K-WANG



< System board for HIMA, HIMax
< For 32-channel card X-DI 32 02 (DI)
< For 32 modules
< Recommended modules: HiC2831 (DI), HiC2853 (DI)
< 24 V DC supply
< Hazardous area: spring terminals, blue
< Non-hazardous area: HIMA system connector, 96-pin
HIMA X-DI3202 Termination Board
< System board for HIMA, HIMax
< For 32-channel card X-DI 32 02 (DI)
< For 32 modules
< Recommended modules: HiC2831 (DI), HiC2853 (DI)
< 24 V DC supply
< Hazardous area: spring terminals, blue
< Non-hazardous area: HIMA system connector, 96-pin
Fault indication output
Connection XG2: terminals 5, 6
Output type volt-free contact
Switch behaviour no fault: relay contact closed
power supply fault: relay contact open
module fault: relay contact open
Contact loading 30 V DC, 1 A
Indicators/settings
Display elements LED PWR1 (termination board power supply), green LED
LED PWR2 (termination board power supply), green LED
LED FAULT (fault indication), red LED
- LED lits: power supply fault
- LED flashes: module fault
LED Run, green LED
- The HIMax I/O module is supplied with power and is connected to the Termination
Board (FTA) via a system cable.
LED Field, red LED
- The HIMax I/O module detects faults in the connection between HIMax I/O module
and Termination Board (FTA).
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibility NE 21:2017
For further information see system description

Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Mechanical specifications
Degree of protection IP20
Connection
Field side explosion hazardous area: spring terminals , blue
Control side non-explosion hazardous area: HIMA system connector, 96-pin
Supply pluggable spring terminals , black
Fault output pluggable spring terminals , black
Core cross section spring terminals: 0.25 ... 1.5 mm2
(24 ... 16 AWG)
Material housing: polycarbonate, 10 % glass fiber reinforced
Mass approx. 1270 g
Dimensions 432 x 200 x 163 mm (17 x 7.9 x 6.42 inch) (W x H x D) , depth including module
assembly
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificate CESI 06 ATEX 022
Marking 1 II (1)G [Ex ia Ga] IIC
1 II (1)D [Ex ia Da] IIIC
1 I (M1) [Ex ia Ma] I
Non-hazardous area
Maximum safe voltage 250 V (Attention! Um is no rated voltage.)
Galvanic isolation
Field circuit/control circuit safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 50303:2000
International approvals
UL approval E106378
Control drawing 116-0327
IECEx approval
IECEx certificate IECEx CES 06.0003