K-WANG
ABB FOUNDATION Fieldbus Linking Device LD 800HSE EX
ABB FOUNDATION Fieldbus Linking Device LD 800HSE EX
The FOUNDATION Fieldbus Linking Device LD 800HSE EX is registered according to class 42c of the HSE profile, therefore providing the following functions:
• Identification of devices connected to the H1 links
• Configuration of connected H1 devices through System Management and Network Management via HSE
• Access to the function blocks of connected H1 devices via HSE
• Republishing of process data between H1 links
• Republishing of process data from H1 to HSE and vice versa
• Distribution of alarms and events sent by H1 devices
General
• Linking device according to class 42c of FF HSE profile
• Connects up to four H1 links to an HSE subnet
• Certified for decentralized installation in hazardous areas Zone 2 / Division 2 - cULus Class I, Division 2, Groups A, B, C, D
- IECEx Ex nA IIC T4 Gc
- ATEX II 3G Ex nA IIC T4 Gc
• G3 coated acc. to:
- ANSI/ISA7104
- EN 60068-2-60
Gateway
• Identification of devices connected to the H1 links
• Configuration of connected H1 devices through System Management and Network Management via HSE
• Access to the function blocks of connected H1 devices via HSE
• Republishing of process data between H1 links
• Republishing of process data from H1 to HSE and vice versa
• Distribution of alarms and events sent by H1 devices
HSE
- System Management Agent
- Network Management Agent
- Server providing object access to H1 devices
- Publishing/Subscribing of process data from/ to H1 devices
- Distribution of alarms and events sent by H1 devices
- Time synchronization via SNTP
- IP address configurable via integrated web server
Technical Data
Power Supply
Supply voltage:24 V DC (+− 20%)
Current consumption:typ. 200 mA
Power dissipation:typ. 4.8 W
Mechanical Properties
Dimensions:(length x height x width) 47 x 131 x 111 mm,
Weight:approx. 0.4 kg