The module receives power from the backplane power supply. No external power source is required for module operation. Power for the user’s transceivers must be supplied from an external source.
GE IC200ALG264 Analog Input Module
Module features include:
Fifteen single-ended input channels, one group
Jumper selection of 4-20mA or 0-20mA operating range
Fifteen bit converter resolution
Software-configurable selection of default/hold last state operation
Host Interface________________________________________
The module provides 15 words of analog input data.
Diagnostics _________________________________________
The module reports a Loss of Internal Power fault for field-side circuits.
The module reports an Open Wire fault for each channel, when in 4-
20mA mode.
LED Indicators _______________________________________
The green OK LED is on when backplane power is present, internally
generated field power is functioning properly, the module has been
configured, and the module has been recognized on the backplane.
Configuration Parameters ______________________________
A jumper on the carrier terminals can be used to configure 4-20mA or
0-20mA input ranges. With no jumper installed, the module accepts 4-
20mA input signals. With a jumper installed, the module accepts 0-
20mA input signals.
The analog inputs are software-configurable to either default or hold last
state upon a loss of module
Module Characteristics
Channels 15 single ended, one group
Module ID FFFFB50F (when cfg for 4-20mA range)
FFFFB40F (when cfg for 0-20mA range)
Isolation:
User input to logic (optical)
and to frame ground
Group to group
Channel to channel
250VAC continuous; 1500VAC for 1 minute
Not applicable
None
LED indicators OK LED indicates successful power-up and
configuration
Thermal derating None
Backplane current consumption 5V output: 100mA maximum
External power supply None
Configuration parameters Range select (terminal jumpers)
Diagnostics Loss of Internal Power,
Open wire detection of 4-20mA signals only
Input Characteristics
Input current 4 to 20mA (default: no terminal jumper installed)
0 to 20mA (with terminal jumper installed)
Input Impedance 100 Ohms
Accuracy at:
25 degrees C *
0 to 60 degrees C
+/-0.3% typical of full scale,
+/-0.5% maximum of full scale
+/-1% maximum of full scale
Resolution 15 bits
0.5µA = 1 counts (for 4-20mA range)
0.625µA = 1 counts (for 0-20mA range)
Filter response
(3dB Corner Freq)
24 Hz +/-20%
Update rate 7.5ms
* In the presence of severe RF interference, (IEC 1000-4-3. 10V/m), accuracy may be
degraded to +/-2%.
Preinstallation Check ________________________________
Carefully inspect all shipping containers for damage. If any equipment is
damaged, notify the delivery service immediately. Save the damaged
shipping container for inspection by the delivery service. After unpacking the
equipment, record all serial numbers. Save the shipping containers and
packing material in case it is necessary to transport or ship any part of the
system.
Terminal assignments for the module are shown below.
Number Connection Number Connection
A1 I1 B1 No connection
A2 I2 B2 No connection
A3 I3 B3 No connection
A4 I4 B4 No connection
A5 I5 B5 No connection
A6 I6 B6 No connection
A7 I7 B7 No connection
A8 I8 B8 No connection
A9 I9 B9 No connection
A10 I10 B10 No connection
A11 I11 B11 No connection
A12 I12 B12 No connection
A13 I13 B13 No connection
A14 I14 B14 No connection
A15 I15 B15 No connection
A16 Range JMPR B16 No connection
A17 RTN B17 No connection
A18 NC B18 No connection
Wiring Connections for Carriers with Two Rows of Terminals
The diagram below shows wiring connections for this module when
installed on a carrier with two rows of terminals.
1 2 3 4 5 6 7 8 9 11 12 13 14 15 16 17 18 10
I1 Range
JMPR I2 I3 I4 I5 I6 I7 I8 I9 I10 I11 I12 I13 I14 I15
A
Wiring Connections for Carriers with Three Rows of Terminals
The next diagram shows wiring connections for this module when
installed on a carrier with three rows of terminals.