K-WANG

+086-15305925923
Service expert in industrial control field!
NameDescriptionContent
Adequate Inventory, Timely Service
pursuit of excellence 
Ship control system
Equipment control system
Power monitoring system
Current position:
新闻动态
newS
   
Brand

Watlow Series 942 Controller

From: | Author:Wang | Time :2025-11-11 | 526 visit: | 🔊 Click to read aloud ❚❚ ▶ | Share:



Watlow Series 942 Controller

Core features and specifications of the product

core functionality

Control mode: Supports PID or ON/OFF control, can be manually selected; Dual output design, output 1 can be set as heating or cooling, and output 2 can be set as heating, cooling, or off.

Input type: compatible with J, K, T, N, R, S, B, C, Pt2 thermocouples, RTD (2-wire or 3-wire) and 0-5VDC, 4-20mA process inputs.

Programming ability: Supports 24 step program curves, including four step types: set point (StPt), constant temperature (SoAh), jump cycle (JL), and end, and can achieve multi-stage temperature control.

Auxiliary functions: optional dual auxiliary output (alarm or time triggered event), set point/process value retransmission output, supports RS-422A/RS-423A/EIA-485 communication interface.

Data storage: Non volatile memory automatically saves all parameters, and data is not lost after power failure; Lithium battery backup operation parameters, with a service life of about 10 years.

Key specifications

Temperature range: thermocouple (-328 ° F~4200 ° F/-200 ° C~2315 ° C), RTD (-328 ° F~1112 ° F/-200 ° C~600 ° C), process input (-500~3500 units).

Accuracy: ± 0.1% ± 1 LSD of full scale (ambient temperature 77 ° F ± 5 ° F, rated voltage ± 10%).

Output specifications:

Solid state relay output: 0.5A@24-264VAC Optical isolation and zero crossing switching.

Mechanical relay output: 6A@120 /240VAC or 28VDC.

Process output: 0-5VDC/0-10VDC (minimum load 10K Ω), 4-20mA/0-20mA (maximum load 600 Ω).

Working environment: Temperature range of 32 ° F~149 ° F (0 ° C~65 ° C), humidity range of 0~90% (no condensation).


Installation and wiring process

Installation preparation

Panel Hole: Process panel holes according to size requirements (nominal 3.625 × 3.625 inches/92.08 × 92.08mm, thickness 0.06~0.25 inches/1.5~6.35mm).

Equipment fixation: Insert the controller housing into the opening, fix it from the back of the panel with the matching bracket, then insert the control chassis into the housing and lock it by rotating the front plate screw 90 ° clockwise (note that the screw should only be rotated 90 ° to avoid excessive force damage).

Wiring operation

Power wiring

Supports 120VAC or 240VAC power supply (50/60Hz universal, no adjustment required), requires connection to L1 and L2 power terminals and grounding terminals, and wiring must comply with the National Electrical Code (NEC) to avoid the risk of electric shock.

The power supply end needs to be connected in series with a fuse. When powered by 120VAC, the L1 end needs to be connected in series with a fuse. When powered by 240VAC, both the L1 and L2 ends need to be connected in series with a fuse.

Sensor wiring

Thermocouple: Use extension cords made of the same material as the thermocouple to avoid errors; If connecting non isolated external devices, an isolated thermocouple should be selected, with positive and negative terminals corresponding to terminals 7 (+) and 9 (-).

RTD: 2-wire RTD needs to short-circuit terminals 5 and 6, and 3-wire RTD needs to ensure that the resistance of the three extension wires is consistent (with the same wire diameter and material) to compensate for lead resistance errors (every 1 Ω lead resistance of 2-wire RTD will cause an error of about+2 ° C).

Process input: 0-5VDC input is connected to terminals 1 (+) and 3 (-), with an input impedance of 100K Ω; 4-20mA input requires short circuiting terminals 2 and 3, followed by connecting the positive and negative poles of the signal, with an input impedance of 249 Ω.

Output wiring

Output 1/2: Select the wiring method according to the model (solid-state relay, mechanical relay, DC switch, process output, etc.), refer to the wiring diagram of the corresponding model in the manual for details, and ensure that the load impedance matches (such as process output 4-20mA maximum load 600 Ω).

