Diagnosis control shows the status of the CI801 and node specific errors and warnings. Module specific diagnosis are displayed in the Diagnosis control for each I/O module.
ABB CI801 I/O module
Device state area
This text field shows the actual state of the FCI. Either the state is Operational or
the text field is left blank.
Device diagnostics area
The device specific errors that are detected for the CI801 are:
• Station warning
At least one error is detected within the entire CI801 station (including
I/O modules etc.).
• Redundant power A failure
Power fail on the optical modem.
• Redundant power B failure
Power fail on the optical modem
Station address warning
There is a mismatch between the actual address on the CI801 and the one
configured in the system or if the address is set above 62. The warning will be
cleared when the system is restarted with the right configuration or if the switch on
the CI801 is changed back to the configured address.
Configuration
For configuration of the module, select the “Configuration” menu item.
This control is not available if the unit is used towards AC 800M. The
configuration data is then set via Control Builder Professional.
Figure 21. CI801 - Configuration for AC870P
Power supervision of opto extension
Mark the check box if the voltage supply to the cluster shall be supervised.
Only if redundant power supply.
• Extended HART mode
Normal mode shall always be used if HART data is < 56 bytes. Mark the check
box if the HART data is > 56 bytes but < 215 bytes. If Extended HART mode
is chosen less I/O modules can be used. See S800 I/O Manuals for more details.
• HCIR Enable
Hot Configuration In Run active
• HCIR Factor
Hot Configuration In Run Factor
• HCIR Watchdog
Hot configuration In Run Worst Case Bus Cycle Base