only be operated after confirmation.

Alarm types: including sensor faults (thermocouple open/short/reverse, RTD open/short), process alarms (high/low process, high/low deviation), system alarms (battery failure, low power consumption, excessive ambient temperature, hardware failure), each alarm corresponds to a specific code and processing method.

Alarm confirmation: Press the "ALARM ACK" button to confirm the alarm. If multiple circuits alarm, they will switch to each faulty circuit in sequence. All alarms need to be confirmed before resetting the global alarm output.

3. Key operational procedures

(1) Modify the set value

Switch to the single circuit display of the target circuit;

Press the "CHNG SP" button, and the display screen will show "SETPOINT? XX" (XX is the current set value);

Press the "YES" key to enter modification mode, and press the "YES"/"NO" keys to increase or decrease the set value;

Press the "ENTER" key to save and return to the single circuit display, or press the "NO"/"BACK" keys to cancel the modification.

(2) Manual/automatic mode switching

Switch to the single circuit display of the target circuit;

Press the "MAN/AUTO" button, press the "YES" button to confirm the mode switch, or press the "NO" button to cancel (in automatic mode);

If switching to manual mode, press the "YES"/"NO" keys to set the heating/cooling output percentage, and press the "ENTER" key to save;

If switched to automatic mode, the controller controls according to the preset PID parameters;

If switched to TUNE mode, the controller automatically optimizes the PID parameters.

(3) Self tuning operation

Prerequisite: The controller has installed control and sensor circuits, the thermal load is in place, the system can operate safely, and the approximate target temperature is known.

Operation steps:

Switch to the single loop display of the target loop, ensuring that the process variable is stable and in manual mode;

Set the set value close to the normal operating temperature (note: during the self-tuning period, the output is 100% or the output limit value must be within a safe range);

Press the "ENTER+ALARM ACK+CHNG SP" key combination to enter the settings menu, and set "INPUT Filter" to 0 SCANS in the "SETUP LOOP INPUT" menu;

Return to single circuit display, press the "MAN/AUTO" key, press the "NO" key to switch to TUNE mode, press the "ENTER" key to start self-tuning (TUNE "flashes);

After self-tuning is completed, automatically switch to automatic mode and restore the original setting value of "INPUT Filter".

Setting guide

1. Enter the settings menu

Enter through the "three key combination": Under the single circuit display of the target circuit, press the "ENTER", "ALARM ACK", and "CHNG SP" keys in sequence (not simultaneously). If there is no operation for 3 minutes, the controller will automatically return to the single circuit display to prevent unauthorized access.

2. Core Settings Menu

(1) SETUP Global Parameters

Includes parameters such as task loading/saving, task selection digital input, output forced digital input, startup alarm delay, ramp/constant temperature time reference, keyboard lock, power on output status, process power digital input, controller address, communication parameters (baud rate, protocol, verification), AC line frequency, digital output polarity during alarm, etc. For example:

Load SETUP FROM JOB "/" SAVE SETUP TO JOB ": Load/save tasks 1-8, which include PID parameters, control status, alarm settings, etc;

Controller Address ": Set the communication address (1-247) to be unique in the EIA/TIA-485 network. Anasoft software supports up to 16 controllers (addresses 1-16);

Communications BAUD RATE ": Set the baud rate (2400/9600/19200) to be consistent with the upper computer.

(2) Loop input setting (SETUP LOOP INPUT)

Configure input type (thermocouple/RTD/linear/pulse/SKIP), circuit name, input unit, input offset, thermocouple reverse detection, pulse sampling time, display format, linear calibration parameters, input filtering, etc., for example:

INPUT TYPE ": Select the sensor type, SKIP is used for unused circuits (does not detect alarms, does not participate in scanning);

INPUT SCALING ": Linear input requires setting high/low process variables and corresponding high/low readings to achieve signal calibration;

INPUT Filter ": Set the filtering for the 0-255 scan period, disable filtering at 0, to suppress input signal fluctuations.

(3) Loop Control Parameter Setting (SETUP LOOP Control PARAMS)

Set PID core parameters such as heating/cooling ratio band (PB), integration time (TI), differentiation time (TD), control filtering, temperature difference (SPREAD), PID recovery digital input, etc., for example:

HEAT Control PB ": The larger the proportional band, the weaker the proportional effect, and the default value varies with the sensor type (e.g. J-type thermocouple defaults to 50);

SPREAD ": It is a hysteresis loop during switch control, and a switching threshold (0-255, consistent with the display format) for process variable deviation from the set value during PID control.

