Data sheet 07 KT 95 R0100 / R0200 (for further details see 07 KT 97) Order No. GJR5 2528 00 R0100 / GJR5 2528 00 R0200
ABB-07KT97R0280-Description of ARCNET
The basic unit 07 KT 97 R200 is the standard device for all applications. In addition, there are basic units with reduced performance (e.g. 07 KT 95 or 07 KT 96) as well as ones with extended performance (e.g. 07 KT 97 R260 with ARCNET connection, 07 KT 97 R0220 with PROFIBUS connection and 07 KT 97 R0262 with both ARCNET and PROFIBUS connection). A comparison table is given on page 3. This document describes the basic unit 07 KT 97 R200 and then adds the data sheets of the other devices which only show the differences.
Functionality of the basic units 07 KT 97 User program 480 kB User data 256 kB (Flash EPROM) Digital inputs 24 in 3 groups of 8 each, electrically isolated Digital outputs 16 transistor outputs in 2 groups of 8 each, electrically isolated Digital inputs/outputs 8 in 1 group, electrically isolated Analog inputs 8 in 1 group, individually configurable to 0...10 V, 0...5 V, +10 V, +5 V, 0...20 mA, 4...20 mA, Pt100 (2-wire or 3-wire), differential inputs, digital inputs Analog outputs 4 in 1 group, individually configurable to 0...10 V, 0...20 mA, 4...20 mA Serial interfaces COM1. COM 2 as MODBUS interfaces and for programming and test functions Parallel interfaces for connection of couplers 07 KP 90 (RCOM), 07 KP 93 (2 x MODBUS), 07 MK 92 (freely programmable) System bus interface CS31 Integrated couplers see next page High-speed counter integrated, many functions configurable Real-time clock integrated SmartMedia Card memory medium for operating system, user program and user data LED displays for signal conditions, operating statuses and error messages Power supply voltage 24 V DC Data backup with lithium battery 07 LE 90 Programming software 907 AC 1131
2.1.1 Brief description The basic unit 07 KT 97 works either as · bus master in the decentralized automation system Advant Controller 31 or as · slave (remote processor) in the decentralized automation system Advant Controller 31 or as · stand-alone basic unit. The basic unit is powered by 24 V DC. 2.1.1.1 Main features · 24 digital inputs with LED displays · 16 digital transistor outputs with LED displays · 8 digital inputs/outputs with LED displays · 8 individually configurable analog inputs 0...10 V, 0...5 V, ±10 V, ±5 V, 0...20 mA, 4...20 mA, differential inputs, Pt100 (2-wire or 3-wire), the analog inputs are also individually configurable as digital inputs · 4 individually configurable analog outputs ±10 V, 0...20 mA, 4...20 mA · 2 counters for counting frequencies up to 50 kHz, configurable in 7 different operating modes · 1 CS31 system bus interface for system expansion · 1 interface for connecting communication modules (e.g. 07 KP 90) · 2 serial interfaces COM1. COM2 – as MODBUS interfaces and – for programming and test functions · Real-time clock · LEDs for displaying operating conditions and error messages · Detachable screw-type terminal blocks · Fastening by screws or by snapping the device onto a DIN rail · The lithium battery 07 LE 90 can be put into the battery compartment in order to – store and backup the user program in the RAM – store and backup data which is additionally contained in the RAM, e.g. the status of flags – backup the time and date (real-time clock) · RUN/STOP switch for starting and aborting the program execution · Extensive diagnosis functions – self-diagnosis of the basic unit – diagnosis of the CS31 system bus and the connected modules · Integrated Flash EPROM for storing program and data · Exchangeable SmartMedia Card 07 MC 90 for user data or for updating the operating system or PLC program 2.1.1.2 Project planning / start-up The following has to be observed for project planning and start-up: · Programming is performed with AC31 programming software, which can be run on commercially available IBM compatible PCs (see documentation of the programming system 907 AC 1131). · Online program modification A quick modification of the user program is possible without interrupting the operation (see programming system 907 AC 1131). · Possible operating modes – Stand-alone basic unit – Bus master basic unit – Slave basic unit · Backup of data areas, i.e. saving of data during power OFF/ON, is possible with an integrated battery and/or by storing them in the Flash EPROM.
User name | Member Level | Quantity | Specification | Purchase Date |
---|