Auxiliary output: 6 auxiliary options are available (single relay, dual relay, relay+retransmission, etc.), wired according to the corresponding terminals (24-27) of the model, and the alarm/event output is a mechanical relay( 6A@28VDC /120VAC)。

Wiring precautions

Separation of strong and weak electricity: The sensor signal line (low power) is wired separately from the power line and output line (high power), with a minimum spacing of 12 inches (305mm) to avoid cross interference; When crossing, use a 90 ° crossing.

Shielding and grounding: Shielded cables are used for low-level signal lines, and the shielding layer is only grounded at the controller end; The system is grounded at a single point to avoid grounding loops, and all grounding terminals are connected to a unified grounding body.

Parameter Configuration Guide

Enter the configuration menu

Press the UP and DOWN keys simultaneously for 3 seconds to enter the Setup menu (displaying LOC parameters); Continue holding down the UP and DOWN keys under the LOC parameter to enter the calibration menu.

During the configuration process, press the MODE key to switch parameters, use the UP/DOWN key to adjust values, and if there is no operation for 5 seconds, it will automatically save and return to the previous level, or press the MODE key to manually save and switch.

Key configuration parameters (Setup menu)

Parameter Category Core Parameter Function Description Default Values

Security and Permission LOC Operation Permission Lock (Level 0-3): Level 0 Full Permission, Level 3 Only View Setpoint/Process Values 0

Input configuration In Select input type (such as J, K, RTD, 4-20, etc.) J or r

Temperature unit (° F/° C), only displays F when input as thermocouple/RTD

The upper and lower limits of the range for the rL/rH set point/process input, as well as the default range for scaling and retransmitting the output range of the sensor

Output configuration Ot1/Ot2 output 1/2 action type (ht heating/CL cooling/no off) ht/CL

HYS1/HYS2 output 1/2 ON/OFF switching hysteresis (effective when Pb=0) 3 ° F

Alarm and event Ot3/Ot4 auxiliary output 3/4 function (AL alarm/Ent event/PrOC retransmission) AL/PrOC

AL1/AL2 alarm type (Pr process alarm/DE deviation alarm) Pr

Programming configuration PtYP program type (ti time basis/ratE ramp rate basis) ti

GSD constant temperature deviation window (program pauses when out of range) 0 (disabled)

Power outage recovery Pout program recovery method after power outage (Cont continue/HOLD hold/Abrt abort) Cont

Communication configuration: bAUD baud rate (300-9600), only models with communication function display 1200

Addr device address (0-31), only displaying 0 under FULL protocol

Operation menu parameters (Operation menu)

Setpoint (SP): Adjust the control target value within the range of rL~rH, and display OFF (disable all outputs) when it is lower than rL.

PID parameters (Pb1/Pr2, rE1/rE2, rA1/rA2): proportional band, reset/integral, rate/derivative, automatically generated after automatic tuning, or manually adjustable.

Automatic tuning (Aut): Only output 1 for heating display, select tuning rate (1 slow/2/3 fast), and the controller automatically optimizes PID parameters after startup.

Alarm setting (A1LO/A1HI, A2LO/A2HI): Process alarm setting upper and lower limits (Pr type) or deviation alarm offset (dE type).

Program Programming and Running

Fundamentals of Programming

Program structure: Up to 24 steps, each step can be selected from four types: StPt (Setpoint Slope), SoAh (Constant Temperature Holding), JL (Jump Loop), and End (Program End), supporting multiple program concatenation (a new program can start after one End step).

Programming entrance: Select Prog=YES from the Operation menu to enter the Program menu. Press the StEP parameter to select steps (1-24), and press StYP to select the step type.

Detailed explanation of four step programming methods

1. Set point step (StPt)

Core parameters:

SP: Target Set Point (rL~rH).

Time basis (PtYP=ti): HOUr/Min/SEC, total time is the sum of the three (0-23h59m59s).

Rate basis (PtYP=rAtE): rAtE, temperature change rate (0-360 ° F/min or 0-200 ° C/min).

Ent1/Ent2: On/Off status of event 1/2, displayed only when Ot3/Ot4 is set to Ent.