(4) Loop output setting (SETUP LOOP OUTPUTS)

Enable/disable heating/cooling output, set output type (TP/DZC/SDA/ON/OFF/3P DZC), cycle time (TP mode), SDAC parameters, output action (reverse/forward), output limit, sensor fault output, thermocouple break output average, output linearity, etc., for example:

HEAT CON OUTPUT ": Enable/disable heating output, which can be used as an alarm output when disabled;

SENSOR FAIL HT OUTPUT ": Heating output percentage (0-100%) in case of sensor failure, default 0%.

(5) SETUP LOOP ALARMS

Configure high/low process alarm settings, alarm types (OFF/ALARM/MOTOR), alarm outputs, deviation alarm values, alarm dead zones, alarm delays, for example:

HI PROC ALARM SETPT "/" LO PROC ALARM SETPT ": High/low process alarm threshold, within the sensor range;

ALARM DEADBAND ": Alarm hysteresis, preventing process variables from fluctuating near the alarm threshold and causing frequent alarms (0-255, units consistent with display format).

(6) Manual I/O Test

Test digital input (displaying H/L status), digital output (manually switching ON/OFF), keyboard (displaying key names by pressing any key), and display screen (displaying pixel patterns) to troubleshoot I/O faults.


Troubleshooting and Maintenance

1. Common faults and their solutions

(1) Power and display malfunction

LOW POWER: Confirm that the power supply voltage is ≥ 12.0V DC (1A), and check the power supply wiring; If the error persists after restarting, record the parameters and perform a NO key reset. If it is ineffective, contact the manufacturer.

BATTERY DEAD (battery failure): When the battery cannot maintain parameter storage during power failure, the parameters will be reset to default and the battery needs to be replaced. If it fails, contact the manufacturer.

The display screen does not light up: check the power wiring and confirm that the power supply is normal; If it is an EPROM issue, replace the EPROM (anti-static operation is required); If the controller is damaged, send it back for repair.

(2) Sensor malfunction

Thermocouple failure (FS/RT/ST): Check the thermocouple wiring (positive and negative poles, broken wires, short circuits), and confirm whether the "REVERSED T/C DETECT" parameter is enabled; If it is a broken wire, replace the thermocouple; If it is reversed, adjust the wiring.

RTD fault (RO/RS): Check the RTD wiring (open/short circuit), measure the RTD resistance (20-250 Ω normal), replace if damaged.

(3) Communication malfunction

Check whether the communication parameters (address, baud rate, protocol, verification) are consistent with the upper computer;

Check the wiring of EIA/TIA-232/485, terminal resistance (150-200 Ω) is required for EIA/TIA-485, shielded wire is needed for long-distance communication, and one end of the shielding layer is grounded;

Use a communication tester or oscilloscope to detect the signal and eliminate the grounding loop (an optical isolation converter can be used).

2. Maintenance operations

(1) NO key reset

Restore all parameters to default values. Operation: Press and hold the "NO" key after power off, release it after power on, and press the "YES" key to confirm when the prompt "RESET WITH DEFAULTS?" appears; Before resetting, the parameters need to be recorded, and the computer monitoring system can save the parameters through software.

(2) EPROM replacement

Prerequisite: A cross screwdriver, a straight screwdriver, and an anti-static wristband are required. Record the parameters before replacement.

Step: Power off, remove the 4 screws on the front panel of the controller, and take out the electronic components; Remove the 4 screws from the top circuit board and unplug the circuit board; Use an IC extractor to remove the old EPROM and insert the new EPROM (pay attention to the direction of the notch); Reverse the steps to reassemble, power on and re-enter the parameters.

(3) Calibration resistor installation

The current, voltage, and RTD inputs of CLS204/CLS208/CLS216 require the installation of specific calibration resistors. The resistance value and position vary with the input type (such as CLS204 current input using 6 Ω or 3 Ω resistors), and must be soldered by professional technicians to avoid damaging the circuit board.


Technical specifications

1. Core specifications of the controller

Environmental parameters: working temperature 0-50 ℃, storage temperature -20-60 ℃, humidity 10-95% (non condensing), indoor use.

Physical dimensions: CLS200 processor module weighs 1.98 pounds (0.9kg), measures 8.0 inches (203mm) in length (without SCSI interface), has a width of 3.78 inches (96mm), and a height of 1.96 inches (50mm); TB50 weighs 0.32 pounds (0.15kg), measures 4.1 inches (104mm) in length, 4.0 inches (102mm) in width, and 1.5 inches (37mm) in height 🔶 1-3423, 1-3425, 1-3451 🔷。

Input/output: Analog input supports -10 to+60mV (or 0-25V with calibrated resistor), resolution>14 bits, accuracy 0.03% of full range (25 ℃); 8 digital inputs (TTL level), 35 digital outputs (open collector, maximum 60mA/24V DC); One CPU watchdog output (maximum 10mA/5V DC).

