Honeywell Analog Output, 0 to 20mA, (4 channel)900B01-0301
Digital Output – AC Type (900H03-xxxx)The AC Digital Output module provides 8 isolated zero
switching Triac solid-state outputs. A shorting comb is
available for use with barrier type terminal blocks to
simplify connections to a common voltage source for all
outputs. Each output has a MOV for transient overvoltage protection and a field-replaceable fuse.
There is a green LED state indicator for each channel on
the module to indicate when a digital output is ON.
A green blinking status LED on the module indicates
when the module is being scanned. An amber blinking
status LED indicates when channels are forced and a red
status LED when module diagnostics exist..
Outputs per Module 8
Galvanic Isolation Per output to output, output to logic
Operating Voltage 85 VAC to 240 VAC
Output Type Triac (zero switching voltage)
Peak Voltage 250 VAC
AC Frequency 47 Hz to 63 Hz
ON Voltage Drop <2.0 VAC (>0.1 A)
<3.0 VAC (<0.1 A)
Transient Over voltage
Protection
MOV
Maximum Load Current 2 A per point, 8 A max. per module,
resistive load
Maximum Leakage Current 4 mA (240 VAC, 60 Hz)
1.2 mA (100 VAC, 60 Hz)
0.9 mA (100 VAC, 50 Hz)
Maximum Inrush Current 15 A for 10 ms
Minimum Load 50 mA
OFF to ON response time* 3 ms + 0.5 line cycle max
ON to OFF response time* 3 ms + 0.5 line cycle max
Fuses 1 per output, 3.15 A Time-lag.
Replacement part: Littelfuse
37413150410
Power Supply Loading 5V; 220mA max
24V; 0mA
*excluding controllers scan time and excluding transmission time from module to backplane

32 Point Digital Output Module – DC Type (900H32-xxxx)
The DC digital Output module provides 32 outputs
separated in to 2 groups of 16 channels each that are
powered externally. Each group has a pair of screw
terminals for +V and COM connections. The outputs are
high side switching (current sourcing) type. Over current
protection is provided for all outputs in 4 groups of 8
channels each. In case of short circuit for any output
channel, that whole group of 8 is switched off. Power
cycling is not required to reset the module.
There is a green LED state indicator for each channel on
the module to indicate when a digital output is ON.
A green blinking status LED on the module indicates
when the module is being scanned. An amber blinking
status LED indicates when channels are forced and a red
status LED when module diagnostics exist. Requires
Euro style 36-terminal terminal block.
Outputs per module 32 (current sourcing, high
side).
Note: Outputs 17 through 32
may not be used for TPO
(Time Proportioning Output),
PPO (Position Proportioning
Output) or TPSC (Three
Position Step Output) output
types.
Galvanic Isolation 2 groups of 16 outputs
Operating Voltage 10.5 to 32 VDC
Output Type High side driver
Peak Voltage 32 VDC
AC Frequency N/A
ON Voltage Drop 0.15 VDC @ 0.5 A load
Overload Protection Active Current Limiting is
integrated into the output
driver as 4 groups of 8
channels each. Power cycling
is not required to reset the
module after a fault condition.
Maximum Load
Current
0.5 A per point, 6 A max per
channel group
12 A max. per module,
resistive load
0.25 A per point incandescent
lamp load
(5 mH max)
Maximum Leakage
Current
0.15mA @ 32 VDC
Maximum Inrush
Current
2 A for 10 ms
Minimum Load 0.0 mA
OFF to ON response
time*
6 ms
ON to OFF response
time*
6 ms
Fuses Electronic limiting
Power Supply Loading 5V; 235mA
24V; 0mA
*excluding controllers scan time and excluding
transmission time from module to backplane