Example: Step 1 is set to StPt, SP=75 ° F, Min=0, SEC=1, Ent1=OFF, achieving the initial setting of reaching 75 ° F within 1 second.

2. Constant temperature step (SoAh)

Core parameters: HOUr/Min/SEC (constant temperature duration), Ent1/Ent2 (event switch), no SP parameter (inherited from the previous set point).

Example: Set Step 3 to SoAh, Min=0, SEC=25, Ent1=On, achieve 25 seconds of constant temperature and trigger Event 1.

3. Jump loop step (JL)

Core parameters:

JS: Jump to the target step (must be smaller than the current step, cannot jump to itself).

JC: Jump count (0=infinite loop, 1-100=finite loop).

Example: Set Step 6 to JL, JS=2, JC=1, implement a jump to Step 2 and repeat once (execute Steps 2-5 twice in total).

4. End step

Core parameters: End (HOLD remains in the last state/OFF closes all outputs/OFFA closes control outputs, retains alarms).

Example: Step 4 is set to End, End=OFF. After the program ends, all outputs are turned off, and 'lower' displays' OFF '.

Program Execution and Control

Start program: In the non Setup menu interface, press the HOLD/RUN button, the RUN LED flashes, select the Start Step (StP), then press the HOLD/RUN button to confirm, the RUN LED stays on, and the program starts.

Pause and Resume: Press the HOLD/RUN button once to pause (RUN LED flashes); Press the HOLD/RUN key again to switch to the rESU parameter, and press the HOLD/RUN key to resume operation (only when the program has not been modified).

View operating status: Press the MODE key to switch parameters in the RUN menu, where you can view remaining time (HOUr/Min/SEC), current rate (rAtE), event status (Ent1/Ent2), etc.

Programming Example (Slope Constant Temperature Cycle)

Requirement: Initial temperature of 75 ° F → 25 seconds to rise to 100 ° F (event 1 activated) → 25 seconds constant temperature → 25 seconds to rise to 125 ° F (event 2 activated) → 25 seconds constant temperature → jump to step 1 and repeat twice → maintain the final state.

Step by step SP (° F) Time (minutes: seconds) Ent1 Ent2 JS JC End

1 StPt 75 0:01 OFF OFF - - -

2 StPt 100 0:25 ON OFF - - -

3 SoAh - 0:25 ON OFF - - -

4 StPt 125 0:25 OFF ON - - -

5 SoAh - 0:25 ON OFF - - -

6 JL - - - - 1 2 -

7 End - - - - - - HOLd

Tuning operation (automatic and manual)

Automatic tuning (recommended)

Applicable scenario: Quickly obtain optimized PID parameters after first use and system load changes.

Operation steps:

Enter the Operation menu and find the Aut parameter (displayed only when Ot1=ht).

Press the UP/DOWN keys to select the tuning rate (1 slow/2/3 fast, mostly 2 in most scenarios).

Press the MODE key to start tuning, and the lower display alternately flashes Aut and the current parameter. During tuning, the cooling output is turned off, and the heating output runs at 90% set point ON/OFF.

Complete tuning within 80 minutes, automatically save PID parameters, restore Aut to 0, and return to normal control mode; Modifying the set point during tuning will restart tuning. Press the UP/DOWN key to set Aut=0 to abort (restore the original parameters).

Manual tuning (precise optimization)

Operation steps:

Initialization parameters: Pb1=1, Ct1=5, rE1=rA1=0, CAL=0, Aut=0, set target temperature.

Proportional band (Pb1) adjustment: gradually increase Pb1 until the process temperature stabilizes (initial reset to 0, temperature may deviate from the set point).

Reset/Integral (rE1) Adjustment: Gradually increase rE1 until the temperature begins to oscillate, then slowly decrease until the temperature stabilizes near the set point.

Rate/Differential (rA1) Adjustment: Assuming rA1=1.00 minutes, raise the set point by 20-30 ° F. If the temperature is overshoot, increase rA1 (maximum 9.99) to avoid overshoot and slow response.

Cycle time (Ct1) adjustment: Optimized within the range of 1-60 seconds. It is recommended to choose a longer cycle time for mechanical contactors (to reduce wear) and a shorter time for electronic loads (to improve control accuracy).


