+086-15305925923

K-WANG

Service expert in industrial control field!
NameDescriptionContent
Adequate Inventory, Timely Service
pursuit of excellence 
Ship control system
Equipment control system
Power monitoring system
Current position:
新闻动态
newS
   
Brand

MKS Type T3B Butterfly Valve (with DeviceNet Interface)

From: | Author:Wang | Time :2025-09-23 | 342 visit: | 🔊 Click to read aloud ❚❚ | Share:

MKS Type T3B Butterfly Valve (with DeviceNet Interface)

Security Information

Symbol Definition

The symbol "Warning" in the manual indicates a potential danger of injury to personnel; CAUTION "indicates the potential danger of product damage; NOTE "indicates important information that requires special attention.

Symbols on equipment: including power on/off (IEC 417 No.5007/5008), grounding (IEC 417 No.5017/5019/5020/5021), AC/DC (IEC 417 No.5031/5032/5033-a), Class II equipment (IEC 417 No.5172-a), three-phase AC (IEC 617-2 No.020206), hand compression risk (ISO 3864), electric shock risk (ISO 3864 No.B.3.6), etc. The manual provides detailed explanations of the meanings of each symbol in table form.

Safety operation standards

Mechanical safety: Before the valve is fully integrated into the system, there is a risk of injury from moving parts. Keep away from the valve opening and do not insert objects into openings that may come into contact with moving parts; Cut off the electrical and pneumatic power supply of the valve before operation.

Component and modification restrictions: The use of substitute components or unauthorized modification of valves is prohibited. Repairs must be sent to the MKS calibration service center to ensure that safety functions are intact; Only qualified personnel are allowed to perform component replacement and internal adjustments.

Use of hazardous materials: If hazardous materials are used, safety regulations must be followed, and valves must be thoroughly purged if necessary to ensure compatibility between the materials in contact with the valves (including sealing materials); Blowing should be carried out under a fume hood and protective gloves should be worn.

Environmental and pressure requirements: Prohibited for use in explosive environments (unless specifically certified); Use connectors that meet specifications and are compatible, and assemble and tighten them according to the manufacturer's instructions; Check the sealing of vacuum component connections; The operating pressure shall not exceed the rated maximum pressure (refer to product specifications); The pressurized gas source system requires the installation of rupture discs; Prevent pollutants such as dust and metal shavings from entering the equipment; Keep away from valve openings during operation.

Product Overview

Core Composition and Function

Components: T3B butterfly valve consists of a throttle valve (with motor board electronic housing), microprocessor, drive circuit (no separate controller box required), DeviceNet communication interface, and analog output reflecting pressure or valve position. The valve is controlled by digital values sent through the DeviceNet network.

Control principle: Based on digital pressure/position control algorithm, guide the valve to the appropriate position for pressure or position control. The pressure or position setting value can be sent through digital DeviceNet command; Directly read the control pressure signal from the MKS Baratron pressure sensor, and all operation settings are controlled through the DeviceNet protocol.

Data storage and anti-interference: When the power is turned off, the calibration constant is saved in non-volatile memory, and it can run without recalibration after re powering on; Adopting a metal casing, optimized internal design, surge/ESD suppression network, and RFI filtering (all inputs and outputs) to enhance resistance to radio frequency interference and electromagnetic noise; When using fully metal braided shielded cables with both ends correctly grounded, they comply with the EU CE certification testing standards.

key parameters

Power Requirements: Requires 24 VDC @ 3 Amp input voltage (powered through a power connector); If a heating pressure sensor is used and powered by a valve, the sensor power demand needs to be added, and the valve can provide a maximum current of 750 mA (total of high and low sensors) for the heating pressure sensor.

Control range: The pressure control range is 0.5% -100% of the sensor range, and the position control range is 0 ° -90 °; The repeatability of the controller is ± 0.1% of full scale (FS).

control mode

Pressure control: The valve moves to maintain the target pressure (set value), supporting two algorithms: Model Based Control and PID Control.

