K-WANG
This document describes the system configurations, development/maintenance, software configurations, network and specifications, for two types of autonomous controllers in the STARDOM: FCN with NFCP100 CPU module and FCJ. (FCN is an acronym for f
YOKOGAWA FCN/FCJ Autonomous Controller Function
Notation in this document:
• The term “FCN” refers to the module consisting type
autonomous controllers.
• The term “FCN-500” refers to the autonomous
controllers with NFCP501/NFCP502 CPU module.
• The term “FCN-100” refers to the autonomous
controllers with NFCP100 CPU module.
• The term “FCN-RTU” refers to the low power
autonomous controllers with NFCP050 CPU module.
• The term “FCJ” refers to the all-in-one type
autonomous controllers.
High Performance
• Applicable to a variety of processes, from sequence
control processes to analog control processes.
• Intercommunication with other autonomous
controllers or other equipment for inter-linked control
actions, in addition to stand-alone operation.
• Using Versatile Data Server Software (VDS) or
Supervisory Systems (FAST/TOOLS) together allows
a system with enriched operation and monitoring
functions to be built up.
• An FCN/FCJ OPC server for Windows can be used
for accessing the data of an FCN/FCJ from an OPC
(OLE for Process Control) client on a PC.
• Java-enabled — enables users to implement various
applications, including displaying images on a Web
browser, saving data files, transferring files using the
FTP protocol, sending/receiving e-mails and public
network connection using the PPP protocol.
With InfoWell, applications such as web browsers
and e-mail communications can be utilized without
programming.
l High Reliability
• RAS features (CPU self-diagnostics, temperature
monitoring, I/O diagnostics, and more)
• Memory with error-correcting code (ECC)
• Low heat dissipation, eliminating the need for a
cooling fan
• The Ethernet control network, CPU, power supply
module, and SB bus (FCN local bus) can all be
duplexed for an FCN-100.
• The control network can be duplexed for an FCJ.
l Engineering Efficiency
• Five IEC 61131-3 compliant programming languages
are supported, enabling the user to selectively use
these languages according to their purposes of use
and applications.
• Control logic can be encapsulated into software
parts for reuse, allowing efficient and quality system
configuration.
• Application Portfolios packed with Yokogawa’s
application expertise, enable easy implementation of
advanced functions, including control-loop instrument
blocks and communication with non-Yokogawa PLCs.
l Easy Maintenance
• Online download function allows a control application
to be modified during system operation
• All modules are hot-swappable with an F
FCN-100 is a controller module consisting of CPU, I/O,
and other modules as necessary. It supports a variety
of I/O modules, provides a highly reliable system with
duplexed power supply, CPU and control network
options as well as superb scalability.
For hardware details, refer to FCN Autonomous
Controller Hardware (FCN-100), GS 34P02Q12-01E
FCJ is an all-in-one controller with a built-in I/O
interface — ideal for installing inside machine
equipment as well as configuring a distributed system.
Its control network can be duplexed.
For hardware details, refer to FCJ Autonomous
Controller Hardware, GS 34P02Q11-01E
System Configurations Resource Configurator is a tool program to be installed
Both FCN and FCJ are locally mounted controllers to
allow diverse systems to be configured according to
in the computer used for maintenance, and is used to
make the FCN/FCJ hardware settings.
the individual users’ work sites; however, the possible The user can access FCN and FCJs via a Web browser
system configurations can be broadly divided into three from a PC to make detailed settings for the network
types: and so on, and to perform maintenance operations
• A system consisting of a standalone FCN or FCJ such as database backup and restoration.
• A system in which FCNs and/or FCJs are connected Logic Designer is a tool program for the development
to each other through the control network and of control applications for an FCN/FCJ. Logic Designer
perform interlinked actions (up to a total of 15 FCNs requires a license to run.
and FCJs can intercommunicate with one FCN/FCJ). These tool programs are supplied on a DVD-ROM. • A system in which one or more FCNs and/or FCJs
are interlinked with VDS, FCN/FCJ OPC Server or
FAST/TOOLS (up to a total of 4 VDSs, FCN/FCJ SPECIFICATIONS
OPC Servers and FAST/TOOLS can be connected).
l CPU Function Specifications
Using a communication portfolio within an Application Execution Speed:
Portfolio allows an FCN/FCJ to communicate with other Approx. 50 µs per kilosteps in an IL
kinds of controllers and devices. program
Number of Control Applications: Max. 16 tasks
Control network (Ethernet) Task Priority: Can be specified (in 16 levels)
Data
Data communication
Data
Task Execution Cycle:
10 ms or longer (by 10 msec. increments) communication communication
l CPU Memory Capacity
Control Application Capacity:
Max. 3 MB (approx. 400 kilosteps in an IL
program)
Data Area (*1): Max. 8 MB
Retained Data Area (*2): Max. 410 KB (*3)
Java Application Capacity: Max. 32 MB
*1: The data is not retained when the power is off.
*2: The data is retained even if the power is off. The
User name | Member Level | Quantity | Specification | Purchase Date |
---|