Alarm and fault handling

Alarm function operation

Alarm type:

Process alarm (Pr): Based on the absolute temperature threshold (A1LO/A1HI), an alarm is triggered when the temperature exceeds the range.

Deviation alarm (dE): Based on the set point offset (such as+7 ° F/-5 ° F), the alarm threshold synchronously shifts when the set point changes.

Alarm status:

Non Locked (nLA): Automatically resets after the alarm condition disappears.

Lock (LAt): Manual reset is required (first eliminate the alarm condition, then press the HOLD/RUN button).

Alarm indication: The lower display alternately flashes "LO"/"HI" and the current parameter, the L3/L4 LED lights up, and the auxiliary output triggers (N.O. closed/N.C. open).

Common faults and solutions

Fault symptoms, error codes, possible causes, and solutions

The upper display shows "----", the lower display shows Er7 Er7 A/D overflow, the sensor is open/polarity reversed, check the sensor wiring (positive and negative poles, terminal contact), confirm that the In parameter is consistent with the sensor type

The upper display shows "----", the lower display shows Er1/Er2 Er1/Er2 sensor over/under range, A/D fault confirms that the sensor range matches rL/rH, checks if the sensor is damaged, and recalibrates the A/D

Pause during program operation - gSD deviation window enabled, adjust gSD value if temperature exceeds ± gSD range (increase window), check if heating/cooling system is normal, eliminate load interference

Communication failure - baud rate/protocol/address mismatch, wiring error. Confirm that bAUd (baud rate), Prot (protocol), Addr (address) in the Setup menu are consistent with the host, and check the communication line wiring (RS-485 requires corresponding A/B lines)

Large temperature measurement error - sensor wiring error, calibration offset, environmental interference. Reconnect and confirm sensor type, enter Cal menu to adjust CAL offset, check signal line shielding and grounding

Output unresponsive - Set the set point to OFF, configure the output type incorrectly, adjust the SP to the rL~rH range for load faults, confirm the Ot1/Ot2 parameters (ht/CL), check if the load impedance matches the output type, and test if the load is normal


Calibration operation (accuracy calibration)

Calibration prerequisite

Only enter under LOC parameters and require precise equipment (such as precision millivolt source, resistance box, voltage/current source, 4.5-inch multimeter).

Backup all parameters (Setup/Operation/Program) before calibration, turn off all outputs during calibration (except for process outputs), and automatically save calibration values when the RUN LED lights up.

Core Calibration Process (Taking Thermocouples as an Example)

Wiring: Connect the precision millivolt source to terminals 7 (+) and 9 (-), connect to AC power and ground.

Preheating: Power on for 15 minutes, enter the Cal menu (hold down the UP/DOWN key under LOC parameters), press the MODE key to select the tCL parameter.

Low range calibration: The millivolt source outputs 0.00mV, and after stabilizing for 10 seconds, press the MODE button.

High range calibration: J-type thermocouple outputs 50.00mV, R/S/B type outputs 16.035mV. After stabilizing for 10 seconds, press the MODE button.

Compensation calibration: Disconnect the millivolt source and connect the J-type reference compensator (32 ° F/0 ° C). After stabilizing for 10 seconds, press the HOLD/RUN button to exit the RUN mode and complete the calibration.

Other calibrations (RTD/process input/output)

RTD calibration: Use a 1K Ω precision resistance box to connect terminals 4-6, and input low/high resistance values according to the rLO/rHI parameters (refer to Table 7 in the manual).

4-20mA input calibration: Short circuit terminals 2-3, output 4.00mA (4A parameter) and 20.00mA (20A parameter) from the current source, and calibrate sequentially.

Process output calibration: Connect a multimeter and a matching resistor (such as 4-20mA connected to a 470 Ω resistor), adjust the output to the target value (such as 4.00mA/20.00mA) according to the O1LO/O1HI parameters.


Maintenance and Precautions

routine maintenance

Regular inspection: Check whether the sensor wiring is loose or corroded, whether the panel screws are tightened, and whether the heat dissipation is good.

Battery replacement: Lithium batteries (with backup operating parameters) have a lifespan of about 10 years. In case of abnormal Pout or Run parameters, they need to be returned to the factory for replacement.