Communication: Supports EIA/TIA-232 (3-wire, maximum 50 feet), EIA/TIA-485 (4-wire, maximum 4000 feet), baud rate 2400/9600/19200, protocol Modbus RTU/Anafaze/Allen Bradley, verification BCC/CRC.

2. Auxiliary component specifications

Power supply: Input 120/240V AC (0.75A, 50/60Hz), output 5V DC (4A), 15V DC (1.2A).

Dual DAC: Operating temperature 0-50 ℃, output supports 4-20mA, 0-5V, 0-10V, accuracy ± 0.75% of full scale, load resistance varies with output type and power supply.

Serial DAC: Operating temperature 0-70 ℃, output supports 0-10V or 4-20mA (jumper selection), can cascade up to 16, CE certified.


  • ABB 560CMR01 Communication Module RTU560 Control Unit
  • Metso 1NWH155 - Ethernet Hub
  • Metso T22PO 103913968 - Sampler Valve (LF02C)
  • Metso EDS-516A-MM-SC - Ethernet Device Switch
  • Metso MC4-16-4 - Brass Rotary Oscillator Drive
  • Metso XT03CWTAS6SJHA - 3" Ball Valve Assembly
  • Metso 181226 - Digital Input Module
  • Metso RAU4E62037 - Valmet Posieve Plus Measuring Head
  • Metso VT-223779/2 - Sealing Housing SD42"B
  • Metso J2029 010 10722 - Circuit Board
  • Metso D202038-ACN-PO - Automation Component
  • Metso NE724/S1-CE01 - Electro-pneumatic Valve Positioner
  • Metso M851004 - CPU Module T194-v0
  • Metso Trucker Hat - Finland Golf Ball Cap
  • Metso DN6-50 - Jamesbury 1/4" Valve
  • Metso B1CU6/20L - Pneumatic Actuator
  • Metso B1CU6/25L - Pneumatic Actuator
  • Metso A416040-09 - Power Rating Unit 28 VDC
  • Metso A4300018B - Central Unit Communication Interface
  • Metso ND9106HN/K05 - Intelligent Valve Controller
  • Metso D200537 BOU83 - Binary Output Model 02
  • Metso A413111 TIU61 - Temperature Input Unit Board
  • Jamesbury 730S313600XTZ2 - 1" Flanged SS Ball Valve
  • Metso HG4A12SH0 - Pressure Transmitter with Coupling
  • Metso A413146 BIU 4 - Binary Input Module
  • Metso DDC7940-D201139 - Controller Module
  • Metso Square Flange - Discharge Flange for Slurry Pump
  • Metso A413177 - Automation Board
  • Metso BOU82 D200536 - Binary Output Module
  • Metso D200619 - Personality Module
  • Metso RKN50MT - Actuator Repair Kit
  • Metso IOP335 - Counter Timer Module
  • Valmet IOP341R 181560 - Positioner Module
  • Metso A413150 - Power Module
  • Metso RKN-184XTZ - Actuator Repair Kit
  • Metso Flinger Seal - Slurry Pump Component
  • Metso Smart-Pulp M2 - Flow Transmitter 24v-dc
  • Metso S420154 - Automation Rack
  • Metso MM0317187 - Efector Kit
  • Metso TCU (MCA) - Consistency Transmitter Analyzer
  • Metso K7504-E - Crusher Pull Back Rod And Nut
  • Metso M2DA02AP - Stainless Flanged Ball Valve 2in
  • Metso vpvl350sr4/5bd - ValvPowr Actuator with ASCO 8551 Valve
  • Metso A413115 TCU41 - Consistency Controller Board
  • Metso D100226 BIC12 - Circuit Board
  • Metso PDWB031 - Bearing Assembly
  • Metso D200532 BIU8 - Binary Input Unit
  • Metso QPXC2/K20C - Spring Diaphragm Actuator
  • Metso PN8504 - Efector Pressure Kit
  • Valmet A413331 SPU - Power Supply Module
  • Metso EDS-518A-MM-SC - Ethernet Switch
  • Metso LK865 - Valve Actuator Mounting Kit
  • Metso LK-909 - Valve Actuator Mounting Kit
  • Metso Z6287570990 - Seal Kit 4501622310
  • Kajaani U4300115A - VME CPU Board Central Unit
  • Metso PO Node - Controller Module
  • Metso NP726/S1 - Neles Pneumatic Positioner