Model based control: During the control cycle, the algorithm calculates the next valve position based on the current pressure, position, and set value, requiring knowledge of system parameters such as chamber volume and valve conductivity to optimize control; The relationship between chamber pump speed and valve position is obtained through the "LEARN function" (based on actual working conditions such as sensor type and chamber volume), which is usually executed once during initial installation. The process includes setting the chamber volume, selecting the volume estimator switch, configuring the pressure sensor range, setting the learning flow rate, and starting learning (lasting about 45 seconds, maintaining stable flow rate).

PID control: The set value optimizes the response through two parameters, Phase and Gain, and the default value can be adjusted; The response speed of phase control pressure to changes in the set value is too fast, which can lead to slow response or oscillation, and too small, which can cause overshoot and oscillation; Gain enables the controller to track the set value and minimize steady-state error. Excessive gain can cause overshoot, while insufficient gain can result in slow response.

Position control: The valve moves to the target position (set value) without feedback signal. The encoder can provide the user with the required feedback, but it is not used for closed-loop control.

Trip Points

Basic configuration: Includes 4 software trip points that can be adjusted through digital communication commands. The status changes when the pressure is above/below the set value; The trip point can be configured to monitor pressure or valve position (any combination), two of which can be mapped to hardware relays through auxiliary connectors.

Key parameters:

Hysteresis: default 10%, adjustable through digital commands, used to compensate for system noise and avoid "relay jitter", ideal value close to but not less than peak to peak noise.

Delay: The alarm status of the trip point needs to be continuously set for a set time (0-10000 ms, default 0) before reporting "ON". Different delay values can be set for different trip points (monitoring controller object pressure properties, trip point object valve position properties).

Direction: default "low" (when the pressure is lower than the set value, the trip point is activated, the LED lights up, and the pressure needs to be higher than the hysteresis value to release), can be changed to "high" through digital commands (when the pressure is higher than the set value, it is activated, and the pressure needs to be lower than the hysteresis value to release).

Top panel component

Connectors: Includes 5-pin miniature digital communication connector (DeviceNet communication interface), 25 pin D-type female auxiliary connector (sensor power supply, alarm relay output, RS-232 communication), 9-pin D-type male external power connector (valve power supply), and 2 15 pin D-type female analog sensor connectors (high/low sensor power supply and pressure input).

Indicator lights and switches:

Valve position indicator light: "OPEN" (red) lights up to indicate that the valve is fully open, and "CLOSE" (red) lights up to indicate that it is fully closed.

Manual valve switch: a button type switch that can manually drive the valve to the open/close position.

Trip point indicator light: It lights up green when the trip point is activated.

DeviceNet status light: including module status light (green/red dual color) and network status light (green/red dual color), the power startup sequence complies with the ODVA DeviceNet specification, the module status light is always green to indicate normal, and the red to indicate unrecoverable fault; The green constant light of the network status indicates that the communication link is normal and a connection has been established, the green flashing indicates online but no connection, and the red constant light indicates a serious link failure.

Configure switch:

Baud rate switch: 4-bit rotary switch, optional PGM (read from non-volatile memory), 125 Kb, 250 Kb, 500 Kbps.

MAC ID (Node Address) Switch: Two 10 bit rotary switches, set the node address (0-63), with ten bits on the left (MSD) and one bit on the right (LSD); When the address is greater than 63, it is equivalent to the "PGM" position.

Installation Guide

Unpacking and Inspection

Unboxing process: MKS uses professional packaging to ensure that the equipment is in good condition. After receiving it, it is necessary to check whether the valve is damaged, the connector is damaged, and other transportation damages are present. Do not discard the packaging materials until safety is confirmed.

Problem handling: If damage is found, immediately notify the carrier and MKS; If you need to return the device, you need to first obtain the ERA number (device return authorization number) from the MKS service center. The MKS calibration service center list is listed on the inside of the back cover of the manual; Only qualified personnel are allowed to install and debug, and ESD protection and operating procedures must be followed.

Standard accessories: including T3B unit, T3B with DeviceNet interface user manual, MKS T3B/T3P with DeviceNet interface supplementary manual (No. 138993-P1, installation needs to refer to this supplementary manual).