Cleaning and maintenance: Wipe the panel with a dry soft cloth to prevent liquid from seeping into the interior of the equipment; Avoid using in damp, dusty, and corrosive environments.

Safety precautions

Disconnect the power supply before wiring, strictly follow NEC and local electrical regulations, and ensure reliable grounding (to avoid electric shock and interference).

The front plate screws should only be rotated 90 °, and excessive force should be avoided to avoid damaging the chassis locking structure.

Mercury relays are only suitable for resistive loads and are prohibited from being used for inductive loads (such as motors without buffering).

Calibration and maintenance must be carried out by professional personnel, and unauthorized disassembly of the equipment casing is prohibited (which may affect warranty).


  • Siemens 6SL3244-0SA01-1AA0 - SINAMICS G120 Control Unit
  • DANFOSS 175Z2688 - COATEDE CONTROLUNIT VLT5000
  • SIEMENS 6FM1721-3AA20 - Positioning Module
  • REXORTH VTS0605 PVAR S21 - Drive Module
  • BECKHOFF 2915-0000 - Control Module
  • COOPER EATON CGLine 400 40071347901 - CEAG CG Controller
  • SIEMENS 3UF5031-3AN00-1 - SIMOCODE DP Basic Unit
  • SIGMATEK DNC305 05-011-305 - Drive Controller
  • Multivac MV1 10249768 - Control Module
  • SCHNEIDER ELECTRIC MES114 59646 & 59645 - Circuit Breaker Accessory
  • CAMILLE BAUER CAPAX 44-580-0012 - Transmitter
  • HENGSTLER VT360P LS1/TOK - Encoder
  • BURKERT 8792 - 24V DC IP65 / IP67 Positioner
  • SENSOPART V10-OB-A1-W6 - Vision Sensor
  • ALLEN-BRADLEY 1762-L40BXB SER.C REV.J - MicroLogix 1200 Controller
  • HITACHI CPU22-02HC 33025801-2 - CPU Module
  • HITACHI AGH-0 33034810-2 - Control Board
  • PHILIPS AIH110 VER 1.0 - Control Module
  • BAUMULLER DO8000 - Drive Controller
  • B&R PS477 3PS477.9 Rev.C0 - Power Supply
  • ABB ALFA LAVAL 200-CISB - Communication Interface 2 x SatBus
  • Moeller MI4-570-TA1 - HMI Operator Panel
  • ABB ACH550-01-06A9-4+B055 - Variable Frequency Drive
  • ABB TPU2 3HNE00313-1 REV 12 - Teach Pendant Unit
  • Schneider Electric BRS368H130ABA - Stepper Motor
  • Foxboro FCM100E P0972ZA - I/A Series Communication Module
  • Siemens 6ES7 450-1AP00-0AE0 6ES7450-1AP00-0AE0 - Simatic S7 Version:04 Counter Module
  • Schneider Electric ATV320U07N4W - Altivar Machine Drive
  • Priva TouchPoint Flush V06:02 5060002 - Control Panel
  • Lenze ESMD402L4TXA - 4kW SMD Inverter Drive
  • Lenze ESMD402L4TXA - 4kW SMD Inverter Drive
  • Schneider Electric PM210 PM210MG - Powerlogic Power Meter
  • ASCOM U982-DB/1C U982 - Power Supply / Communication Module
  • DYADIC SYSTEMS SCN5-010-050-S03-NA - Servo Cylinder
  • Reliance Electric GMI-S04 - AC/AC CONVERTER 380/400V 50/60Hz 3.9/5.2A
  • Pro-Face GLC150-BG41-XY32KF-24V 3080060 PFXGLC150BDBP - Touch Screen HMI
  • ROFIN RSL TERMINAL V2 0185.01/03 - TERMINAL