  • Metso D201138 IBC - Controller Module
  • Metso APS002 - Power Supply 046823
  • Kajaani 15JK-2 A4150110B - Preamplifier Board
  • Wittenstein LP090S-MF1-3-1 - Planetary Gear Head
  • Metso k5232-hjr - Safety Shoe RH
  • Metso A416013 PFC - Iq Controller Interface Platform
  • Metso IOP341 - Positioner Module
  • Metso DCEAEA - Automation Valve Actuator
  • Metso PLU3 A413183 - Automation Board
  • Metso 610-1-4-06-01 - Paper Machinery Panel Display
  • Metso IOP304 181503 - TC/mV Input Module
  • Metso D201138L IBC - Controller with Base
  • Metso AOF2V A413767 - Automation Module
  • Metso PDP401 181580 - Distributed Processing Unit
  • Iittala Capercaillie - Oiva Toikka Design Glass Bird
  • Metso TR2432 - Efector Temperature Transmitter with Well
  • Metso A413084 - CPU Module 32 16M
  • Metso A413052 - SBC Serial Bus Controller
  • Metso PLU2 A413182 - Automation Board
  • Metso A413240 PIC2 - Process Interface Controller Board
  • Metso MBI8 - PLC 8-Slot Chassis
  • Metso MM0290431 - Efector Pressure Kit
  • Metso IOP336 - Automation Interface Module
  • Valmet IOP371 181500 - I/O Bus Extender Module
  • Metso 1057602103 - Nordberg Bronze Thrust Bearing
  • Metso IOP331 - Controller Module
  • Metso A413325 IPU - Power Module
  • Metso B1CU9/35L - Pneumatic Actuator
  • Metso QPX5C/MC - Quadra-Power Rotary Actuator
  • Metso ND9106HXT - Intelligent Valve Controller
  • Metso QPX2C/K20 - Quadra-Powr X Rotary Actuator
  • Metso BIU83 D200534 - Binary Input Unit
  • Metso R185362210 - Rexroth Linear Roller Rail Runner Block
  • Metso A4730024 - Smart-pulp RDU Consistency Transmitter
  • GE DS3800NHVG Control Circuit Board
  • GE DS3800HIOC I/O Control Circuit Board
  • GE DS3800NB1A Circuit Board
  • GE DS3815PAHB1A1A Printed Circuit Board
  • Metso NP704/B1S1A - Neles Pneumatic Valve Positioner
  • Metso ND9103HU2 - Valve Controller Positioner
  • Metso ND9203HE2-KA3 - Electro Pneumatic Positioner
  • Metso NP724/J30 - Neles Valve Positioner
  • Metso M2 SMART PULP - Consistency Transmitter
  • Metso T00162 - Smart-Pulp Consistency Transmitter
  • Metso K4246-A 1275 - Crown Gear
  • Metso MAC24726 N74525064 - Housing
  • Metso NE724A Straight stroke - Intelligent Valve Positioner
  • Metso NE726A - Intelligent Valve Positioner
  • Metso A413016 - NCU Network Control Unit
  • Metso B1JVU8/35L - Pneumatic Actuator
  • Metso A413310 - Power Supply Unit
  • Metso ND9103HU-K - Intelligent Valve Controller
  • Metso ND9103HUT-DS02 - ND9000 Digital Positioner
  • Metso NE726/S1 - Pneumatic Valve Positioner
  • Metso BB01/BD01 D200625 - Automation Module
  • Metso NDX2512HG-NNON 0000 - Intelligence Valve Positioner
  • Metso FPU - Power Supply Unit
  • Metso XZB10025-013T1 2 - Hydraulic Valve
  • Metso XZB10276-001T1 2 - Hydraulic Valve
  • Metso D100789 - IPU2 Power Unit
  • Metso D200137 - Power Supply Module
  • Metso D200175 - Personality Module
  • Metso T00161 - Smart-Pulp Consistency Transmitter
  • Metso A413240 - Automation Module
  • Metso 7041871500 - Gear Wheel
  • Metso NE724A - Pneumatic Valve Positioner
  • Metso PULP-EL-LL2W - Automation Module
  • Metso MM0237480 - Mechanical Part
  • Metso A413160 - Automation Module
  • Metso APL 3037138 - Pneumatic Cylinder
  • Metso A413082 Ver.08 - CPU Module