ABB 1TGE121011R1200 Motor and feeder control unit for MNS iS
The concept of the RTU560 with its module concept and 19”set up,allows the use of differenthousing arrangements.According to the place
restrictions and local (country specific) isolation
requirements the cubicles/cabinets can be designed accordingly.
Swing frame solution
A swing frame set up gives a maximum of flexibility for different process connections. Terminal
blocks on the back plane with or without disconnecting possibilities,external marshalling cabinets
or cross wiring within the cubicles are just a few
to mention
The modules conform to the standard European
format for insertion in a 19" rack.By utilizing surface-mounted devices and multi-layer circuit
boards,a high integration density is achieved on
the modules. These high-density printed circuit
boards result in compact terminals,thus providing
a highly functional capability.
The RTU560 hardware system includes all the
boards and modules needed for an RTU. The basic
boards are listed in this brochure in the Technical
Data chapter. Additional boards and modules can
be found in the hardware documentation.
The RTU560 can be supplied with an input voltage
between 24 and 220V DC or 110 … 230V AC via
an additional AC/DC converter.
The RTU560 is designed to run redundant power
supplies. The two power supplies are each designed for 100% of the load.During normal operation,they share the load.Each module can be
plugged in or pulled out during operation.
The RTU560 is approved to be CE compliant and
checked to the EMC/EMI standards specified for
telecontrol units in IEC 60870-2-1.
Communication Modules
The RTU560 CMU boards are based on the PC 104
concept. A PC 104 main board contains the kernel
of a personal computer (PC) and has become standard recently.It allows the easy integration of standard PC-based software as well as easy adaptation
to specific hardware extensions.
Following these standards secures your investment
and ensures the easy adaptation to subsequent
CMU generations by simply replacing the PC 104
main board with the current version.
CMU modules available:
• Serial Line Interface board 560SLI02
• Ethernet Adapter board 560ETH03
• Communication Unit 560CMU04
• Communication Unit 560CMU80
Each CPU communication board has an additional
serial interface for MMI to a PC. The MMI is used
for diagnostics,up and download of configuration
files,etc.
I/O Boards
Only five I/O board types are needed to cover the
main requirements for the I/O signals connected to
the RTU. This is possible because of a microprocessor-controlled kernel module which is identical on
all types of I/O boards,whereas the individual I/O
function is provided by type specific hardware circuit extensions to the kernel.
• Binary Input Board 23BE21
• Binary Output Board 23BA20
• Binary Output Supervision Board 23BA22
• Analog Input Board 23AE21
• Analog Output Board 23AA20
Direct interfacing of 110-220 V DC binary IO
without interposing relays is possible with:
• Binary Input Board 23BE40
• Binary Output Board 23BA40
Modems
For communication with telecontrol lines differnt
types of FSK Modems are available:
• Universal FSK Modem 23WT22
• V.23 Modem 23WT23
• 9600 bps FSK Modem 23WT24
For fibre optic communication are available:
• fibre optic coupler 23OK22
RTU560 does also provide interfaces to all kind of
analog and digital comminication equipement.

Configurable Process Data Points
Overall total per RTU560 approx.3000 directly connected data
points,including data points from IEDs and subordinate RTUs.
Higher volumes are possible on request.
I/O Boards
Binary Input Board 23BE21
Inputs: 16,optically isolated
Input voltage: 24 ...60 V DC
Binary Output Board 23BA20
Outputs: 16,relay single pole
max.operating voltage: 60 V DC
Switching capacity: 40 VA (L/R=30 ms)
Analog Input Board 23AE21
Inputs: 8 differential inputs
Input range: 2/5/10/20/40 mA
uni-,bipolar or live zero
+/-2 V DC,0..20 V DC
Accuracy: < 0,1%
Resolution: 12 bit + sign
Analog Output Board 23AA20
Outputs: 2,galvanically isolated
Output current: 2,5/5/10/20mA
uni-,and bipolar,
4 ...20 mA
Multi I/O Board 560MIO80 (RTU560E)
Binary Inputs: 16,optically isolated
Input voltage: 24 ...60 V DC or
110 ...220 V DC
Binary Outputs: 8,relay single pole
Max.operating voltage: 60 V DC or 220 V DC
Switching capacity: 40 VA (L/R =30 ms) or
50 VA (L/R=40 ms)
Analog Inputs: 4 differential inputs
Accuracy: < 0,1%
Resolution: 12 bit + sign
Binary Input Board 23BE40
Inputs: 16,optically isolated
Input voltage: 110 ...220 V DC
Binary Output Board 23BA40
Outputs: 16,relay single pole
Max.operating voltage: 220 V DC
Switching capacity: 50 VA (L/R=40 ms)
Communication Board
Serial Line Interface 560SLI02
Serial Line Interfaces: 2 x RS 232C or RS 485
2 x RS 232C or RS 422
1 x MMI RS 232C
Ethernet Interface 560ETH03
Ethernet: 10 Mbit/s,10 Base T
Serial Line Interfaces: 2 x RS 232C or RS 485
1 x MMI RS 232C
Communication Unit 560CMU04
Ethernet: 100Mbit/s,10/100 BaseT
Serial Line Interfaces: 4 x RS 232C or RS 485
1 x MMI RS 232C
Communication Unit 560CMU80 (RTU560E)
Serial Line Interfaces: 2 x RS232C,1 x RS485
1 x MMI RS 232C
Ethernet (Option): 10 Mbit/s,10 Base T
Modems
FSK Modem 23WT22: FSK Modem,CCITT channels
50 ...2400 bit/s
V.23 Modem 23WT23: CCITT V.23,1200 bit/s
2/4 wire,half- or full duplex
FSK Modem 23WT24: 9600 bit/s
2/4 wire,half- or full duplex
V23 Modem 560MOD80
(RTU560E): CCITT V.23,1200 bit/s
2 wire,half duplex
Analog Modem 560MOD81
(RTU560E): CCITT V.34+,33.600 Bit/s
Opto-Coupler 23OK22: 1 fiber optic channel to various serial
interaces configurable max.distance
2600 m
Real Time Clock Boards
GPS Board 560RTC01: with extenal antenna
DCF 77 Board 560RTC02: with extenal antenna
Power Supply Boards
Power Supply Board 560PSU01
for redundant operation: 24 ...60 V DC or 110 ...220 V DC
- 20% / + 15%
RTU560E Power Supply
560PSU80: 24 ...60 V DC or 110 ...220 V DC
- 20% / + 15%
RTU560E Power Supply
560PSU81: 115 ...230 V AC
Mechanics
RTU Board Type: Single European Standard
Communication Subrack
560CSR01: 19" Rack,max.8 CPU + 2x PS +RTC
No.of 560CSR01 max.2 per RTU560
I/O subrack for hinged
frame 23ET23: 19" Rack,max.19 I/O boards + PS
I/O subrack mouning
plate 23TP21: 19" Rack,max.19 I/O boards + PS
Number of I/O subracks: max.28 per RTU560
RTU560E compact housing
366x258x310 mm (HxWxD)
CE Declaration
EMC Immunity: EN 50082-2:1995
EMI Emmission: EN 50081-2:1993
Safety: EN 60950:1999
Environmental Conditions
Temperature: - 10 ...+ 55 °C
- 20 ...+ 55 °C (RTU560E)
Relative humidity: 5 ...95 % non-condensing