Interface cable requirements

Cable specification: Full metal braided shielded cable (correctly grounded at both ends) is required to comply with CE certification; MKS provides a full range of cables, and if self-produced, they must meet the following requirements: shielding layer covering all wires (insufficient aluminum foil or spiral shielding effect may affect compliance); The metal shell of the connector is in direct contact with the entire circumference of the cable shielding layer (to avoid reduced shielding effect caused by flying wires); Good contact between the connector and the controller housing (approximately 0.01 ohms, with grounding surrounding all wires); Consider voltage level, wire I ² R heating, IR voltage drop, capacitance and inductance of fast signal cables, and internal wire shielding requirements.

Connection method: Two shielding cable connection methods are provided (priority is to use cable clamps to fix the shielding layer, and if there is no cable clamp, the shielding layer can be twisted and fixed with washers), ensuring that the shielding layer is grounded and the wire is in contact with the shell.

Installation environment and location

Environmental requirements: The working temperature range is 20 ° C-40 ° C, the working humidity is 0% -95% (non condensing), and the storage temperature range is -20 ° C-80 ° C.

Installation position: It can be installed on the vacuum exhaust pipeline (with suitable joints). To achieve optimal pressure control, the pressure sensor and T3B should be as close to the process chamber as possible to reduce the time constant; The connecting pipe between the sensor and the chamber should be less than 6 inches and have a diameter of not less than 1/4 inch. If it exceeds 6 inches, a larger diameter pipe should be used to compensate for the conductivity loss.

System configuration and electrical connections

Typical configuration: The system includes a DeviceNet network host (sending set values, receiving pressure/position/diagnostic data), a 24 VDC valve power supply, a sensor power supply (optional ± 15 VDC), a T3B unit, an analog Baratron sensor, and an alarm relay output that can be connected to external alarm devices.

Grounding requirements: If power is taken from the DeviceNet network, it must comply with the grounding requirements of the ODVA DeviceNet specification (Volume I).

Definition of connector pins:

Digital communication connector (5-pin): 1-pin (Drain), 2-pin (V+), 3-pin (V -), 4-pin (CAN_S), 5-pin (CAN_L).

Auxiliary connector (25 pins): includes receive data (RX), send data (TX), pressure output (A Out), position output (A Out), 2 sets of relays (normally open/normally closed/common terminal), valve open/closed status (digital output), interlock (digital input), analog ground, digital ground, chassis ground, etc. Pins 11-13 are related to analog signals, pins 14-19 are relays, pins 20-22 are digital status and input, and pins 24-25 are ground.

Analog sensor connector (15 pins, with the same high and low sensor pins): 2-pin (pressure input+), 5-pin (sensor power return), 6-pin (-15 V), 7-pin (+15 V), 12 pin (pressure input -), 14 pin (+24 V power output), 15 pin (chassis ground), with no other pins connected.

External power connector (9-pin): 1-2 pins (+24 V input), 3-4 pins (24 V return), 5-pin (+15 V auxiliary input, for instruments), 6-pin (15 V return), 7-pin (-15 V auxiliary input, for instruments), 8-pin (reserved), 9-pin (chassis ground).

startup process

Power on sequence: First supply power to the DeviceNet network, then supply power to T3B; When powered on, the device checks the communication link, EEPROM, and RAM internal diagnostics, and the results are indicated by the top status LED (color and flashing status).

LED startup sequence: The module status LED flashes alternately green and red for about 0.25 seconds each before turning green; The network status LED flashes alternately in green and red for about 0.25 seconds each before turning off; After initialization is completed, the module status LED remains constantly green; When there are no other network devices, the network status LED remains off; When there are other devices, the network LED flashes green during repeated MAC checks and before establishing a connection.

Preheating time: After installation and power on, the preheating time of the controller is less than 1 minute.

Operation Guide

Operation Mode

User mode: default power on mode, which is the normal operation mode.

