Introduction The DeltaV M-series Virtual I/O Module 2 (VIM2) provides nonintrusive simulation of the DeltaV Mseries I/O Cards and digital bus field devices for process simulation when used with MYNAH Technologies’ MiMiC Simulation Software. DeltaV Control strategies and system configurations can be fully tested with this powerful simulation interface.
Emerson M-series Virtual I/O Module2
The VIM2 also provides an interface to Ethernet I/O
networks and devices that use the Modbus TCP/IP
or Ethernet/IP protocol drivers. DeltaV M-series
controllers can read and write signals from plant
floor devices connected to Ethernet I/O networks
such as PLC’s, Motor Control Centers, and Weigh
Scales.
Benefits
Non-Intrusive DeltaV I/O simulation. Use the VIM2
in conjunction with the MYNAH Technologies’ MiMiC
Simulation Software to simulate your DeltaV M-Series
I/O and digital bus field devices.
Supports DeltaV I/O modules. Provides completely
non-intrusive simulation of all DeltaV M-series I/O
Modules. Supports autosensing of I/O and accurate
testing of controller loading. DeltaV configuration can
be fully tested without modifying the control
strategies.
Digital bus support. Provides simulation of all
DeltaV Digital Busses and Foundation Fieldbus
function blocks. Supports Foundation Fieldbus control
in the field configuration testing.
Powerful simulation solution. Provides full
simulation of up to 64 DeltaV I/O modules per
controller. Simulation execution is fast and efficient;
the DeltaV controller thinks it’s talking with real IO.
Powerful integration solution. Use the VIM2 in
conjunction with the MYNAH Ethernet I/O drivers to
integrate your DeltaV system with your Ethernet I/O device
networks.
Large device capacity. Each VIM emulates four
DeltaV Serial Cards and support up to 128 Serial
Card Datasets of information from 32 network devices
in simplex installations and 16 devices in redundant
installations. Communication over the Ethernet I/O
device network is fast and efficient.
Flexible networking. User configurable IP
addressing allows the VIM2 to be used in almost any
plant environment regardless of networking scheme.
The VIM2 and the Ethernet I/O devices must be on
the same IP subnet to communicate.
1:1 Redundancy. Redundancy can be added to any
Ethernet I/O system by adding a second VIM2 and
configuring the two cards as a redundant pair. The
VIM2 appears as four redundant DeltaV Serial Card
pairs. Automatic switchover of primary to standby
cards is handled like the DeltaV Serial Card. The
operator is given clear notification of a switchover at
the operator display. Manual switchover can be
controlled in DeltaV Diagnosti
Automatic updates. Simulation I/O driver updates for
the VIM2 are included with the MiMiC software
releases. Updates are quick and easy over the
simulation network.
Seamless Ethernet I/O integration. When used with
the MYNAH Ethernet I/O drivers, the VIM2 is seen by
the DeltaV M-series controller as four DeltaV Serial
Cards. Commissioned VIM2s are auto-sensed by the
DeltaV controller as DeltaV Serial Cards.
Configured in DeltaV Explorer. Serial dataset
configuration used for Ethernet I/O integration is done
in the DeltaV Explorer in the same manner as a
DeltaV Serial Card. Ethernet I/O signals can be used
in DeltaV Control Modules, displayed on DeltaV
Operate graphics and stored in the DeltaV
Continuous Historian.
Intuitive setup. The VIMNet Explorer application
provides plug-n-play capability making setup of the
VIM2 easy and intuitive. Graphical, drag-n-drop,
functionality makes setting up multiple VIM2s almost
effortless. VIMNet Explorer is integrated with DeltaV
Explorer to make setup of the VIM2 easy and intuitive.
Modular, flexible packaging. The VIM2 mounts in the
same manner as the DeltaV controller. It mounts in the
controller slot of a DeltaV 2-wide horizontal or 4-wide
vertical carrier and uses a standard DeltaV Power Supply.
The advanced design of the VIM2 will provide years of
uninterrupted use.
IO Simulation When used with MYNAH’s MiMiC
Simulation Software, the VIM2 supports I/O simulation all
DeltaV M-series I/O cards including classic IO, Foundation
Fieldbus, ProfibusDP, DeviceNet, ASi-bus and Serial.
MiMiC Simulation Software provide dynamic simulation for
DeltaV system software acceptance testing and operator
training. The MiMiC software works by simulating the
DeltaV I/O. It also simulates field devices using
Foundation Fieldbus, ProfibusDP, DeviceNet and AS-i
buses. In order for MiMiC to do this, the real I/O cards are
disconnected from the control system. The MiMiC driver
writes to the I/O subsystem of the DeltaV controller.
Process models in MiMiC simulate realistic process
reactions to control system output signals.
Each process controller being simulated uses one MiMiC
Dataset. A MiMiC server can have up to 32 datasets or
ports. Each dataset can support up to 4000 MiMiC
simulation tags.
The I/O simulation driver is provided with the VIM2
hardware, pre-loaded in the VIM2. The MiMiC Simulation
Software must be purchased separately from MYNAH
Technologies. Technical support for the MiMiC Simulation
Software and I/O simulation driver is provided by MYNAH
Technologies.
Ethernet I/O Integration When used with the MYNAH
Ethernet I/O drivers, the VIM2 can communicate with
high-speed Ethernet networks over Modbus TCP or
Ethernet/IP. When the VIM2 is configured with the
appropriate Ethernet I/O driver, the DeltaV Controller autosenses a commissioned VIM2 as four DeltaV Serial Cards.
In simplex installations these cards will be sensed in
slots 57-60 or 61-64.
In redundant installations the redundant pairs will be
sensed in slots 57 to 64.
Configuration of the I/O signals from the commissioned
VIM2 is done in the DeltaV Explorer in the same manner
as a DeltaV Serial Card.
VIMNet Explorer. The VIMNet Explorer utility allows the
user to commission the VIM2. setup primary and
redundant VIM2s, and the Ethernet I/O network. The useris able