K-WANG
This is a modular automation system based on the CANbus, intended for industrial
control applications within the medium to high performance range.
The automation system is designed for use within Overvoltage Category l
(IEC 364-4-443) for the controlling and regulating of machinery and industrial
processes in low-voltage installations in which the rated supply voltage does not
exceed 1,000 VAC (50/60 Hz) or 1,500 VDC
MOOG M3000 Control System Analog I/O Extension Module
Qualified project planning and design, proper transport, storage, installation, use
and careful maintenance are essential to the flawless and safe operation of the
automation system.
The automation system may only be used within the scope of the data and applica-
tions specified in the present documentation and associated user manuals.
The automation system is to be used only as follows:
as prescribed,
in technically flawless condition,
without arbitrary or unauthorised changes and
exclusively by qualified users
The regulations of the German professional and trade associations, the German
technical supervisory board (TÜV),the VDE (Association of German electricians)
or other corresponding national bodies are to be observed.
Safety-oriented (fail-safe) systems
Particular measures are required in connection with the use of SPC in safety-
oriented systems. lf an SPC is to be used in a safety-oriented system, the user
ought to seek the full advice of theSPC manufacturer in addition to observing any
standards or guidelines on safety installations which may be available.
2.
Analog I/O expansion module
2.1. Overview
Order number
For replacement parts, the order/item no. can be found on the module's namepla
Function
The module is used to expand the analog I/O level of Cell Controllers.
The modules are connected by direct E-bus coupling and is available with voltag
or current inputs.
Features
Common characteristics
4 analog output channels
in the form of voltage outputs, +/-10 V (GND sensing)
resolution 11 bit + sign
·1 reference voltage output +10 V
·Low space requirements and low mounting depth.
The modules with voltage or current inputs also have the following features:
Module with voltage inputs:
·16 analog voltage input channels,
suitable for connecting active and passive resistors.
voltage rating,differential+/-10V
measured value resolution 11bit + sign
Module with current inputs:
.16 analog current input channels,
current rating,0...20 mA
measured value resolution 11bit + sign
Lieferumfang
Supplied with the module package is:
·An analog /O expansion module with voltage or current inputs.
2.2.
Technical data
Module data
Analog I/O expansion module
voltage or current inputs
Dimensions w x h x d [mm)
124 x 170 x 85.5 (modular dimension:B=113/118.5)
Weight
approx.550 g
Mounting
Mounting rail NS 35/7.5EN 50022
Working temperature
5°℃ to 50°℃ (no moisture condensation)
Operation and display
4 status LED's
EMC, class of protection, insulation testing, degree of protection
EMC (EN 50081-2/EN 50082-2)
To achieve the precision specified, the user
is required to implement shielding measures.
Emitted interference
EN 50081-2.industrial sector
Noise immunity
EN 50082-2.industrial sector
Class of protection
EN 61131-2
Insulation resistance
EN61131-2;500 VDC (test voltage)
Degree of protection
IP 20
Supply voltage, power consumption
Module electronics power supply
SELV DC +24V max. 0.3 A (EN 61131-2)
(supply voltage)
on AGND earth
Power consumption
at Ue= DC +24Vidling max.300 mA
Electrical isolation
yes, optodecoupled fromE bus;
no isolation between power supply and analog channels
Reverse voltage protection
yes
Connections
vertical front wiring push-on terminal strips
for screw. crimp or pinch connection
Reference voltage source
Reference voltage
DC +10V permanent short-circuit protection; lkmax 25 mA
Load current
max.5 mA
Precision
0.1%
Various characteristics
Data format in applicationprogram
Integer 16 bit
Monotonicity
yes
Cross talk between channels
-direct current
>70 dB
-50Hz
>70 dB
-60Hz
>70 dB
Non-linearity
<1LSB
Repeat accuracy at certain temperature
after 1 hour stabilising time
<1LSB
Analog inputs
Static characteristics::
voltage inputs
current inputs
Number
16
16
Type
voltage± 10V, differential
current,±20mA
Input impedance in signal range
10M Ohm
50 Ohm
Analog input error of measurement
- greatest error a 25*C
±0.1% of maximum scale value
±0.2% of maximum scale value
-temperature coefficient±0.01% of maximum scale value/°K
±0.02% of maximum scale value/*K
Greatest error over full
temperature range
±0.2 % of maximum scale value
±0.3 % of maximum scale value
LSB value
4.883 mV
9.766 μA
Max. permissible continuous overload
(exceeding this causes damage)
±30V
50 mA
User name | Member Level | Quantity | Specification | Purchase Date |
---|