  • HONEYWELL R7241E1077 - Burner Control / Amplifier
  • SEW MM22C-503-00 8241201 - 2.2kW Movimot Drive
  • Brand Digital III 50mL - Burette
  • Danfoss 195N0039 VLT2811PS2B20STR1DBF00A00C0 - 2.4kVA VLT Drive
  • SONY LG10-2 EK1 - Digital Gauge Indicator
  • EMERSON SKD3400750 - 7.5kW AC Drive
  • SIEMENS 6AV6 542-0AG10-0AX0 - MULTIPANEL HMI
  • TELEMECANIQUE ATV21HU55N4 - ALTIVAR21 5.5KW Variable Speed Drive
  • MITSUBISHI A985GOT-TBA-EU - GOT900 Touch Screen HMI
  • SCHNEIDER LXM32AD30N4 - Lexium 32 Servo Drive
  • SICK PSR01-1501 M20Z-02550A122 - Safety Laser Scanner
  • GECMA CHALLENGER 15-2-FMO - LITE TOUCH Monitor
  • Uniop EK02 6ZA982 - HMI Operator Panel
  • TELEMECANIQUE ATV18U54M2 - SQUARE D ALTIVAR 18 3kW Drive
  • Schneider Electric ATV312HU75S6 - 7.5kW Altivar 312 Drive
  • Siemens 6GK7243-5DX30-0XE0 6GK7 243-5DX30-0XE0 - Communications Processor
  • Schneider Electric LV432455 VIGI630 - 3POLE Earth Leakage Module
  • Rexroth PSI 6100.750 L1 R911170694-107 - frequency inverter / inverter
  • SWEDISH MICROWAVE AB Ku-Band BDC 138010-45-D0 - Block Downconverter
  • METTLER TOLEDO IND429 IND429-BB30 - Weighing Terminal
  • Siemens 6SL3210-5HE10-4UF0 - Sinamics V90 Servo Drive
  • B&R X20CP0482 Rev.D0 - X20 CPU Module
  • Mitsubishi FR-E720S-110SC-EC FRE720S110SCEC - 31A~11A Drive With Filter
  • ABB ACH580-01-026A-4 - Variable Frequency Drive
  • Siemens 6SL3210-1KE13-2AP1 - SINAMIC G120CDP 1.1kw Drive
  • Schneider Electric TM250D 4P3D LV431440 - Compact NSX250 Circuit Breaker
  • RELIANCE ELECTRIC GD.722.81.00-A 802288-74C - MAXITRON Servo Control Card
  • Uniop EK02 6ZA982 - HMI Operator Panel
  • Siemens 6SE9113-7JA13 - MICRO MASTER Junior 1.5kW Inverter
  • Mitsubishi FR-E720S-110SC-EC FRE720S110SCEC - 31A~11A Drive with Filter
  • Johnson Controls FEC2621 MS-FEC2621-0 - Field Equipment Controller
  • BENDER IR475LYT-429 - A-ISOMETER Insulation Monitor
  • Berger lahr D550 RS15 22.550-00-30b - Stepper Drive
  • Rexroth PSI 6100.750 L1 R911170694-107 - Frequency Inverter / INVERTER
  • KOYO 205 D2-06B-1 D2-240 H2-ECOM D2-08ND3 F2-08TRS - DIRECT LOGIC PLC WITH MODULE
  • TELEMECANIQUE ATV18U54M2 ATV18U54M - SQUARE D ALTIVAR 18 3kW Drive
  • Lenze 471-E1.D - Board / Controller Speed
  • Mitsubishi FR-A740-00038-EC - Frequency Inverter
  • Johnson Controls IOM3723 MS-IOM3723-0 - Input/Output Module
  • CURTIS 1238-5602 - AC Motor Controller
  • FOXBORO P0912XX REV.A - 220VAC Power Supply
  • Siemens 6SE9113-7JA13 - MICRO MASTER Junior 1.5kW Inverter
  • Mitsubishi FR-A740-00038-EC - Frequency Inverter
  • KOYO 205 D2-06B-1 D2-240 H2-ECOM D2-08ND3 F2-08TRS - DIRECT LOGIC PLC WITH MODULE
  • AUTZ M406D-00101 - Servo Motor
  • Lauer PCS095 PG095.508.BB - Operator Panel
  • ABB SCOP45SB/DX232 - SattCon OP45 SB Operator Panel