Calibration mode: used to access specific calibration and operating parameters. The device functions are the same in both modes, but network access to certain attributes may be restricted (refer to the object attribute table in the supplementary manual for specific permissions).

Communication Configuration

Baud rate and MAC ID settings: can be set through software (DeviceNet protocol network command) or manually (top rotary switch). When powered on, if the switch is in the "PGM" position, the baud rate/address can be read from non-volatile memory, and the network can modify parameters. Changes in the switch position require a power outage and restart to take effect; If the switch is not in the "PGM" position and the switch value is directly read, the network modification request is rejected and an error code of "Attribute_Cot_Settable" is returned.

Communication specifications: Supports 125/250/500 Kbps baud rates; The network topology is linear (trunk/branch), with power and signals sharing the same cable; Supports up to 64 nodes; Explicit message communication delay<50 milliseconds (average<25 milliseconds), I/O polling message delay<4.5 milliseconds (average<1.5 milliseconds); Equipped with module status (green/red) and network status (green/red) LED indicators.

Core operational functions

Parameter setting and monitoring: Through the DeviceNet network, set values (pressure/position), valve direction (forward/reverse), pressure values and units, valve position, trip point values/hysteresis/delay/status can be set and reported, monitoring system status, reporting operating time, and setting valve soft start; Storage device identification information (manufacturer information, model serial number, factory calibration data, software and hardware version number).

Maintenance and troubleshooting

routine maintenance

Routine inspection: No special maintenance requirements, only correct installation and operation are required; Regularly check for cable wear and signs of shell damage; Regularly wipe the surface of the equipment with a damp cloth.

Equipment return: If you need to return the MKS for repair, you need to obtain the ERA number first; The returned equipment must be free of harmful, corrosive, radioactive, or toxic substances.

troubleshooting

General faults:

When the valve is closed, the conductivity does not meet the standard: it may be due to wear or damage of the baffle seal, and the factory needs to be contacted to obtain a seal replacement kit.

25 pin I/O connector interlock missing (22-24 pins): Connect pin 22 to pin 24 or verify external interlock wiring.

Valve not open/closed: Check if the 24V power supply is properly connected to the valve terminal or if the valve is faulty (need to be sent to MKS for repair); Simultaneously confirm the interlocking wiring.

Pressure control failure (report full range/low/zero): Sensor disconnected (reconnect) or pressure gauge not powered (check power supply).

Pressure control oscillation/poor effect: PID mode needs to optimize gain and phase, and the model base mode needs to relearn the pump speed curve; The control offset may be due to high grounding impedance (judged by MKS valve GUI as a debugging or grounding issue); The control difference within a specific pressure range may be due to incorrect intersection point settings (configuring and installing pressure gauges for intersection pressure).

Unable to achieve target pressure: The baffle seal is worn or damaged (replace seal).

Report negative/abnormal pressure: pressure gauge not zeroed (zeroing), no power supply (checking power supply); Pressure gauge full range setting error (configured with correct range), voltage range error.

Pump speed learning failed: The pressure gauge is not connected to the high range (retry after connecting to the high range).

Communication malfunction:

RS-232 communication failure: Check baud rate, data bits, checksum, CR-LF settings, or cable wiring issues.

DeviceNet communication failure: Check MAC address and baud rate settings, or network power supply for normal operation.

Meaning of fault indicator light:

Module status LED: evergreen (normal), flashing green (visual indication), constantly red (non recoverable fault), flashing red (minor fault, such as interlock not enabled), off (no power supply), alternating red and green (self check).

Network status LED: evergreen (communication link normal, online and connection established), flashing green (online but no connection established), constantly red (severe link failure, such as repeated MAC address or bus shutdown), flashing red (connection timeout), alternating red and green (initialization), off (not online, such as incomplete repeated MAC check or no power supply); When using a single device network, it is normal to keep it off until there is no connection.

Fault type:

Minor faults: MAC ID or baud rate switch changed during operation, safety interlock opened (only T3P gas interlock), controller error reported through abnormal status bit (refer to supplementary manual), equipment remains in operation.