  • SEW Eurodrive MCH42A0030-5A3-4-00 MDX60A0030-5A3-4-00 - 4.8kVA Movidrive Inverter
  • BENDER IR475LYT-429 - A-ISOMETER Insulation Monitor
  • Johnson Controls FEC2621 MS-FEC2621-0 - Field Equipment Controller
  • Johnson Controls IOM3723 MS-IOM3723-0 - Input/Output Module
  • Berger lahr D550 RS15 22550-00-30b - Stepper Drive
  • SIEMENS 6FX1120-4BD03 6FX11204BD03 5702049304.00 E-Stand: A - Sinumerik Module
  • Allen-Bradley 1771-NIV B - HIGH RESOLUTION ISOLATED ANALOG SERIES Module
  • HONEYWELL XFC2D06001 - Flow Computer / Controller
  • Contraves Varidyn Compact ADB 380.90M - DC Drive 380v - 400v 90A 50kVA
  • Red Lion Control GEM52000 - Control Module
  • Siemens 6ES5 955-3NC13 - modular power supply TYPE:DIN41752
  • Danfoss ICV50 G20Mn50T / 027H5200 - Valve zaw
  • Eberle PLS508 P-814 / 2X EA-88 / A-812 / MT-81 / S-11 - PLC with Modules
  • Siemens 6ES7 314-6CF01-0AB0 6ES7314-6CF01-0AB0 - SIMATIC CPU314C-2 DP
  • EBERLE EM-525-87 EM52487 - ICE DETECTOR BASE UNIT
  • Telemecanique / Schneider TSXRKZ02 - TSX Micro automation plus 7module
  • B&R 5DLSDL.1001-00 - Display Link Receiver
  • Siemens 6FX1120-4BD03 6FX11204BD03 5702049304.00 E-Stand: A - Sinumerik Module
  • ALLEN-BRADLEY 1771-NIV A - HIGH RESOLUTION ISOLATED ANALOG SERIES Module
  • ALLEN-BRADLEY 1771-NIV B - HIGH RESOLUTION ISOLATED ANALOG SERIES Module
  • Contraves Varidyn Compact ADB 380.90M - DC Drive 380V - 400V 90A 50kVA
  • Contraves Varidyn Compact ADB 380.90M - DC Drive 380V - 400V 90A 50kVA
  • Ropex RES-202 - Resistron Temperature Controller
  • HONEYWELL XFC2D06001 - Flow Computer / Controller
  • Telemechanics ATV452U40 - DIMMER ALTIVAR5 SERIES 452 4kW 5HP Frequency Inverter
  • VEGA VEGAPLUS61 PS61.XXAGPHAMAX - Radar Level Sensor
  • BRANSON ULTRASONIC TRANSDUCER - Ultrasonic Transducer
  • Danfoss ICV50 G20Mn50T / 027H5200 - Valve Valvola Zaw
  • Schneider Electric 2001549/1 GALAXY PW 5102851200 NT07 - panler card
  • REXROTH VT3006-36 A - Proportional Valve Amplifier
  • Allen-Bradley 1746-OBP16 SERIES:C - SLC 500 OUTPUT MODULE
  • SCHNEIDER LXM32MD12N4 - Lexium 32 Servo Drive
  • Schneider Electric ATV630U22N4 - 2.2KW Altivar Process Drive
  • Allen-Bradley 1746-OBP16 SERIES:C - SLC 500 OUTPUT MODULE
  • Vanderlande 0E2550-00002... - Bagtrax Integrated Power Module 400V 32A
  • B&R X20CP0410 Rev.D0 - X20 CPU Module
  • VANDERLANDE 0E2550-00002 02EDD2B0100 - BAGTRAX Integrated Power Module 400V 32A
  • Rexroth R061205010 - Linear Bushing / Bearing
  • INDRAMAT TVM1.2-50-220/300-W0-220/380 - Power Supply Module
  • Vanderlande 0E2550-00002... - Bagtrax Integrated Power Module 400V 32A
  • HOMAG KEB 07F5S1A-YA00 09E5T60-1001 - Combivert Inverter WITH KEYPAID AND FILTER
  • Siemens 3RW3047-1BB14 - Soft Starter
  • Sumitomo AF-500 AF502-A40 - 0.4kW Transistor Inverter
  • Sumitomo AF-500 AF502-A40 - 0.4kW Transistor Inverter