Serious malfunction: During self inspection, EEPROM hardware or RAM memory issues were detected, the module status LED is constantly red, and the device has entered a serious malfunction state, unable to respond to network services. MKS needs to be contacted.


  • Metso XZB10025-011T12 - Moog Valve 9650962700
  • Metso XZB10025-010T12 - Moog Valve 9650965300
  • Metso-SP Transmitter Cable - Operating Unit with 10m Cable
  • Harkila Metso Hybrid - Hunting Jacket Willow Green
  • Metso ND8221/S1 - Neles Valve Positioner
  • Metso METSO10119 - ScreenCheck Component
  • Metso LK-2025 - Linkage Kit
  • Metso A416733 - IQweight External Air Gap Temperature Sensor
  • Metso RKC22MT - Automation Component
  • Metso A413281 - Automation Board
  • Metso LCP9HLY - Stainless Steel Enclosure
  • Metso NP704S/B1S1 - Pneumatic Positioner with I/P Converter
  • Metso BAH3 - Slurry Seal Type
  • Metso A413531-03 - PLC Module Chassis Rack
  • Metso P4610004 - MCAI Communicator Controller
  • Metso QN2AN03HDM - Quartz Valve Positioner Stonel
  • Metso RKW-352-XZ - Automation Component
  • Metso A4300081 - Kajaani LCD Display
  • Metso A428026 7B - Kajaani Rectifier Unit 1
  • Metso 202218 - Kajaani Sensor Power Supply SR 902660
  • Metso 9150 316SS CSTL - Jamesbury 150-2" BN50 Valve
  • Metso 81806 - IOP101 Module
  • Metso STOM000272 - Paper Bushing CR38
  • Metso 1975413 - Chain Hoist Links
  • Metso IMO G053-191597 - Minor Seal Kit
  • Metso VAL0087418 - Cylinder Valmet NTS6LV
  • Metso A413061 - DMU Board VPA 420355-4B
  • Metso P2620-80/25-100 - Automation Component
  • Metso VAL0035292 - Automation Component
  • Metso A413721 - Automation Component
  • Metso ST600 - Automation Component
  • Metso P4500001 - Automation Component
  • Metso SDBX/RA2 - CAT x KVM Extender
  • Metso D201126-DI8 - Digital Input Module
  • Metso D201189L - AI8H Analog Module
  • Metso NA004418 LK1016 - Wafersphere Actuator Mounting Bracket
  • Metso RKN172MTT - Repair Kit
  • Metso MM0311584 - Air Filter Kit RadialSeal
  • Metso 181517 - IOP301 Isolated Analog Input Module
  • Metso RAU3906506 - Automation Component
  • Metso 181208 - IOP332 Digital Input Module
  • Metso A413760 - AIF2C PCB Module
  • Metso 006 1089 36 - Shaft Bearing Seal
  • Metso A413046 - Automation Component
  • Metso VKJ650 - Automation Brake Component
  • Metso LK-1875 - Linkage Kit
  • Metso D201193L - FI4S24 Frequency Input Module
  • Metso D200533 - BIU82 Binary Input Module
  • Metso 500838-M1 - Impeller Pump Release Collar Assembly
  • Metso 2.00SB2ALUS19A - Pneumatic Cylinder 1.375 Stroke
  • Metso D201351 - RES Reserve Module
  • Metso A416100 - IQMoisture Spare Part Kit Halogen Lamp
  • Metso Slurry Pump - Back Liner
  • Metso 7088010042 - Bronze Lantern Ring
  • Metso IMC-101-M-SC - Industrial Media Converter
  • Voith S1-S1-CAM-ENCL - Metso Pump Cmare Housing & Bracket
  • Metso A4430726V1.1 - Kajaani Connection Box CI 4-9-10
  • Metso A413016 - NCU2 PLC Board
  • Metso D202213P - MBMT80 Base
  • Metso A413135 - AOU-4 Analog Output Board
  • Metso NP 724A - Pneumatic Valve Positioner
  • Metso A413246 - Automation Controller Module
  • Konaflex VKJ-650 - Disc Brake Set Pair
  • Metso WIN3096535D - Core Chuck
  • Metso D201380 - MBR Base with IBC & IPS
  • Metso D202213L - MBMT80 Base Module
  • Metso 181571 - IOP337 PLC Module
  • Metso MF0588336 - Main Hydraulic Filter
  • Metso 181504 - IOP303 RTD Input Module
  • Metso A413240 - PIC2 Board
  • Denver 566534PS - Case Liner Gland Side SRL Frame 2
  • Metso 181508 - IOP322 Digital Input Module 120V
  • Metso 181520 - IOP351 Relay Output Module Form A/B
  • Metso 181220 - IOP351 Relay Output Module
  • Metso A413150 - BOU 8 Binary Output Module
  • Metso 128400-M1 - Impeller
  • Metso D201379 - MBB Base with IBC & IPS
  • Metso 205181 - T/B MTD PRWSW Assembly
  • Metso QPX1C/K15 - Jamesbury Quadra-Powr X Actuator Valve
  • Harkila Metso Winter - Hunting Jacket Willow Green
  • Metso NE724A/A-L - Electro-Pneumatic Positioner
  • Metso PACP-100-80-31 916 - Automation Component
  • Metso 81814 - Automation Component
  • Metso ER-12-01-M-CT - Automation Board
  • Metso ELO24 - Automation Board
  • Metso A413000 - Valmet Neles CPU PLC Board
  • Metso XL-2213-0525 - Mainframe Bushing
  • Metso D100097 - ECR Extension Module
  • Metso 804511 - Filter Housing Assembly
  • Metso S420154 - Automation Rack Chassis
  • TRICONEX 2211 Baseplate for 3211 I/O Module Triconex System Component
  • TRICONEX CM3201 Communication Module Industrial Control System
  • ABB 560CMR01 Communication Module RTU560 Control Unit
  • Metso 1NWH155 - Ethernet Hub
  • Metso T22PO 103913968 - Sampler Valve (LF02C)
  • Metso EDS-516A-MM-SC - Ethernet Device Switch
  • Metso MC4-16-4 - Brass Rotary Oscillator Drive
  • Metso XT03CWTAS6SJHA - 3" Ball Valve Assembly
  • Metso 181226 - Digital Input Module
  • Metso RAU4E62037 - Valmet Posieve Plus Measuring Head
  • Metso VT-223779/2 - Sealing Housing SD42"B
  • Metso J2029 010 10722 - Circuit Board
  • Metso D202038-ACN-PO - Automation Component
  • Metso NE724/S1-CE01 - Electro-pneumatic Valve Positioner
  • Metso M851004 - CPU Module T194-v0
  • Metso Trucker Hat - Finland Golf Ball Cap
  • Metso DN6-50 - Jamesbury 1/4" Valve
  • Metso B1CU6/20L - Pneumatic Actuator
  • Metso B1CU6/25L - Pneumatic Actuator
  • Metso A416040-09 - Power Rating Unit 28 VDC
  • Metso A4300018B - Central Unit Communication Interface
  • Metso ND9106HN/K05 - Intelligent Valve Controller
  • Metso D200537 BOU83 - Binary Output Model 02
  • Metso A413111 TIU61 - Temperature Input Unit Board
  • Jamesbury 730S313600XTZ2 - 1" Flanged SS Ball Valve
  • Metso HG4A12SH0 - Pressure Transmitter with Coupling
  • Metso A413146 BIU 4 - Binary Input Module
  • Metso DDC7940-D201139 - Controller Module
  • Metso Square Flange - Discharge Flange for Slurry Pump
  • Metso A413177 - Automation Board
  • Metso BOU82 D200536 - Binary Output Module
  • Metso D200619 - Personality Module
  • Metso RKN50MT - Actuator Repair Kit
  • Metso IOP335 - Counter Timer Module
  • Valmet IOP341R 181560 - Positioner Module
  • Metso A413150 - Power Module
  • Metso RKN-184XTZ - Actuator Repair Kit
  • Metso Flinger Seal - Slurry Pump Component